Certificate holders

Subtype

Aquarea Monobloc 16 kW T-CAP (J Series) + TD30

Certificate Holder
Panasonic Marketing Europe GmbH
Hagenauer Strasse 43, Wiesbaden
65203 Wiesbaden
Germany
Registration number
011-1W0564
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Aquarea Monobloc 16 kW T-CAP (J Series) + TD30
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,800 kg

Certification Date
22.12.2022
Testing basis
European KEYMARK Scheme for Heat Pumps Rev. 10 (as of 2022-06)
Generate PDF Export model CSV
  • Number of models 2

Models

WH-MXC16J9E8
Configure model
Model name
WH-MXC16J9E8
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.54 kW

5.59 kW

COP

4.52

2.86

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

232 %

160 %

Prated

16.00 kW

16.00 kW

SCOP

5.88

4.09

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

16.00 kW

16.00 kW

COP Tj = +2°C

2.96

2.03

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

10.30 kW

10.30 kW

COP Tj = +7°C

5.32

3.56

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

9.10 kW

8.90 kW

COP Tj = 12°C

7.25

5.21

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

16.00 kW

16.00 kW

COP Tj = Tbiv

2.96

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.00 kW

16.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.96

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3634 kWh

5230 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

150 %

125 %

Prated

19.00 kW

18.00 kW

SCOP

3.83

3.20

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

11.50 kW

10.90 kW

COP Tj = -7°C

2.69

2.57

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.10 kW

6.80 kW

COP Tj = +2°C

5.04

3.97

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

8.00 kW

7.90 kW

COP Tj = +7°C

6.35

5.04

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

9.10 kW

9.00 kW

COP Tj = 12°C

7.59

6.31

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.50 kW

14.70 kW

COP Tj = Tbiv

2.42

1.83

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.30 kW

13.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.91

1.39

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.70 kW

4.60 kW

Annual energy consumption Qhe

12233 kWh

13870 kWh

Pdh Tj = -15°C (if TOL<-20°C)

15.50

14.70

COP Tj = -15°C (if TOL<-20°C)

2.42

1.83

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

129 %

Prated

13.00 kW

16.00 kW

SCOP

4.46

3.31

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.50 kW

14.20 kW

COP Tj = -7°C

2.70

1.86

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.00 kW

8.60 kW

COP Tj = +2°C

4.43

3.30

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

8.00 kW

7.90 kW

COP Tj = +7°C

5.68

4.31

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

9.30 kW

9.20 kW

COP Tj = 12°C

7.28

5.55

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

13.00 kW

16.00 kW

COP Tj = Tbiv

2.70

1.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.00 kW

16.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

1.67

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6018 kWh

9984 kWh

WH-MXC16J9E8 + PAW-TD30C1E5-HI
Configure model
Model name
WH-MXC16J9E8 + PAW-TD30C1E5-HI
Application
Heating + DHW + low temp
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.54 kW

5.59 kW

COP

4.52

2.86

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

232 %

160 %

Prated

16.00 kW

16.00 kW

SCOP

5.88

4.09

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

16.00 kW

16.00 kW

COP Tj = +2°C

2.96

2.03

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

10.30 kW

10.30 kW

COP Tj = +7°C

5.32

3.56

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

9.10 kW

8.90 kW

COP Tj = 12°C

7.25

5.21

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

16.00 kW

16.00 kW

COP Tj = Tbiv

2.96

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.00 kW

16.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.96

2.03

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3634 kWh

5230 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

150 %

125 %

Prated

19.00 kW

18.00 kW

SCOP

3.83

3.20

Tbiv

-15 °C

-15 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

11.50 kW

10.90 kW

COP Tj = -7°C

2.69

2.57

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.10 kW

6.80 kW

COP Tj = +2°C

5.04

3.97

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

8.00 kW

7.90 kW

COP Tj = +7°C

6.35

5.04

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

9.10 kW

9.00 kW

COP Tj = 12°C

7.59

6.31

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.50 kW

14.70 kW

COP Tj = Tbiv

2.42

1.83

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.30 kW

13.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.91

1.39

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.70 kW

4.60 kW

Annual energy consumption Qhe

12233 kWh

13870 kWh

Pdh Tj = -15°C (if TOL<-20°C)

15.50

14.70

COP Tj = -15°C (if TOL<-20°C)

2.42

1.83

Cdh Tj = -15 °C

0.900

0.900

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

66 dB(A)

66 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

129 %

Prated

13.00 kW

16.00 kW

SCOP

4.46

3.31

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

11.50 kW

14.20 kW

COP Tj = -7°C

2.70

1.86

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

7.00 kW

8.60 kW

COP Tj = +2°C

4.43

3.30

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

8.00 kW

7.90 kW

COP Tj = +7°C

5.68

4.31

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

9.30 kW

9.20 kW

COP Tj = 12°C

7.28

5.55

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

13.00 kW

16.00 kW

COP Tj = Tbiv

2.70

1.67

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.00 kW

16.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.70

1.67

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

12 W

12 W

PTO

14 W

14 W

PSB

12 W

12 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6018 kWh

9984 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

134 %

COP

3.23

Heating up time

1:17 h:min

Standby power input

40.0 W

Reference hot water temperature

52.7 °C

Mixed water at 40°C

390 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

81 %

COP

1.88

Heating up time

1:09 h:min

Standby power input

120.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

388 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

116 %

COP

2.77

Heating up time

1:00 h:min

Standby power input

50.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

386 l