2,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.20 kW
4.60 kW
El input
1.01 kW
1.57 kW
COP
5.17
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
238 %
180 %
Prated
4.97 kW
4.05 kW
SCOP
6.03
4.58
Tbiv
2 °C
2 °C
TOL
-20 °C
-20 °C
Pdh Tj = +2°C
4.97 kW
4.05 kW
COP Tj = +2°C
4.41
2.55
Cdh Tj = +2 °C
0.981
0.981
Pdh Tj = +7°C
3.21 kW
2.75 kW
COP Tj = +7°C
5.84
4.00
Cdh Tj = +7 °C
0.958
0.958
Pdh Tj = 12°C
3.25 kW
3.25 kW
COP Tj = 12°C
7.00
6.20
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
4.97 kW
4.04 kW
COP Tj = Tbiv
4.41
2.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.97 kW
4.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.41
2.55
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
21 W
21 W
PTO
15 W
15 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
1100 kWh
1180 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
156 %
125 %
Prated
11.40 kW
11.10 kW
SCOP
3.97
3.20
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.90 kW
6.72 kW
COP Tj = -7°C
3.71
2.87
Cdh Tj = -7 °C
0.992
0.992
Pdh Tj = +2°C
4.20 kW
4.06 kW
COP Tj = +2°C
5.45
4.25
Cdh Tj = +2 °C
0.981
0.981
Pdh Tj = +7°C
3.10 kW
3.00 kW
COP Tj = +7°C
6.42
5.85
Cdh Tj = +7 °C
0.958
0.958
Pdh Tj = 12°C
3.32 kW
3.35 kW
COP Tj = 12°C
8.25
6.40
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
6.90 kW
6.72 kW
COP Tj = Tbiv
3.71
2.87
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.60 kW
4.21 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.39
1.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.989
0.992
WTOL
60 °C
60 °C
Poff
21 W
21 W
PTO
15 W
15 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
11.40 kW
11.20 kW
Annual energy consumption Qhe
7086 kWh
8546 kWh
Pdh Tj = -15°C (if TOL<-20°C)
5.60
5.10
COP Tj = -15°C (if TOL<-20°C)
2.90
1.79
Cdh Tj = -15 °C
0.900
0.900
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
47 dB(A)
47 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
152 %
Prated
7.82 kW
7.30 kW
SCOP
5.06
3.88
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.92 kW
6.46 kW
COP Tj = -7°C
3.40
2.36
Cdh Tj = -7 °C
0.992
0.992
Pdh Tj = +2°C
4.62 kW
4.02 kW
COP Tj = +2°C
5.06
3.70
Cdh Tj = +2 °C
0.981
0.981
Pdh Tj = +7°C
3.15 kW
2.81 kW
COP Tj = +7°C
6.20
5.60
Cdh Tj = +7 °C
0.958
0.958
Pdh Tj = 12°C
3.32 kW
3.24 kW
COP Tj = 12°C
8.25
6.14
Cdh Tj = +12 °C
0.960
0.960
Pdh Tj = Tbiv
6.92 kW
6.46 kW
COP Tj = Tbiv
3.40
2.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.40 kW
6.07 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.11
2.22
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
21 W
21 W
PTO
15 W
15 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.42 kW
1.23 kW
Annual energy consumption Qhe
3192 kWh
3890 kWh