12,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
66.80 kW
62.00 kW
El input
16.30 kW
23.80 kW
COP
4.10
2.61
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
17.67 kW
Cooling capacity
53.20
EER
3.01
EN 14825
+7°C/+12°C
Pdesignc
53.20 kW
SEER
4.85
Pdc Tj = 35°C
53.20 kW
EER Tj = 35°C
3.01
Pdc Tj = 30°C
39.20 kW
EER Tj = 30°C
4.06
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
29.04 kW
EER Tj = 25°C
5.10
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
31.50 kW
EER Tj = 20°C
6.73
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
6581 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
81 dB(A)
81 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
155 %
120 %
Prated
49.00 kW
51.00 kW
SCOP
3.94
3.08
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-9 °C
Pdh Tj = -7°C
43.60 kW
45.50 kW
COP Tj = -7°C
2.09
1.55
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
28.80 kW
28.50 kW
COP Tj = +2°C
3.89
3.02
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
33.10 kW
35.30 kW
COP Tj = +7°C
5.67
4.38
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
36.90 kW
39.70 kW
COP Tj = 12°C
7.01
6.82
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
43.60 kW
45.50 kW
COP Tj = Tbiv
2.09
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
41.70 kW
42.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.79
1.41
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
58 °C
58 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
76 W
76 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
7.30 kW
51.00 kW
Annual energy consumption Qhe
25821 kWh
34544 kWh