4,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.69 kW
7.24 kW
El input
1.22 kW
2.41 kW
COP
4.67
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.99
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.98
Poff
21 W
PTO
41 W
PSB
21 W
PCK
0 W
Annual energy consumption Qce
1038 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
140 %
Prated
12.5 kW
12.5 kW
SCOP
4.51
3.58
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.1 kW
11.2 kW
COP Tj = -7°C
3.12
2.47
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.7 kW
6.9 kW
COP Tj = +2°C
4.44
3.56
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
5.7 kW
6.9 kW
COP Tj = +7°C
5.84
4.44
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
6.0 kW
6.2 kW
COP Tj = 12°C
7.40
5.72
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
11.1 kW
12.2 kW
COP Tj = Tbiv
3.12
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.19
WTOL
35 °C
55 °C
Poff
21 W
21 W
PTO
41 W
41 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.4 kW
0.0 kW
Annual energy consumption Qhe
5726 kWh
7211 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.90 kW
7.24 kW
El input
1.23 kW
2.47 kW
COP
4.79
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.87
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.97
Poff
31 W
PTO
33 W
PSB
42 W
PCK
0 W
Annual energy consumption Qce
1069 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
140 %
Prated
12.5 kW
12.5 kW
SCOP
4.71
3.57
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
11.1 kW
COP Tj = -7°C
2.97
2.43
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.9 kW
6.7 kW
COP Tj = +2°C
4.94
3.52
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
6.2 kW
6.5 kW
COP Tj = +7°C
5.95
4.54
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
5.6 kW
5.2 kW
COP Tj = 12°C
7.07
5.97
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
10.7 kW
12.5 kW
COP Tj = Tbiv
2.97
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12.5 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.12
WTOL
35 °C
55 °C
Poff
31 W
31 W
PTO
33 W
33 W
PSB
42 W
42 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0.0 kW
Annual energy consumption Qhe
5479 kWh
7236 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.69 kW
7.24 kW
El input
1.22 kW
2.41 kW
COP
4.67
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.99
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.98
Poff
21 W
PTO
41 W
PSB
21 W
PCK
0 W
Annual energy consumption Qce
1038 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
140 %
Prated
12.5 kW
12.5 kW
SCOP
4.51
3.58
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.1 kW
11.2 kW
COP Tj = -7°C
3.12
2.47
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.7 kW
6.9 kW
COP Tj = +2°C
4.44
3.56
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
5.7 kW
6.9 kW
COP Tj = +7°C
5.84
4.44
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
6.0 kW
6.2 kW
COP Tj = 12°C
7.40
5.72
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
11.1 kW
12.2 kW
COP Tj = Tbiv
3.12
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.19
WTOL
35 °C
55 °C
Poff
21 W
21 W
PTO
41 W
41 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.4 kW
0.0 kW
Annual energy consumption Qhe
5726 kWh
7211 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.90 kW
7.24 kW
El input
1.23 kW
2.47 kW
COP
4.79
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.87
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.97
Poff
31 W
PTO
33 W
PSB
42 W
PCK
0 W
Annual energy consumption Qce
1069 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
186 %
140 %
Prated
12.5 kW
12.5 kW
SCOP
4.71
3.57
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
11.1 kW
COP Tj = -7°C
2.97
2.43
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.9 kW
6.7 kW
COP Tj = +2°C
4.94
3.52
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
6.2 kW
6.5 kW
COP Tj = +7°C
5.95
4.54
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
5.6 kW
5.2 kW
COP Tj = 12°C
7.07
5.97
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
10.7 kW
12.5 kW
COP Tj = Tbiv
2.97
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12.5 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.12
WTOL
35 °C
55 °C
Poff
31 W
31 W
PTO
33 W
33 W
PSB
42 W
42 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0.0 kW
Annual energy consumption Qhe
5479 kWh
7236 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.69 kW
7.24 kW
El input
1.22 kW
2.41 kW
COP
4.67
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.99
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.98
Poff
21 W
PTO
41 W
PSB
21 W
PCK
0 W
Annual energy consumption Qce
1038 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
142 %
Prated
12.5 kW
12.5 kW
SCOP
4.57
3.62
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.1 kW
11.2 kW
COP Tj = -7°C
3.12
2.47
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.7 kW
6.9 kW
COP Tj = +2°C
4.44
3.56
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
5.7 kW
6.9 kW
COP Tj = +7°C
5.84
4.44
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
6.0 kW
6.2 kW
COP Tj = 12°C
7.40
5.72
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
11.1 kW
12.2 kW
COP Tj = Tbiv
3.12
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.19
WTOL
35 °C
55 °C
Poff
21 W
21 W
PTO
41 W
41 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.4 kW
0.0 kW
Annual energy consumption Qhe
5649 kWh
7134 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.90 kW
7.24 kW
El input
1.23 kW
2.47 kW
COP
4.79
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.87
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.97
Poff
31 W
PTO
33 W
PSB
42 W
PCK
0 W
Annual energy consumption Qce
1069 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
142 %
Prated
12.5 kW
12.5 kW
SCOP
4.81
3.63
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
11.1 kW
COP Tj = -7°C
2.97
2.43
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.9 kW
6.7 kW
COP Tj = +2°C
4.94
3.52
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
6.2 kW
6.5 kW
COP Tj = +7°C
5.95
4.54
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
5.6 kW
5.2 kW
COP Tj = 12°C
7.07
5.97
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
10.7 kW
12.5 kW
COP Tj = Tbiv
2.97
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12.5 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.12
WTOL
35 °C
55 °C
Poff
31 W
31 W
PTO
33 W
33 W
PSB
42 W
42 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0.0 kW
Annual energy consumption Qhe
5366 kWh
7122 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.69 kW
7.24 kW
El input
1.22 kW
2.41 kW
COP
4.67
3.01
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.99
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.98
Poff
21 W
PTO
41 W
PSB
21 W
PCK
0 W
Annual energy consumption Qce
1038 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
142 %
Prated
12.5 kW
12.5 kW
SCOP
4.57
3.62
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
11.1 kW
11.2 kW
COP Tj = -7°C
3.12
2.47
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.7 kW
6.9 kW
COP Tj = +2°C
4.44
3.56
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
5.7 kW
6.9 kW
COP Tj = +7°C
5.84
4.44
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
6.0 kW
6.2 kW
COP Tj = 12°C
7.40
5.72
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
11.1 kW
12.2 kW
COP Tj = Tbiv
3.12
2.19
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.1 kW
12.2 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.76
2.19
WTOL
35 °C
55 °C
Poff
21 W
21 W
PTO
41 W
41 W
PSB
21 W
21 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.4 kW
0.0 kW
Annual energy consumption Qhe
5649 kWh
7134 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.90 kW
7.24 kW
El input
1.23 kW
2.47 kW
COP
4.79
2.93
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
2.56 kW
Cooling capacity
6.90
EER
2.7
EN 14825
+7°C/+12°C
Pdesignc
6.9 kW
SEER
3.87
Pdc Tj = 35°C
6.90 kW
EER Tj = 35°C
2.70
Pdc Tj = 30°C
5.23 kW
EER Tj = 30°C
3.65
Cdc Tj = 30 °C
0.98
Pdc Tj = 25°C
5.05 kW
EER Tj = 25°C
4.58
Cdc Tj = 25 °C
0.97
Pdc Tj = 20°C
4.94 kW
EER Tj = 20°C
5.41
Cdc Tj = 20 °C
0.97
Poff
31 W
PTO
33 W
PSB
42 W
PCK
0 W
Annual energy consumption Qce
1069 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
45.6 dB(A)
45.6 dB(A)
Sound power level outdoor
54.0 dB(A)
54.0 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
190 %
142 %
Prated
12.5 kW
12.5 kW
SCOP
4.81
3.63
Tbiv
-7 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.7 kW
11.1 kW
COP Tj = -7°C
2.97
2.43
Cdh Tj = -7 °C
1.00
1.0
Pdh Tj = +2°C
6.9 kW
6.7 kW
COP Tj = +2°C
4.94
3.52
Cdh Tj = +2 °C
1.0
1.0
Pdh Tj = +7°C
6.2 kW
6.5 kW
COP Tj = +7°C
5.95
4.54
Cdh Tj = +7 °C
1.0
1.0
Pdh Tj = 12°C
5.6 kW
5.2 kW
COP Tj = 12°C
7.07
5.97
Cdh Tj = +12 °C
1.0
1.0
Pdh Tj = Tbiv
10.7 kW
12.5 kW
COP Tj = Tbiv
2.97
2.12
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.1 kW
12.5 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.88
2.12
WTOL
35 °C
55 °C
Poff
31 W
31 W
PTO
33 W
33 W
PSB
42 W
42 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.4 kW
0.0 kW
Annual energy consumption Qhe
5366 kWh
7122 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
101 %
COP
2.38
Heating up time
1:25 h:min
Standby power input
49.0 W
Reference hot water temperature
47.0 °C
Mixed water at 40°C
149.0 l