Certificate holders

Subtype

35. Yutaki S (N1) & S Combi (NW1) 220L 6HP R410A (3ph)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-56
Certification Body
BRE Global Limited
Subtype title
35. Yutaki S (N1) & S Combi (NW1) 220L 6HP R410A (3ph)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

3,400 kg

Certification Date
08.02.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 09
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

03. RAS-6WHNPE RWD-6.0NW1E-220S - Heating Only
Configure model
Model name
03. RAS-6WHNPE RWD-6.0NW1E-220S - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

161 %

134 %

Prated

16.00 kW

14.00 kW

SCOP

4.11

3.41

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7844 kWh

7662 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

04. RAS-6WHNPE RWD-6.0NW1E-220S - with cooling kit
Configure model
Model name
04. RAS-6WHNPE RWD-6.0NW1E-220S - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.25 kW

3.19 kW

Cooling capacity

10.50

13.50

EER

3.23

4.23

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

10.50 kW

13.50 kW

SEER

5.14

7.70

Pdc Tj = 35°C

10.50 kW

13.50 kW

EER Tj = 35°C

3.23

4.23

Pdc Tj = 30°C

7.80 kW

9.95 kW

EER Tj = 30°C

4.56

6.86

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.00 kW

7.20 kW

EER Tj = 25°C

5.77

9.54

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

7.80 kW

EER Tj = 20°C

7.69

12.47

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

715 kWh

613 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

135 %

Prated

16.00 kW

14.00 kW

SCOP

4.15

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7774 kWh

7592 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

05. RAS-6WHNPE RWD-6.0NW1E-220S-K – UK Version - Heating Only
Configure model
Model name
05. RAS-6WHNPE RWD-6.0NW1E-220S-K – UK Version - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

161 %

134 %

Prated

16.00 kW

14.00 kW

SCOP

4.11

3.41

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7844 kWh

7662 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

06. RAS-6WHNPE RWD-6.0NW1E-220S-K – UK Version - with cooling kit
Configure model
Model name
06. RAS-6WHNPE RWD-6.0NW1E-220S-K – UK Version - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.25 kW

3.19 kW

Cooling capacity

10.50

13.50

EER

3.23

4.23

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

10.50 kW

13.50 kW

SEER

5.14

7.70

Pdc Tj = 35°C

10.50 kW

13.50 kW

EER Tj = 35°C

3.23

4.23

Pdc Tj = 30°C

7.80 kW

9.95 kW

EER Tj = 30°C

4.56

6.86

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.00 kW

7.20 kW

EER Tj = 25°C

5.77

9.54

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

7.80 kW

EER Tj = 20°C

7.69

12.47

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

715 kWh

613 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

135 %

Prated

16.00 kW

14.00 kW

SCOP

4.15

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7774 kWh

7592 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

01. RAS-6WHNPE RWM-6.0N1E - Heating Only
Configure model
Model name
01. RAS-6WHNPE RWM-6.0N1E - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

161 %

134 %

Prated

16.00 kW

14.00 kW

SCOP

4.11

3.41

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7844 kWh

7662 kWh

02. RAS-6WHNPE RWM-6.0N1E - with cooling kit
Configure model
Model name
02. RAS-6WHNPE RWM-6.0N1E - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

16.00 kW

16.00 kW

El input

3.50 kW

6.40 kW

COP

4.57

2.50

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

3.25 kW

3.19 kW

Cooling capacity

10.50

13.50

EER

3.23

4.23

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

10.50 kW

13.50 kW

SEER

5.14

7.70

Pdc Tj = 35°C

10.50 kW

13.50 kW

EER Tj = 35°C

3.23

4.23

Pdc Tj = 30°C

7.80 kW

9.95 kW

EER Tj = 30°C

4.56

6.86

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

5.00 kW

7.20 kW

EER Tj = 25°C

5.77

9.54

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.20 kW

7.80 kW

EER Tj = 20°C

7.69

12.47

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

715 kWh

613 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

163 %

135 %

Prated

16.00 kW

14.00 kW

SCOP

4.15

3.45

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

13.80 kW

11.20 kW

COP Tj = -7°C

2.40

1.94

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

8.40 kW

6.82 kW

COP Tj = +2°C

3.90

3.35

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

5.40 kW

4.38 kW

COP Tj = +7°C

6.16

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.50 kW

3.60 kW

COP Tj = 12°C

7.10

7.05

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

13.80 kW

11.20 kW

COP Tj = Tbiv

2.40

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

14.10 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.30

1.40

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.90 kW

3.50 kW

Annual energy consumption Qhe

7774 kWh

7592 kWh