Certificate holders

Subtype

i-HPV5H 0250

Certificate Holder
Advantix S.p.A.
Via San Giuseppe Lavoratore, 24
37040 Arcole Verona
Italy
Registration number
ICIM-PDC-000134
Certification Body
ICIM S.p.A.
Subtype title
i-HPV5H 0250
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

8,500 kg

Certification Date
25.02.2022
Testing basis
Heat Pump KEYMARK V9
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

i-HPV5H 0250
Configure model
Model name
i-HPV5H 0250
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

50.20 kW

48.30 kW

El input

12.20 kW

18.02 kW

COP

4.11

2.68

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

11.70 kW

Cooling capacity

36.30

EER

3.10

EN 14825

+7°C/+12°C

Pdesignc

36.30 kW

SEER

4.72

Pdc Tj = 35°C

36.30 kW

EER Tj = 35°C

3.10

Pdc Tj = 30°C

26.80 kW

EER Tj = 30°C

3.93

Cdc Tj = 30 °C

1.000

Pdc Tj = 25°C

21.65 kW

EER Tj = 25°C

5.00

Cdc Tj = 25 °C

0.990

Pdc Tj = 20°C

23.94 kW

EER Tj = 20°C

6.45

Cdc Tj = 20 °C

0.990

Poff

22 W

PTO

0 W

PSB

28 W

PCK

0 W

Annual energy consumption Qce

4614 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

75 dB(A)

75 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

122 %

Prated

44.00 kW

44.00 kW

SCOP

4.16

3.11

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

39.30 kW

39.20 kW

COP Tj = -7°C

2.22

1.55

Cdh Tj = -7 °C

1.000

1.000

Pdh Tj = +2°C

24.90 kW

23.80 kW

COP Tj = +2°C

4.25

3.06

Cdh Tj = +2 °C

1.000

1.000

Pdh Tj = +7°C

24.70 kW

23.70 kW

COP Tj = +7°C

5.55

4.48

Cdh Tj = +7 °C

1.000

1.000

Pdh Tj = 12°C

28.50 kW

27.70 kW

COP Tj = 12°C

7.22

7.10

Cdh Tj = +12 °C

1.000

1.000

Pdh Tj = Tbiv

39.30 kW

39.20 kW

COP Tj = Tbiv

2.22

1.55

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

34.00 kW

34.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.91

1.25

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

1.000

1.000

WTOL

58 °C

58 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

76 W

76 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

10.00 kW

9.40 kW

Annual energy consumption Qhe

22063 kWh

29398 kWh