Certificate holders

Subtype

S18L-M-CC

Certificate Holder
Heliotherm GmbH
Sportplatzweg 18
A-6336 Langkampfen
Austria
Registration number
011-1W0479
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
S18L-M-CC
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

8,000 kg

Certification Date
14.12.2017
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV
  • Number of models 1

Models

HELIOTHERM - Luft/Wasserwärmepumpe modulierend Baureihe Sensor Comfort Compact
Configure model
Model name
HELIOTHERM - Luft/Wasserwärmepumpe modulierend Baureihe Sensor Comfort Compact
Application
Heating (low temp)
Units
Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

17.55 kW

El input

3.50 kW

COP

5.01

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Sound power level outdoor

51 dB(A)

EN 14825

ηs

247 %

Prated

18.00 kW

SCOP

6.25

Tbiv

2 °C

TOL

2 °C

Pdh Tj = +2°C

18.04 kW

COP Tj = +2°C

4.18

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

11.30 kW

COP Tj = +7°C

5.87

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

7.33 kW

COP Tj = 12°C

7.03

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

18.04 kW

COP Tj = Tbiv

4.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.04 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.18

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

4032 kWh

Colder Climate

EN 12102-1

Sound power level outdoor

51 dB(A)

EN 14825

ηs

166 %

Prated

18.00 kW

SCOP

4.64

Tbiv

-18 °C

TOL

-22 °C

Pdh Tj = -7°C

10.98 kW

COP Tj = -7°C

3.52

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

6.83 kW

COP Tj = +2°C

5.25

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.26 kW

COP Tj = +7°C

5.84

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

7.52 kW

COP Tj = 12°C

7.26

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

16.52 kW

COP Tj = Tbiv

2.16

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.77 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

4.23 kW

Annual energy consumption Qhe

8147 kWh

Pdh Tj = -15°C (if TOL<-20°C)

14.48

COP Tj = -15°C (if TOL<-20°C)

2.42

Cdh Tj = -15 °C

0.990

Average Climate

EN 12102-1

Sound power level outdoor

51 dB(A)

EN 14825

ηs

195 %

Prated

18.00 kW

SCOP

4.96

Tbiv

-10 °C

TOL

-10 °C

Pdh Tj = -7°C

15.86 kW

COP Tj = -7°C

3.04

Cdh Tj = -7 °C

0.990

Pdh Tj = +2°C

9.02 kW

COP Tj = +2°C

4.97

Cdh Tj = +2 °C

0.990

Pdh Tj = +7°C

6.80 kW

COP Tj = +7°C

6.32

Cdh Tj = +7 °C

0.990

Pdh Tj = 12°C

7.97 kW

COP Tj = 12°C

7.28

Cdh Tj = +12 °C

0.990

Pdh Tj = Tbiv

18.11 kW

COP Tj = Tbiv

2.54

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

18.11 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.54

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.990

WTOL

62 °C

Poff

1 W

PTO

7 W

PSB

7 W

PCK

6 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

7500 kWh