1,800 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.33 kW
6.94 kW
El input
0.93 kW
2.41 kW
COP
4.66
2.88
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
53 dB(A)
53 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
128 %
Prated
8.00 kW
6.80 kW
SCOP
4.45
3.29
Tbiv
-5 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.02 kW
6.02 kW
COP Tj = -7°C
3.16
2.22
Cdh Tj = -7 °C
0.970
0.960
Pdh Tj = +2°C
4.31 kW
3.66 kW
COP Tj = +2°C
4.70
3.29
Cdh Tj = +2 °C
0.970
0.960
Pdh Tj = +7°C
4.44 kW
4.27 kW
COP Tj = +7°C
5.63
4.27
Cdh Tj = +7 °C
0.970
0.960
Pdh Tj = 12°C
5.04 kW
4.97 kW
COP Tj = 12°C
6.66
5.48
Cdh Tj = +12 °C
0.970
0.960
Pdh Tj = Tbiv
6.46 kW
6.02 kW
COP Tj = Tbiv
3.36
2.22
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.74 kW
5.77 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
1.93
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.960
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
43 W
39 W
PSB
27 W
27 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.26 kW
1.03 kW
Annual energy consumption Qhe
3714 kWh
4275 kWh