1,470 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.20 kW
8.20 kW
El input
1.58 kW
2.67 kW
COP
5.19
3.07
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
203 %
145 %
Prated
9.30 kW
9.10 kW
SCOP
5.16
3.70
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
8.20 kW
8.00 kW
COP Tj = -7°C
3.24
2.29
Cdh Tj = -7 °C
0.970
0.980
Pdh Tj = +2°C
5.00 kW
4.90 kW
COP Tj = +2°C
5.10
3.60
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
3.90 kW
3.70 kW
COP Tj = +7°C
6.81
4.94
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
4.50 kW
4.40 kW
COP Tj = 12°C
8.75
6.60
Cdh Tj = +12 °C
0.970
0.980
Pdh Tj = Tbiv
8.20 kW
8.00 kW
COP Tj = Tbiv
3.24
2.29
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
8.00 kW
7.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.93
2.03
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.970
0.980
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
15 W
14 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.30 kW
1.50 kW
Annual energy consumption Qhe
3725 kWh
5079 kWh