Certificate holders

Subtype

F1355-28

Certificate Holder
Nibe AB
Box 14
S-28521 Markaryd
Sweden
Registration number
012-SC1196-17
Certification Body
RISE CERT
Subtype title
F1355-28
Driving energy
n/a
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R407c
Mass of Refrigerant

4,400 kg

Certification Date
n/a
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

F1355-28
Configure model
Model name
F1355-28
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

20.77 kW

19.87 kW

El input

4.56 kW

6.48 kW

COP

4.55

3.07

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

211 %

165 %

Prated

28.00 kW

28.00 kW

SCOP

5.47

4.32

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

17.00 kW

17.00 kW

COP Tj = -7°C

5.10

3.90

Pdh Tj = +2°C

10.30 kW

10.30 kW

COP Tj = +2°C

5.50

4.50

Pdh Tj = +7°C

6.60 kW

6.60 kW

COP Tj = +7°C

6.30

5.40

Pdh Tj = 12°C

3.80 kW

3.70 kW

COP Tj = 12°C

5.90

5.40

Pdh Tj = Tbiv

28.00 kW

28.00 kW

COP Tj = Tbiv

4.10

2.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

28.00 kW

28.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.10

2.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.97

0.98

WTOL

65 °C

65 °C

Poff

7 W

7 W

PTO

50 W

35 W

PSB

19 W

19 W

PCK

25 W

25 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

12907 kWh

16450 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

155 %

Prated

28.00 kW

28.00 kW

SCOP

5.07

4.07

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

24.80 kW

25.00 kW

COP Tj = -7°C

4.40

3.10

Pdh Tj = +2°C

15.60 kW

15.30 kW

COP Tj = +2°C

4.90

3.90

Pdh Tj = +7°C

9.70 kW

9.70 kW

COP Tj = +7°C

5.60

4.60

Pdh Tj = 12°C

4.30 kW

4.30 kW

COP Tj = 12°C

6.10

5.30

Pdh Tj = Tbiv

28.00 kW

28.00 kW

COP Tj = Tbiv

4.10

2.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

28.00 kW

28.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.10

2.80

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.98

0.99

WTOL

65 °C

65 °C

Poff

7 W

7 W

PTO

50 W

35 W

PSB

19 W

19 W

PCK

25 W

25 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

11528 kWh

14621 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

26.68 kW

25.23 kW

El input

4.76 kW

6.37 kW

COP

5.60

3.96

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

252 %

197 %

Prated

35.00 kW

35.00 kW

SCOP

6.37

4.99

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

21.20 kW

21.20 kW

COP Tj = -7°C

6.20

4.60

Pdh Tj = +2°C

12.90 kW

12.90 kW

COP Tj = +2°C

6.50

5.30

Pdh Tj = +7°C

8.30 kW

8.30 kW

COP Tj = +7°C

7.50

6.40

Pdh Tj = 12°C

6.90 kW

6.80 kW

COP Tj = 12°C

7.40

6.60

Pdh Tj = Tbiv

35.00 kW

35.00 kW

COP Tj = Tbiv

4.90

3.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

35.00 kW

35.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.90

3.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.97

0.98

WTOL

65 °C

65 °C

Poff

7 W

7 W

PTO

65 W

45 W

PSB

19 W

19 W

PCK

25 W

25 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

13541 kWh

17279 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

243 %

188 %

Prated

35.00 kW

35.00 kW

SCOP

6.15

4.79

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

31.00 kW

31.00 kW

COP Tj = -7°C

5.40

3.80

Pdh Tj = +2°C

21.60 kW

18.80 kW

COP Tj = +2°C

6.10

4.70

Pdh Tj = +7°C

12.10 kW

12.10 kW

COP Tj = +7°C

6.60

5.50

Pdh Tj = 12°C

7.00 kW

6.80 kW

COP Tj = 12°C

7.70

6.60

Pdh Tj = Tbiv

35.00 kW

35.00 kW

COP Tj = Tbiv

4.90

3.50

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

35.00 kW

35.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.90

3.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.97

0.99

WTOL

65 °C

65 °C

Poff

7 W

7 W

PTO

65 W

45 W

PSB

19 W

19 W

PCK

25 W

25 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

11765 kWh

15111 kWh