Certificate holders

Subtype

Bosch Compress 7800i LW 16

Certificate Holder
Bosch Thermotechnik GmbH
Junkersstraße 20 - 24
73249 Wernau
Germany
Registration number
011-1W0433
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Bosch Compress 7800i LW 16
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

2,300 kg

Certification Date
08.12.2020
Testing basis
HP KEYMARK certification scheme rules rev. 10
Generate PDF Export model CSV
  • Number of models 2

Models

CS7800i LW 16 M (+MF)
Configure model
Model name
CS7800i LW 16 M (+MF)
Application
Heating + DHW + low temp
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz
Off-peak product
No

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

15.54 kW

14.19 kW

El input

4.14 kW

5.68 kW

COP

3.75

2.50

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

204 %

155 %

Prated

15.53 kW

14.18 kW

SCOP

5.30

4.07

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

15.54 kW

14.19 kW

COP Tj = +2°C

3.75

2.46

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

9.99 kW

9.32 kW

COP Tj = +7°C

5.05

3.63

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

4.89 kW

4.71 kW

COP Tj = 12°C

5.98

4.98

Cdh Tj = +12 °C

0.900

0.990

Pdh Tj = Tbiv

15.54 kW

14.19 kW

COP Tj = Tbiv

3.75

2.46

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.46

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3916 kWh

4658 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

161 %

Prated

15.53 kW

14.18 kW

SCOP

5.47

4.24

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

10.06 kW

8.96 kW

COP Tj = -7°C

5.18

3.86

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

6.20 kW

5.42 kW

COP Tj = +2°C

5.97

4.74

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

4.91 kW

4.76 kW

COP Tj = +7°C

6.07

5.09

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.88 kW

4.75 kW

COP Tj = 12°C

5.89

5.19

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.53 kW

14.19 kW

COP Tj = Tbiv

3.75

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6995 kWh

8251 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

154 %

Prated

15.53 kW

14.18 kW

SCOP

5.28

4.06

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.91 kW

12.81 kW

COP Tj = -7°C

4.07

2.81

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

8.93 kW

7.91 kW

COP Tj = +2°C

5.39

4.21

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

5.72 kW

5.40 kW

COP Tj = +7°C

6.04

4.72

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.89 kW

4.70 kW

COP Tj = 12°C

5.98

4.97

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.54 kW

14.19 kW

COP Tj = Tbiv

3.75

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6074 kWh

7218 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

127 %

COP

3.05

Heating up time

1:09 h:min

Standby power input

110.0 W

Reference hot water temperature

46.9 °C

Mixed water at 40°C

206 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

127 %

COP

3.05

Heating up time

1:09 h:min

Standby power input

110.0 W

Reference hot water temperature

46.9 °C

Mixed water at 40°C

206 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

127 %

COP

3.05

Heating up time

1:09 h:min

Standby power input

110.0 W

Reference hot water temperature

46.9 °C

Mixed water at 40°C

206 l

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

20.43 kW

17.36 kW

El input

4.32 kW

5.53 kW

COP

4.73

3.14

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

289 %

212 %

Prated

20.43 kW

17.37 kW

SCOP

7.43

5.51

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.35 kW

14.99 kW

COP Tj = -7°C

5.21

3.63

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

11.74 kW

9.13 kW

COP Tj = +2°C

7.34

5.58

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.51 kW

6.15 kW

COP Tj = +7°C

9.29

6.85

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.43 kW

6.23 kW

COP Tj = 12°C

9.63

7.21

Cdh Tj = +12 °C

0.980

0.990

Pdh Tj = Tbiv

20.43 kW

17.36 kW

COP Tj = Tbiv

4.73

3.14

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

20.43 kW

17.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.73

3.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

71 °C

71 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5681 kWh

6511 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

153 %

COP

3.70

Heating up time

0:53 h:min

Standby power input

33.2 W

Reference hot water temperature

46.3 °C

Mixed water at 40°C

201 l

CS7800i LW 16 (+F)
Configure model
Model name
CS7800i LW 16 (+F)
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

15.54 kW

14.19 kW

El input

4.14 kW

5.68 kW

COP

3.75

2.50

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

204 %

155 %

Prated

15.53 kW

14.18 kW

SCOP

5.30

4.07

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

15.54 kW

14.19 kW

COP Tj = +2°C

3.75

2.46

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

9.99 kW

9.32 kW

COP Tj = +7°C

5.05

3.63

Cdh Tj = +7 °C

0.990

1.000

Pdh Tj = 12°C

4.89 kW

4.71 kW

COP Tj = 12°C

5.98

4.98

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.54 kW

14.19 kW

COP Tj = Tbiv

3.75

2.46

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.46

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3916 kWh

4658 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

161 %

Prated

15.53 kW

14.18 kW

SCOP

5.47

4.24

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

10.06 kW

8.96 kW

COP Tj = -7°C

5.18

3.86

Cdh Tj = -7 °C

0.990

1.000

Pdh Tj = +2°C

6.20 kW

5.42 kW

COP Tj = +2°C

5.97

4.74

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

4.91 kW

4.76 kW

COP Tj = +7°C

6.07

5.09

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.88 kW

4.75 kW

COP Tj = 12°C

5.89

5.19

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.53 kW

14.19 kW

COP Tj = Tbiv

3.75

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6995 kWh

8251 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

154 %

Prated

15.53 kW

14.18 kW

SCOP

5.28

4.06

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.91 kW

12.81 kW

COP Tj = -7°C

4.07

2.81

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

8.93 kW

7.91 kW

COP Tj = +2°C

5.39

4.21

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

5.72 kW

5.40 kW

COP Tj = +7°C

6.04

4.72

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

4.89 kW

4.70 kW

COP Tj = 12°C

5.98

4.97

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

15.54 kW

14.19 kW

COP Tj = Tbiv

3.75

2.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

15.54 kW

14.19 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.75

2.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

71 °C

71 °C

Poff

11 W

11 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6074 kWh

7218 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

20.43 kW

17.36 kW

El input

4.32 kW

5.53 kW

COP

4.73

3.14

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

289 %

212 %

Prated

20.43 kW

17.37 kW

SCOP

7.43

5.51

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

18.35 kW

14.99 kW

COP Tj = -7°C

5.21

3.63

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

11.74 kW

9.13 kW

COP Tj = +2°C

7.34

5.58

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

7.51 kW

6.15 kW

COP Tj = +7°C

9.29

6.85

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

6.43 kW

6.23 kW

COP Tj = 12°C

9.63

7.21

Cdh Tj = +12 °C

0.980

0.990

Pdh Tj = Tbiv

20.43 kW

17.36 kW

COP Tj = Tbiv

4.73

3.14

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

20.43 kW

17.36 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.73

3.14

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

71 °C

71 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5681 kWh

6511 kWh