2,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
20.56 kW
18.90 kW
El input
4.36 kW
6.30 kW
COP
4.71
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
195 %
151 %
Prated
32.71 kW
32.90 kW
SCOP
5.06
3.99
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
29.51 kW
29.91 kW
COP Tj = -7°C
3.77
2.90
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
18.63 kW
17.01 kW
COP Tj = +2°C
5.10
4.01
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
12.14 kW
11.21 kW
COP Tj = +7°C
5.79
4.64
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
6.97 kW
6.80 kW
COP Tj = 12°C
5.96
4.77
Cdh Tj = +12 °C
0.978
0.982
Pdh Tj = Tbiv
32.71 kW
32.90 kW
COP Tj = Tbiv
3.70
2.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
32.71 kW
32.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.70
2.73
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
0 W
0 W
PTO
26 W
26 W
PSB
26 W
26 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
kW
kW
Annual energy consumption Qhe
13348 kWh
17049 kWh