8,100 kg
Heating
EN 14511-2
Heat output
8.33 kW
El input
1.53 kW
COP
5.43
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Sound power level indoor
41 dB(A)
Sound power level outdoor
40 dB(A)
EN 14825
ηs
224 %
Prated
12.00 kW
SCOP
5.68
Tbiv
2 °C
TOL
2 °C
Pdh Tj = +2°C
12.03 kW
COP Tj = +2°C
4.48
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
7.73 kW
COP Tj = +7°C
5.62
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
5.47 kW
COP Tj = 12°C
5.97
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
12.03 kW
COP Tj = Tbiv
4.48
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.03 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
4.48
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
2958 kWh
Colder Climate
EN 12102-1
Sound power level indoor
41 dB(A)
Sound power level outdoor
40 dB(A)
EN 14825
ηs
157 %
Prated
12.00 kW
SCOP
3.99
Tbiv
-19 °C
TOL
-22 °C
Pdh Tj = -7°C
7.24 kW
COP Tj = -7°C
3.59
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
4.64 kW
COP Tj = +2°C
4.67
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
4.66 kW
COP Tj = +7°C
5.05
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
5.48 kW
COP Tj = 12°C
5.93
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
11.33 kW
COP Tj = Tbiv
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.49 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.68
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
2.51 kW
Annual energy consumption Qhe
6316 kWh
Pdh Tj = -15°C (if TOL<-20°C)
9.57
COP Tj = -15°C (if TOL<-20°C)
2.50
Cdh Tj = -15 °C
0.990
Average Climate
EN 12102-1
Sound power level indoor
41 dB(A)
Sound power level outdoor
40 dB(A)
EN 14825
ηs
189 %
Prated
12.00 kW
SCOP
4.79
Tbiv
-10 °C
TOL
-10 °C
Pdh Tj = -7°C
10.83 kW
COP Tj = -7°C
2.86
Cdh Tj = -7 °C
0.997
Pdh Tj = +2°C
6.70 kW
COP Tj = +2°C
4.92
Cdh Tj = +2 °C
0.993
Pdh Tj = +7°C
7.63 kW
COP Tj = +7°C
5.92
Cdh Tj = +7 °C
0.987
Pdh Tj = 12°C
8.52 kW
COP Tj = 12°C
7.26
Cdh Tj = +12 °C
0.982
Pdh Tj = Tbiv
12.23 kW
COP Tj = Tbiv
2.31
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.23 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.31
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.998
WTOL
62 °C
Poff
1 W
PTO
7 W
PSB
7 W
PCK
6 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
5200 kWh