9,300 kg
Heating
EN 14511-2
Heat output
16.15 kW
El input
3.01 kW
COP
5.37
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
43 dB(A)
Sound power level outdoor
46 dB(A)
EN 14825
ηs
262 %
Prated
18.00 kW
SCOP
6.56
Tbiv
2 °C
TOL
2 °C
Pdh Tj = +2°C
18.40 kW
COP Tj = +2°C
4.39
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
11.35 kW
COP Tj = +7°C
6.16
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
7.48 kW
COP Tj = 12°C
7.38
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
18.40 kW
COP Tj = Tbiv
4.39
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.40 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.39
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
4568 kWh
Colder Climate
EN 12102-1
Sound power level indoor
43 dB(A)
Sound power level outdoor
46 dB(A)
EN 14825
ηs
175 %
Prated
18.00 kW
SCOP
4.38
Tbiv
-18 °C
TOL
-22 °C
Pdh Tj = -7°C
11.20 kW
COP Tj = -7°C
3.70
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
6.97 kW
COP Tj = +2°C
5.51
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
6.39 kW
COP Tj = +7°C
6.13
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
7.67 kW
COP Tj = 12°C
7.62
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
16.85 kW
COP Tj = Tbiv
2.27
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
14.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
3.95 kW
Annual energy consumption Qhe
8791 kWh
Pdh Tj = -15°C (if TOL<-20°C)
14.77
COP Tj = -15°C (if TOL<-20°C)
2.54
Cdh Tj = -15 °C
0.990
Average Climate
EN 12102-1
Sound power level indoor
43 dB(A)
Sound power level outdoor
46 dB(A)
EN 14825
ηs
205 %
Prated
18.00 kW
SCOP
5.21
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
16.18 kW
COP Tj = -7°C
3.19
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
9.20 kW
COP Tj = +2°C
5.22
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
6.94 kW
COP Tj = +7°C
6.64
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
8.13 kW
COP Tj = 12°C
7.64
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
18.47 kW
COP Tj = Tbiv
2.67
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
18.47 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.67
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
7100 kWh