Certificate holders

Subtype

DAIKIN ALTHERMA 3 M 6kW

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Registration number
011-1W0528
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA 3 M 6kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,350 kg

Certification Date
18.05.2022
Testing basis
HP KEYMARK certification scheme rules rev. 9
Generate PDF Export model CSV
  • Number of models 4

Models

EBLA06E3V3
Configure model
Model name
EBLA06E3V3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

5.8 kW

El input

1.24 kW

2.15 kW

COP

4.85

2.7

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.55 kW

Cooling capacity

5.09

EER

3.28

EN 14825

+7°C/+12°C

Pdesignc

5.1 kW

SEER

5.31

Pdc Tj = 35°C

5.09 kW

EER Tj = 35°C

3.28

Pdc Tj = 30°C

3.75 kW

EER Tj = 30°C

4.75

Cdc Tj = 30 °C

0.987

Pdc Tj = 25°C

2.47 kW

EER Tj = 25°C

6.21

Cdc Tj = 25 °C

0.975

Pdc Tj = 20°C

2.52 kW

EER Tj = 20°C

7.08

Cdc Tj = 20 °C

0.972

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

576 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

257 %

162 %

Prated

6 kW

5.6 kW

SCOP

6.51

4.13

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

6 kW

5.6 kW

COP Tj = +2°C

3.5

2.15

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.9 kW

3.6 kW

COP Tj = +7°C

5.92

3.45

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

2.7 kW

2.3 kW

COP Tj = 12°C

8

5.48

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6 kW

5.6 kW

COP Tj = Tbiv

3.5

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

5.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.5

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

1232 kWh

1813 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

7 kW

7 kW

SCOP

4.52

3.28

Tbiv

-6 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6 kW

5.9 kW

COP Tj = -7°C

2.86

1.98

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

3.9 kW

3.9 kW

COP Tj = +2°C

4.25

3.16

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.2 kW

3 kW

COP Tj = +7°C

6.3

4.49

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

3.3 kW

3.3 kW

COP Tj = 12°C

7.78

6.1

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6.1 kW

6.1 kW

COP Tj = Tbiv

3.07

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.01 kW

5.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.53

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.64 kW

Annual energy consumption Qhe

3196 kWh

4405 kWh

EBLA06EV3
Configure model
Model name
EBLA06EV3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

5.8 kW

El input

1.24 kW

2.15 kW

COP

4.85

2.7

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.55 kW

Cooling capacity

5.09

EER

3.28

EN 14825

+7°C/+12°C

Pdesignc

5.1 kW

SEER

5.31

Pdc Tj = 35°C

5.09 kW

EER Tj = 35°C

3.28

Pdc Tj = 30°C

3.75 kW

EER Tj = 30°C

4.75

Cdc Tj = 30 °C

0.987

Pdc Tj = 25°C

2.47 kW

EER Tj = 25°C

6.21

Cdc Tj = 25 °C

0.975

Pdc Tj = 20°C

2.52 kW

EER Tj = 20°C

7.08

Cdc Tj = 20 °C

0.972

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

576 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

257 %

162 %

Prated

6 kW

5.6 kW

SCOP

6.51

4.13

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

6 kW

5.6 kW

COP Tj = +2°C

3.5

2.15

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.9 kW

3.6 kW

COP Tj = +7°C

5.92

3.45

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

2.7 kW

2.3 kW

COP Tj = 12°C

8

5.48

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6 kW

5.6 kW

COP Tj = Tbiv

3.5

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

5.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.5

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

1232 kWh

1813 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

128 %

Prated

7 kW

7 kW

SCOP

4.52

3.28

Tbiv

-6 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6 kW

5.9 kW

COP Tj = -7°C

2.86

1.98

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

3.9 kW

3.9 kW

COP Tj = +2°C

4.25

3.16

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.2 kW

3 kW

COP Tj = +7°C

6.3

4.49

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

3.3 kW

3.3 kW

COP Tj = 12°C

7.78

6.1

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6.1 kW

6.1 kW

COP Tj = Tbiv

3.07

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.01 kW

5.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.53

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.64 kW

Annual energy consumption Qhe

3196 kWh

4405 kWh

EDLA06E3V3
Configure model
Model name
EDLA06E3V3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

5.8 kW

El input

1.24 kW

2.15 kW

COP

4.85

2.7

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.55 kW

Cooling capacity

5.09

EER

3.28

EN 14825

+7°C/+12°C

Pdesignc

5.1 kW

SEER

5.31

Pdc Tj = 35°C

5.09 kW

EER Tj = 35°C

3.28

Pdc Tj = 30°C

3.75 kW

EER Tj = 30°C

4.75

Cdc Tj = 30 °C

1

Pdc Tj = 25°C

2.47 kW

EER Tj = 25°C

6.21

Cdc Tj = 25 °C

1

Pdc Tj = 20°C

2.52 kW

EER Tj = 20°C

7.08

Cdc Tj = 20 °C

1

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

576 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

249 %

158 %

Prated

6 kW

5.6 kW

SCOP

6.28

4.03

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

6 kW

5.6 kW

COP Tj = +2°C

3.5

2.15

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.9 kW

3.6 kW

COP Tj = +7°C

5.92

3.45

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

2.7 kW

2.3 kW

COP Tj = 12°C

8

5.48

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6 kW

5.6 kW

COP Tj = Tbiv

3.5

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

5.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.5

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

1276 kWh

1858 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

127 %

Prated

7 kW

7 kW

SCOP

4.47

3.26

Tbiv

-6 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6 kW

5.9 kW

COP Tj = -7°C

2.86

1.98

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

3.9 kW

3.9 kW

COP Tj = +2°C

4.25

3.16

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.2 kW

3 kW

COP Tj = +7°C

6.3

4.49

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

3.3 kW

3.3 kW

COP Tj = 12°C

7.78

6.1

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6.1 kW

6.1 kW

COP Tj = Tbiv

3.07

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.01 kW

5.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.53

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.64 kW

Annual energy consumption Qhe

3233 kWh

4441 kWh

EDLA06EV3
Configure model
Model name
EDLA06EV3
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

5.8 kW

El input

1.24 kW

2.15 kW

COP

4.85

2.7

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.55 kW

Cooling capacity

5.09

EER

3.28

EN 14825

+7°C/+12°C

Pdesignc

5.1 kW

SEER

5.31

Pdc Tj = 35°C

5.09 kW

EER Tj = 35°C

3.28

Pdc Tj = 30°C

3.75 kW

EER Tj = 30°C

4.75

Cdc Tj = 30 °C

1

Pdc Tj = 25°C

2.47 kW

EER Tj = 25°C

6.21

Cdc Tj = 25 °C

1

Pdc Tj = 20°C

2.52 kW

EER Tj = 20°C

7.08

Cdc Tj = 20 °C

1

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

576 kWh

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

249 %

158 %

Prated

6 kW

5.6 kW

SCOP

6.28

4.03

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

6 kW

5.6 kW

COP Tj = +2°C

3.5

2.15

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.9 kW

3.6 kW

COP Tj = +7°C

5.92

3.45

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

2.7 kW

2.3 kW

COP Tj = 12°C

8

5.48

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6 kW

5.6 kW

COP Tj = Tbiv

3.5

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

5.6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.5

2.15

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

1276 kWh

1858 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

127 %

Prated

7 kW

7 kW

SCOP

4.47

3.26

Tbiv

-6 °C

-6 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6 kW

5.9 kW

COP Tj = -7°C

2.86

1.98

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

3.9 kW

3.9 kW

COP Tj = +2°C

4.25

3.16

Cdh Tj = +2 °C

1

1

Pdh Tj = +7°C

3.2 kW

3 kW

COP Tj = +7°C

6.3

4.49

Cdh Tj = +7 °C

1

1

Pdh Tj = 12°C

3.3 kW

3.3 kW

COP Tj = 12°C

7.78

6.1

Cdh Tj = +12 °C

1

1

Pdh Tj = Tbiv

6.1 kW

6.1 kW

COP Tj = Tbiv

3.07

2.12

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.01 kW

5.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.53

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.99 kW

1.64 kW

Annual energy consumption Qhe

3233 kWh

4441 kWh