1,470 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
10.30 kW
10.30 kW
El input
2.10 kW
3.42 kW
COP
4.90
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
205 %
146 %
Prated
10.60 kW
10.20 kW
SCOP
5.19
3.73
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
9.40 kW
9.00 kW
COP Tj = -7°C
3.17
2.27
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
5.70 kW
5.50 kW
COP Tj = +2°C
5.17
3.66
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
3.70 kW
3.50 kW
COP Tj = +7°C
6.91
4.91
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
4.50 kW
4.40 kW
COP Tj = 12°C
8.40
6.63
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
9.40 kW
9.00 kW
COP Tj = Tbiv
3.17
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.10 kW
8.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.84
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
15 W
14 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.50 kW
2.00 kW
Annual energy consumption Qhe
4219 kWh
5655 kWh