11,700 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
61.40 kW
56.50 kW
El input
15.00 kW
21.70 kW
COP
4.09
2.60
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
El input
15.50 kW
Cooling capacity
48.00
EER
3.10
EN 14825
+7°C/+12°C
Pdesignc
48.00 kW
SEER
4.86
Pdc Tj = 35°C
48.00 kW
EER Tj = 35°C
3.10
Pdc Tj = 30°C
35.40 kW
EER Tj = 30°C
4.12
Cdc Tj = 30 °C
1.000
Pdc Tj = 25°C
27.02 kW
EER Tj = 25°C
5.16
Cdc Tj = 25 °C
1.000
Pdc Tj = 20°C
28.95 kW
EER Tj = 20°C
6.45
Cdc Tj = 20 °C
1.000
Poff
22 W
PTO
0 W
PSB
28 W
PCK
0 W
Annual energy consumption Qce
5926 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
80 dB(A)
80 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
154 %
120 %
Prated
47.00 kW
47.00 kW
SCOP
3.92
3.08
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
41.80 kW
41.30 kW
COP Tj = -7°C
2.18
1.55
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
27.70 kW
29.10 kW
COP Tj = +2°C
3.78
2.93
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
31.20 kW
43.40 kW
COP Tj = +7°C
5.56
4.68
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
35.60 kW
42.30 kW
COP Tj = 12°C
7.38
7.25
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
41.80 kW
41.30 kW
COP Tj = Tbiv
2.18
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
40.10 kW
37.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.87
1.28
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
1.000
1.000
WTOL
58 °C
58 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
76 W
76 W
Supplementary Heater: Type of energy input
n/a
n/a
Supplementary Heater: PSUP
6.90 kW
9.10 kW
Annual energy consumption Qhe
24924 kWh
31333 kWh