1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
16.00 kW
16.00 kW
El input
3.54 kW
5.59 kW
COP
4.52
2.86
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
66 dB(A)
66 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
129 %
Prated
13.00 kW
16.00 kW
SCOP
4.46
3.31
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.50 kW
14.20 kW
COP Tj = -7°C
2.70
1.86
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
7.00 kW
8.60 kW
COP Tj = +2°C
4.43
3.30
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
8.00 kW
7.90 kW
COP Tj = +7°C
5.68
4.31
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
9.30 kW
9.20 kW
COP Tj = 12°C
7.28
5.55
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
13.00 kW
16.00 kW
COP Tj = Tbiv
2.70
1.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.00 kW
16.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.70
1.67
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
55 °C
55 °C
Poff
12 W
12 W
PTO
14 W
14 W
PSB
12 W
12 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
6018 kWh
9984 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
87 %
COP
2.00
Heating up time
0:48 h:min
Standby power input
80.0 W
Reference hot water temperature
47.9 °C
Mixed water at 40°C
232 l