Certificate holders

Subtype

ADAPT 0416

Certificate Holder
KRONOTERM d.o.o.
Trnava 5e
3303 Gomilsko
Slovenia
Registration number
011-1W0517
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
ADAPT 0416
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R452B
Mass of Refrigerant

4,200 kg

Certification Date
18.01.2022
Testing basis
HP KEYMARK certification scheme rules rev. 9
Generate PDF Export model CSV
  • Number of models 4

Models

ADAPT 0416-K3 HT / HK 1F
Configure model
Model name
ADAPT 0416-K3 HT / HK 1F
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.48 kW

7.78 kW

El input

1.54 kW

2.44 kW

COP

5.60

3.20

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

46 dB(A)

46 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

144 %

Prated

11.10 kW

10.40 kW

SCOP

5.12

3.75

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.02 kW

9.23 kW

COP Tj = -7°C

3.30

2.41

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.29 kW

6.03 kW

COP Tj = +2°C

5.16

3.83

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

4.11 kW

3.72 kW

COP Tj = +7°C

6.51

4.47

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.93 kW

3.94 kW

COP Tj = 12°C

7.43

5.62

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

11.12 kW

10.61 kW

COP Tj = Tbiv

2.99

1.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.12 kW

10.61 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.99

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

67 °C

67 °C

Poff

15 W

15 W

PTO

14 W

14 W

PSB

15 W

15 W

PCK

14 W

14 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

4475 kWh

5734 kWh

ADAPT 0416-K3 HT / HK 1F + HYDRO C
Configure model
Model name
ADAPT 0416-K3 HT / HK 1F + HYDRO C
Application
Heating + DHW
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

7.78 kW

El input

2.44 kW

COP

3.20

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level indoor

0 dB(A)

Sound power level outdoor

46 dB(A)

EN 14825

Medium temperature

ηs

144 %

Prated

10.40 kW

SCOP

3.75

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

9.23 kW

COP Tj = -7°C

2.41

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

6.03 kW

COP Tj = +2°C

3.83

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

3.72 kW

COP Tj = +7°C

4.47

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

3.94 kW

COP Tj = 12°C

5.62

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

10.61 kW

COP Tj = Tbiv

1.99

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.61 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.99

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

67 °C

Poff

15 W

PTO

14 W

PSB

15 W

PCK

14 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

5734 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

127 %

COP

3.02

Heating up time

1:24 h:min

Standby power input

54.4 W

Reference hot water temperature

52.3 °C

Mixed water at 40°C

236 l

ADAPT 0416-K3 HT / HK 3F
Configure model
Model name
ADAPT 0416-K3 HT / HK 3F
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8.50 kW

7.81 kW

El input

1.53 kW

2.40 kW

COP

5.55

3.26

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

46 dB(A)

46 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

142 %

Prated

11.00 kW

10.30 kW

SCOP

5.21

3.67

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.78 kW

9.07 kW

COP Tj = -7°C

3.39

2.46

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

6.22 kW

5.82 kW

COP Tj = +2°C

5.17

3.71

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.90 kW

3.57 kW

COP Tj = +7°C

6.65

4.50

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.91 kW

3.73 kW

COP Tj = 12°C

7.71

5.29

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

10.99 kW

10.29 kW

COP Tj = Tbiv

3.11

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.99 kW

10.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.11

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

67 °C

67 °C

Poff

12 W

12 W

PTO

12 W

12 W

PSB

12 W

12 W

PCK

12 W

12 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.01 kW

0.01 kW

Annual energy consumption Qhe

4365 kWh

5801 kWh

ADAPT 0416-K3 HT / HK 3F + HYDRO C
Configure model
Model name
ADAPT 0416-K3 HT / HK 3F + HYDRO C
Application
Heating + DHW
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Medium temperature

Heat output

7.81 kW

El input

2.40 kW

COP

3.26

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Medium temperature

Sound power level indoor

0 dB(A)

Sound power level outdoor

46 dB(A)

EN 14825

Medium temperature

ηs

142 %

Prated

10.30 kW

SCOP

3.67

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

9.07 kW

COP Tj = -7°C

2.46

Cdh Tj = -7 °C

0.900

Pdh Tj = +2°C

5.82 kW

COP Tj = +2°C

3.71

Cdh Tj = +2 °C

0.900

Pdh Tj = +7°C

3.57 kW

COP Tj = +7°C

4.50

Cdh Tj = +7 °C

0.900

Pdh Tj = 12°C

3.73 kW

COP Tj = 12°C

5.29

Cdh Tj = +12 °C

0.900

Pdh Tj = Tbiv

10.29 kW

COP Tj = Tbiv

2.04

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.29 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.04

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

WTOL

67 °C

Poff

12 W

PTO

12 W

PSB

12 W

PCK

12 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.01 kW

Annual energy consumption Qhe

5801 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

131 %

COP

3.12

Heating up time

1:24 h:min

Standby power input

51.2 W

Reference hot water temperature

52.2 °C

Mixed water at 40°C

238 l