Certificate holders

Subtype

31. Yutaki S (N1) & S Combi (NW1) 220L 4HP R410A (3ph)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-52
Certification Body
BRE Global Limited
Subtype title
31. Yutaki S (N1) & S Combi (NW1) 220L 4HP R410A (3ph)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

3,300 kg

Certification Date
08.02.2022
Testing basis
Heat Pump Keymark Scheme Rules Rev 09
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

03. RAS-4WHNPE RWD-4.0NW1E-220S - Heating Only
Configure model
Model name
03. RAS-4WHNPE RWD-4.0NW1E-220S - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

135 %

Prated

11.00 kW

10.00 kW

SCOP

4.58

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4823 kWh

5837 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

04. RAS-4WHNPE RWD-4.0NW1E-220S - with cooling kit
Configure model
Model name
04. RAS-4WHNPE RWD-4.0NW1E-220S - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
n/a

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.87 kW

2.31 kW

Cooling capacity

7.20

10.40

EER

3.84

4.50

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.20 kW

10.40 kW

SEER

5.00

6.22

Pdc Tj = 35°C

7.20 kW

10.40 kW

EER Tj = 35°C

3.84

4.50

Pdc Tj = 30°C

5.30 kW

7.66 kW

EER Tj = 30°C

4.60

6.30

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

3.50 kW

4.93 kW

EER Tj = 25°C

5.80

7.20

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

5.10 kW

EER Tj = 20°C

7.50

8.20

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

504 kWh

585 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

136 %

Prated

11.00 kW

10.00 kW

SCOP

4.64

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4753 kWh

5767 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

05. RAS-4WHNPE RWD-4.0NW1E-220S-K – UK Version - Heating Only
Configure model
Model name
05. RAS-4WHNPE RWD-4.0NW1E-220S-K – UK Version - Heating Only
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

135 %

Prated

11.00 kW

10.00 kW

SCOP

4.58

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4823 kWh

5837 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

06. RAS-4WHNPE RWD-4.0NW1E-220S-K – UK Version - with cooling kit
Configure model
Model name
06. RAS-4WHNPE RWD-4.0NW1E-220S-K – UK Version - with cooling kit
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.87 kW

2.31 kW

Cooling capacity

7.20

10.40

EER

3.84

4.50

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.20 kW

10.40 kW

SEER

5.00

6.22

Pdc Tj = 35°C

7.20 kW

10.40 kW

EER Tj = 35°C

3.84

4.50

Pdc Tj = 30°C

5.30 kW

7.66 kW

EER Tj = 30°C

4.60

6.30

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

3.50 kW

4.93 kW

EER Tj = 25°C

5.80

7.20

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

5.10 kW

EER Tj = 20°C

7.50

8.20

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

504 kWh

585 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

136 %

Prated

11.00 kW

10.00 kW

SCOP

4.64

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4753 kWh

5767 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

127 %

COP

3.10

Heating up time

1:05 h:min

Standby power input

34.0 W

Reference hot water temperature

52.6 °C

Mixed water at 40°C

288 l

01. RAS-4WHNPE RWM-4.0N1E - Heating Only
Configure model
Model name
01. RAS-4WHNPE RWM-4.0N1E - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

180 %

135 %

Prated

11.00 kW

10.00 kW

SCOP

4.58

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4823 kWh

5837 kWh

02. RAS-4WHNPE RWM-4.0N1E - with cooling kit
Configure model
Model name
02. RAS-4WHNPE RWM-4.0N1E - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
+7°C/12°C and +18°C/+23°C
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

+18°C/+23°C

El input

1.87 kW

2.31 kW

Cooling capacity

7.20

10.40

EER

3.84

4.50

EN 14825

+7°C/+12°C

+18°C/+23°C

Pdesignc

7.20 kW

10.40 kW

SEER

5.00

6.22

Pdc Tj = 35°C

7.20 kW

10.40 kW

EER Tj = 35°C

3.84

4.50

Pdc Tj = 30°C

5.30 kW

7.66 kW

EER Tj = 30°C

4.60

6.30

Cdc Tj = 30 °C

0.900

0.900

Pdc Tj = 25°C

3.50 kW

4.93 kW

EER Tj = 25°C

5.80

7.20

Cdc Tj = 25 °C

0.900

0.900

Pdc Tj = 20°C

3.60 kW

5.10 kW

EER Tj = 20°C

7.50

8.20

Cdc Tj = 20 °C

0.900

0.900

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Annual energy consumption Qce

504 kWh

585 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

39 dB(A)

39 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

183 %

136 %

Prated

11.00 kW

10.00 kW

SCOP

4.64

3.44

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.45 kW

8.60 kW

COP Tj = -7°C

3.05

1.80

Cdh Tj = -7 °C

0.900

0.900

Pdh Tj = +2°C

5.75 kW

5.23 kW

COP Tj = +2°C

4.50

3.60

Cdh Tj = +2 °C

0.900

0.900

Pdh Tj = +7°C

3.70 kW

3.52 kW

COP Tj = +7°C

6.00

4.80

Cdh Tj = +7 °C

0.900

0.900

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

7.50

5.80

Cdh Tj = +12 °C

0.900

0.900

Pdh Tj = Tbiv

9.45 kW

8.60 kW

COP Tj = Tbiv

3.05

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

7.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.70

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.900

0.900

WTOL

55 °C

55 °C

Poff

19 W

19 W

PTO

0 W

0 W

PSB

19 W

19 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

2.60 kW

Annual energy consumption Qhe

4753 kWh

5767 kWh