1,170 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.40 kW
4.40 kW
El input
0.86 kW
1.47 kW
COP
5.10
3.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
136 %
Prated
4.61 kW
4.09 kW
SCOP
5.17
3.47
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.05 kW
3.60 kW
COP Tj = -7°C
3.26
2.08
Cdh Tj = -7 °C
0.900
0.900
Pdh Tj = +2°C
2.48 kW
2.26 kW
COP Tj = +2°C
5.02
3.44
Cdh Tj = +2 °C
0.900
0.900
Pdh Tj = +7°C
1.67 kW
1.49 kW
COP Tj = +7°C
6.70
4.33
Cdh Tj = +7 °C
0.900
0.900
Pdh Tj = 12°C
1.14 kW
1.02 kW
COP Tj = 12°C
8.74
6.66
Cdh Tj = +12 °C
0.900
0.900
Pdh Tj = Tbiv
4.05 kW
3.60 kW
COP Tj = Tbiv
3.26
2.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.56 kW
3.59 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.68
1.77
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.900
0.900
WTOL
60 °C
60 °C
Poff
7 W
7 W
PTO
8 W
8 W
PSB
7 W
7 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.05 kW
0.48 kW
Annual energy consumption Qhe
1830 kWh
2425 kWh