Certificate holders

Subtype

Buderus Logatherm WLW-10,12,14 SP AR P3

Certificate Holder
Bosch Thermotechnik GmbH (Buderus)
Sophienstraße 30-32
35576 Wetzlar
Germany
Registration number
011-1W0540
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Buderus Logatherm WLW-10,12,14 SP AR P3
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

3,200 kg

Certification Date
10.06.2022
Testing basis
European KEYMARK Scheme for Heat Pumps Rev. 9 (as of 2021-03)
Generate PDF Export model CSV
  • Number of models 9

Models

WLW166i-10 SP AR P3 T190
Configure model
Model name
WLW166i-10 SP AR P3 T190
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.98 kW

8.88 kW

El input

2.09 kW

2.99 kW

COP

4.77

2.97

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

228 %

170 %

Prated

12 kW

12 kW

SCOP

5.77

4.32

Tbiv

4 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.6 kW

9.87 kW

COP Tj = +2°C

3.42

2.61

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

7.51 kW

7.68 kW

COP Tj = +7°C

5.37

3.74

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

6.17 kW

5.94 kW

COP Tj = 12°C

7.09

5.48

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.24 kW

10.28 kW

COP Tj = Tbiv

3.78

2.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.6 kW

9.87 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.42

2.61

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.4 kW

2.13 kW

Annual energy consumption Qhe

2778 kWh

3712 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

126 %

Prated

10 kW

10 kW

SCOP

3.95

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.11 kW

6.12 kW

COP Tj = -7°C

3.63

2.9

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.48 kW

4.23 kW

COP Tj = +2°C

4.56

3.76

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.5

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.14 kW

5.97 kW

COP Tj = 12°C

7.1

5.86

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

7.7 kW

7.71 kW

COP Tj = Tbiv

2.67

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.2 kW

6.91 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

10 kW

10 kW

Annual energy consumption Qhe

6248 kWh

7631 kWh

Pdh Tj = -15°C (if TOL<-20°C)

7.7

7.39

COP Tj = -15°C (if TOL<-20°C)

2.67

2.07

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

135 %

Prated

10 kW

10 kW

SCOP

4.66

3.45

Tbiv

-9 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.84 kW

8.62 kW

COP Tj = -7°C

3.14

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

5.36 kW

5.61 kW

COP Tj = +2°C

4.68

3.49

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.21 kW

4.83 kW

COP Tj = +7°C

5.46

4.22

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.20 kW

5.89 kW

COP Tj = 12°C

7.44

5.83

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.03 kW

8.62 kW

COP Tj = Tbiv

2.88

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.76 kW

7.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.24 kW

2.29 kW

Annual energy consumption Qhe

4435 kWh

5985 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

138 %

COP

3.33

Heating up time

01:26 h:min

Standby power input

40 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

255 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.5

Heating up time

02:08 h:min

Standby power input

50 W

Reference hot water temperature

51.6 °C

Mixed water at 40°C

260 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

120 %

COP

2.87

Heating up time

01:53 h:min

Standby power input

50 W

Reference hot water temperature

52.7 °C

Mixed water at 40°C

264 l

WLW166i-10 SP AR P3 E
Configure model
Model name
WLW166i-10 SP AR P3 E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.98 kW

8.88 kW

El input

2.09 kW

2.99 kW

COP

4.77

2.97

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

228 %

170 %

Prated

12 kW

12 kW

SCOP

5.77

4.32

Tbiv

4 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.6 kW

9.87 kW

COP Tj = +2°C

3.42

2.61

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

7.51 kW

7.68 kW

COP Tj = +7°C

5.37

3.74

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

6.17 kW

5.94 kW

COP Tj = 12°C

7.09

5.48

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.24 kW

10.28 kW

COP Tj = Tbiv

3.78

2.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.6 kW

9.87 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.42

2.61

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.4 kW

2.13 kW

Annual energy consumption Qhe

2778 kWh

3712 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

126 %

Prated

10 kW

10 kW

SCOP

3.95

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.11 kW

6.12 kW

COP Tj = -7°C

3.63

2.9

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.48 kW

4.23 kW

COP Tj = +2°C

4.56

3.76

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.5

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.14 kW

5.97 kW

COP Tj = 12°C

7.1

5.86

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

7.7 kW

7.71 kW

COP Tj = Tbiv

2.67

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.2 kW

6.91 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

10 kW

10 kW

Annual energy consumption Qhe

6248 kWh

7631 kWh

Pdh Tj = -15°C (if TOL<-20°C)

7.7

7.39

COP Tj = -15°C (if TOL<-20°C)

2.67

2.07

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

135 %

Prated

10 kW

10 kW

SCOP

4.66

3.45

Tbiv

-9 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.84 kW

8.62 kW

COP Tj = -7°C

3.14

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

5.36 kW

5.61 kW

COP Tj = +2°C

4.68

3.49

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.21 kW

4.83 kW

COP Tj = +7°C

5.46

4.22

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.20 kW

5.89 kW

COP Tj = 12°C

7.44

5.83

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.03 kW

8.62 kW

COP Tj = Tbiv

2.88

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.76 kW

7.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.24 kW

2.29 kW

Annual energy consumption Qhe

4435 kWh

5985 kWh

WLW166i-10 SP AR P3 B
Configure model
Model name
WLW166i-10 SP AR P3 B
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

9.98 kW

8.88 kW

El input

2.09 kW

2.99 kW

COP

4.77

2.97

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

228 %

170 %

Prated

12 kW

12 kW

SCOP

5.77

4.32

Tbiv

4 °C

4 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

9.6 kW

9.87 kW

COP Tj = +2°C

3.42

2.61

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

7.51 kW

7.68 kW

COP Tj = +7°C

5.37

3.74

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

6.17 kW

5.94 kW

COP Tj = 12°C

7.09

5.48

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.24 kW

10.28 kW

COP Tj = Tbiv

3.78

2.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

9.6 kW

9.87 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.42

2.61

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.4 kW

2.13 kW

Annual energy consumption Qhe

2778 kWh

3712 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

126 %

Prated

10 kW

10 kW

SCOP

3.95

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.11 kW

6.12 kW

COP Tj = -7°C

3.63

2.9

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.48 kW

4.23 kW

COP Tj = +2°C

4.56

3.76

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.5

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.14 kW

5.97 kW

COP Tj = 12°C

7.1

5.86

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

7.7 kW

7.71 kW

COP Tj = Tbiv

2.67

2.15

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.2 kW

6.91 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.26

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

10 kW

10 kW

Annual energy consumption Qhe

6248 kWh

7631 kWh

Pdh Tj = -15°C (if TOL<-20°C)

7.7

7.39

COP Tj = -15°C (if TOL<-20°C)

2.67

2.07

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

135 %

Prated

10 kW

10 kW

SCOP

4.66

3.45

Tbiv

-9 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

8.84 kW

8.62 kW

COP Tj = -7°C

3.14

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

5.36 kW

5.61 kW

COP Tj = +2°C

4.68

3.49

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.21 kW

4.83 kW

COP Tj = +7°C

5.46

4.22

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.20 kW

5.89 kW

COP Tj = 12°C

7.44

5.83

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.03 kW

8.62 kW

COP Tj = Tbiv

2.88

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.76 kW

7.71 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.80

1.86

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.24 kW

2.29 kW

Annual energy consumption Qhe

4435 kWh

5985 kWh

WLW166i-12 SP AR P3 T190
Configure model
Model name
WLW166i-12 SP AR P3 T190
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.6 kW

10.80 kW

El input

2.58 kW

3.75 kW

COP

4.5

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

13 kW

13 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.9 kW

11.3 kW

COP Tj = +2°C

3.28

2.48

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.66 kW

8.67 kW

COP Tj = +7°C

5.22

3.61

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.13

5.51

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

11.3 kW

11.57 kW

COP Tj = Tbiv

3.46

2.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.9 kW

11.3 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.28

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.1 kW

1.7 kW

Annual energy consumption Qhe

2999 kWh

4068 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

126 %

Prated

11 kW

11 kW

SCOP

3.97

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.96 kW

6.95 kW

COP Tj = -7°C

3.61

2.76

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.5 kW

4.44 kW

COP Tj = +2°C

4.6

4.02

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.28 kW

5.01 kW

COP Tj = +7°C

5.56

4.54

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.09

5.89

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.57 kW

8.16 kW

COP Tj = Tbiv

2.45

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.9 kW

7.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11 kW

11 kW

Annual energy consumption Qhe

6834 kWh

8388 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.57

7.78

COP Tj = -15°C (if TOL<-20°C)

2.45

1.96

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

136 %

Prated

11 kW

11 kW

SCOP

4.56

3.48

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.22 kW

9.51 kW

COP Tj = -7°C

3.02

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.14 kW

6.06 kW

COP Tj = +2°C

4.56

3.52

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.22 kW

5.01 kW

COP Tj = +7°C

5.46

4.35

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.17 kW

5.97 kW

COP Tj = 12°C

7.21

5.69

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.76 kW

9.51 kW

COP Tj = Tbiv

2.62

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.76 kW

8.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.93

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

2.11 kW

Annual energy consumption Qhe

4983 kWh

6527 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

138 %

COP

3.33

Heating up time

01:26 h:min

Standby power input

40 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

255 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.5

Heating up time

02:08 h:min

Standby power input

50 W

Reference hot water temperature

51.6 °C

Mixed water at 40°C

260 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

120 %

COP

2.87

Heating up time

01:53 h:min

Standby power input

50 W

Reference hot water temperature

52.7 °C

Mixed water at 40°C

264 l

WLW166i-12 SP AR P3 E
Configure model
Model name
WLW166i-12 SP AR P3 E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.6 kW

10.80 kW

El input

2.58 kW

3.75 kW

COP

4.5

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

13 kW

13 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.9 kW

11.3 kW

COP Tj = +2°C

3.28

2.48

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.66 kW

8.67 kW

COP Tj = +7°C

5.22

3.61

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.13

5.51

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

11.3 kW

11.57 kW

COP Tj = Tbiv

3.46

2.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.9 kW

11.3 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.28

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.1 kW

1.7 kW

Annual energy consumption Qhe

2999 kWh

4068 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

126 %

Prated

11 kW

11 kW

SCOP

3.97

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.96 kW

6.95 kW

COP Tj = -7°C

3.61

2.76

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.5 kW

4.44 kW

COP Tj = +2°C

4.6

4.02

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.28 kW

5.01 kW

COP Tj = +7°C

5.56

4.54

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.09

5.89

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.57 kW

8.16 kW

COP Tj = Tbiv

2.45

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.9 kW

7.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11 kW

11 kW

Annual energy consumption Qhe

6834 kWh

8388 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.57

7.78

COP Tj = -15°C (if TOL<-20°C)

2.45

1.96

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

136 %

Prated

11 kW

11 kW

SCOP

4.56

3.48

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.22 kW

9.51 kW

COP Tj = -7°C

3.02

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.14 kW

6.06 kW

COP Tj = +2°C

4.56

3.52

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.22 kW

5.01 kW

COP Tj = +7°C

5.46

4.35

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.17 kW

5.97 kW

COP Tj = 12°C

7.21

5.69

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.76 kW

9.51 kW

COP Tj = Tbiv

2.62

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.76 kW

8.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.93

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

2.11 kW

Annual energy consumption Qhe

4983 kWh

6527 kWh

WLW166i-12 SP AR P3 B
Configure model
Model name
WLW166i-12 SP AR P3 B
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.6 kW

10.80 kW

El input

2.58 kW

3.75 kW

COP

4.5

2.88

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

13 kW

13 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.9 kW

11.3 kW

COP Tj = +2°C

3.28

2.48

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.66 kW

8.67 kW

COP Tj = +7°C

5.22

3.61

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.13

5.51

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

11.3 kW

11.57 kW

COP Tj = Tbiv

3.46

2.61

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.9 kW

11.3 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.28

2.48

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

2.1 kW

1.7 kW

Annual energy consumption Qhe

2999 kWh

4068 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

156 %

126 %

Prated

11 kW

11 kW

SCOP

3.97

3.23

Tbiv

-15 °C

-13 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

6.96 kW

6.95 kW

COP Tj = -7°C

3.61

2.76

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.5 kW

4.44 kW

COP Tj = +2°C

4.6

4.02

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.28 kW

5.01 kW

COP Tj = +7°C

5.56

4.54

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.97 kW

COP Tj = 12°C

7.09

5.89

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

9.57 kW

8.16 kW

COP Tj = Tbiv

2.45

2.05

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.9 kW

7.15 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.05

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

11 kW

11 kW

Annual energy consumption Qhe

6834 kWh

8388 kWh

Pdh Tj = -15°C (if TOL<-20°C)

9.57

7.78

COP Tj = -15°C (if TOL<-20°C)

2.45

1.96

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

136 %

Prated

11 kW

11 kW

SCOP

4.56

3.48

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.22 kW

9.51 kW

COP Tj = -7°C

3.02

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.14 kW

6.06 kW

COP Tj = +2°C

4.56

3.52

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.22 kW

5.01 kW

COP Tj = +7°C

5.46

4.35

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.17 kW

5.97 kW

COP Tj = 12°C

7.21

5.69

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.76 kW

9.51 kW

COP Tj = Tbiv

2.62

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.76 kW

8.89 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.62

1.93

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

2.11 kW

Annual energy consumption Qhe

4983 kWh

6527 kWh

WLW166i-14 SP AR P3 T190
Configure model
Model name
WLW166i-14 SP AR P3 T190
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.58 kW

12.70 kW

El input

3.41 kW

4.54 kW

COP

4.28

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

14 kW

14 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.2 kW

11.85 kW

COP Tj = +2°C

3.16

2.38

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.88 kW

9.05 kW

COP Tj = +7°C

5.21

3.58

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.16 kW

5.97 kW

COP Tj = 12°C

7.19

5.56

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

12.6 kW

12.3 kW

COP Tj = Tbiv

3.33

2.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.2 kW

11.85 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.16

2.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

2.15 kW

Annual energy consumption Qhe

3228 kWh

4384 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

122 %

Prated

12 kW

12 kW

SCOP

3.96

3.12

Tbiv

-15 °C

-12 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

7.62 kW

7.48 kW

COP Tj = -7°C

3.56

2.68

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.53 kW

4.64 kW

COP Tj = +2°C

4.64

3.86

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.57

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.98 kW

COP Tj = 12°C

7.13

5.91

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.18 kW

8.85 kW

COP Tj = Tbiv

2.42

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.69 kW

7.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.06

1.7

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12 kW

12 kW

Annual energy consumption Qhe

7474 kWh

9483 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.18

8.31

COP Tj = -15°C (if TOL<-20°C)

2.42

1.88

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

45 dB(A)

45 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

138 %

Prated

12 kW

12 kW

SCOP

4.53

3.53

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.98 kW

10.26 kW

COP Tj = -7°C

2.73

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.71 kW

6.60 kW

COP Tj = +2°C

4.71

3.59

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.26 kW

5.09 kW

COP Tj = +7°C

5.40

4.48

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.11 kW

6.06 kW

COP Tj = 12°C

6.75

5.60

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

11.49 kW

10.26 kW

COP Tj = Tbiv

2.56

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.49 kW

9.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

2.96 kW

Annual energy consumption Qhe

5475 kWh

7031 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

138 %

COP

3.33

Heating up time

01:26 h:min

Standby power input

40 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

255 l

Colder Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.5

Heating up time

02:08 h:min

Standby power input

50 W

Reference hot water temperature

51.6 °C

Mixed water at 40°C

260 l

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

120 %

COP

2.87

Heating up time

01:53 h:min

Standby power input

50 W

Reference hot water temperature

52.7 °C

Mixed water at 40°C

264 l

WLW166i-14 SP AR P3 E
Configure model
Model name
WLW166i-14 SP AR P3 E
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.58 kW

12.70 kW

El input

3.41 kW

4.54 kW

COP

4.28

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

14 kW

14 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.2 kW

11.85 kW

COP Tj = +2°C

3.16

2.38

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.88 kW

9.05 kW

COP Tj = +7°C

5.21

3.58

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.16 kW

5.97 kW

COP Tj = 12°C

7.19

5.56

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

12.6 kW

12.3 kW

COP Tj = Tbiv

3.33

2.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.2 kW

11.85 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.16

2.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

2.15 kW

Annual energy consumption Qhe

3228 kWh

4384 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

122 %

Prated

12 kW

12 kW

SCOP

3.96

3.12

Tbiv

-15 °C

-12 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

7.62 kW

7.48 kW

COP Tj = -7°C

3.56

2.68

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.53 kW

4.64 kW

COP Tj = +2°C

4.64

3.86

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.57

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.98 kW

COP Tj = 12°C

7.13

5.91

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.18 kW

8.85 kW

COP Tj = Tbiv

2.42

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.69 kW

7.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.06

1.7

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12 kW

12 kW

Annual energy consumption Qhe

7474 kWh

9483 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.18

8.31

COP Tj = -15°C (if TOL<-20°C)

2.42

1.88

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

138 %

Prated

12 kW

12 kW

SCOP

4.53

3.53

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.98 kW

10.26 kW

COP Tj = -7°C

2.73

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.71 kW

6.60 kW

COP Tj = +2°C

4.71

3.59

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.26 kW

5.09 kW

COP Tj = +7°C

5.40

4.48

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.11 kW

6.06 kW

COP Tj = 12°C

6.75

5.60

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

11.49 kW

10.26 kW

COP Tj = Tbiv

2.56

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.49 kW

9.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

2.96 kW

Annual energy consumption Qhe

5475 kWh

7031 kWh

WLW166i-14 SP AR P3 B
Configure model
Model name
WLW166i-14 SP AR P3 B
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

14.58 kW

12.70 kW

El input

3.41 kW

4.54 kW

COP

4.28

2.80

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

229 %

168 %

Prated

14 kW

14 kW

SCOP

5.79

4.27

Tbiv

3 °C

3 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.2 kW

11.85 kW

COP Tj = +2°C

3.16

2.38

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

8.88 kW

9.05 kW

COP Tj = +7°C

5.21

3.58

Cdh Tj = +7 °C

0.99

0.99

Pdh Tj = 12°C

6.16 kW

5.97 kW

COP Tj = 12°C

7.19

5.56

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

12.6 kW

12.3 kW

COP Tj = Tbiv

3.33

2.56

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.2 kW

11.85 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.16

2.38

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

1.8 kW

2.15 kW

Annual energy consumption Qhe

3228 kWh

4384 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

155 %

122 %

Prated

12 kW

12 kW

SCOP

3.96

3.12

Tbiv

-15 °C

-12 °C

TOL

-20 °C

-20 °C

Pdh Tj = -7°C

7.62 kW

7.48 kW

COP Tj = -7°C

3.56

2.68

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.53 kW

4.64 kW

COP Tj = +2°C

4.64

3.86

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.26 kW

5.01 kW

COP Tj = +7°C

5.43

4.57

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.15 kW

5.98 kW

COP Tj = 12°C

7.13

5.91

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.18 kW

8.85 kW

COP Tj = Tbiv

2.42

2.03

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.69 kW

7.37 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.06

1.7

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.99

0.99

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

12 kW

12 kW

Annual energy consumption Qhe

7474 kWh

9483 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.18

8.31

COP Tj = -15°C (if TOL<-20°C)

2.42

1.88

Cdh Tj = -15 °C

0.99

0.99

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

138 %

Prated

12 kW

12 kW

SCOP

4.53

3.53

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.98 kW

10.26 kW

COP Tj = -7°C

2.73

2.10

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.71 kW

6.60 kW

COP Tj = +2°C

4.71

3.59

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.26 kW

5.09 kW

COP Tj = +7°C

5.40

4.48

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

6.11 kW

6.06 kW

COP Tj = 12°C

6.75

5.60

Cdh Tj = +12 °C

0.98

0.98

Pdh Tj = Tbiv

11.49 kW

10.26 kW

COP Tj = Tbiv

2.56

2.10

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.49 kW

9.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

1.84

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1

1

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

0 W

0 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

2.96 kW

Annual energy consumption Qhe

5475 kWh

7031 kWh