2,100 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
7.67 kW
El input
2.45 kW
2.39 kW
COP
4.90
3.21
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.87 kW
Cooling capacity
9.05
EER
3.15
2.93
EN 14825
+7°C/+12°C
Pdesignc
9.05 kW
SEER
5.40
Pdc Tj = 35°C
9.05 kW
EER Tj = 35°C
3.15
Pdc Tj = 30°C
6.86 kW
EER Tj = 30°C
4.72
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
4.31 kW
EER Tj = 25°C
6.14
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.45 kW
EER Tj = 20°C
7.5
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1541 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.84 kW
9.42 kW
ηs
204 %
143 %
Prated
10.84 kW
9.42 kW
SCOP
5.16
3.65
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
9.59 kW
8.33 kW
COP Tj = -7°C
3.42
2.43
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
5.74 kW
5.47 kW
COP Tj = +2°C
5.10
3.33
Cdh Tj = +2 °C
0.988
0.992
Pdh Tj = +7°C
4.16 kW
3.98 kW
COP Tj = +7°C
6.88
5.04
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
4.71 kW
4.75 kW
COP Tj = 12°C
8.66
6.86
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
9.59 kW
8.33 kW
COP Tj = Tbiv
3.42
2.43
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.11 kW
8.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.09
2.11
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.73 kW
0.74 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
4338 kWh
5335 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
01:01 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
7.67 kW
El input
2.45 kW
2.39 kW
COP
4.90
3.21
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.87 kW
Cooling capacity
9.05
EER
3.15
2.93
EN 14825
+7°C/+12°C
Pdesignc
9.05 kW
SEER
5.40
Pdc Tj = 35°C
9.05 kW
EER Tj = 35°C
3.15
Pdc Tj = 30°C
6.86 kW
EER Tj = 30°C
4.72
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
4.31 kW
EER Tj = 25°C
6.14
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.45 kW
EER Tj = 20°C
7.5
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1541 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.84 kW
9.42 kW
ηs
204 %
143 %
Prated
10.84 kW
9.42 kW
SCOP
5.16
3.65
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
9.59 kW
8.33 kW
COP Tj = -7°C
3.42
2.43
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
5.74 kW
5.47 kW
COP Tj = +2°C
5.10
3.33
Cdh Tj = +2 °C
0.988
0.992
Pdh Tj = +7°C
4.16 kW
3.98 kW
COP Tj = +7°C
6.88
5.04
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
4.71 kW
4.75 kW
COP Tj = 12°C
8.66
6.86
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
9.59 kW
8.33 kW
COP Tj = Tbiv
3.42
2.43
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.11 kW
8.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.09
2.11
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.73 kW
0.74 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
4338 kWh
5335 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
01:01 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
9.50 kW
El input
3.19 kW
3.02 kW
COP
4.70
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.75 kW
Cooling capacity
11
EER
2.93
4.70
EN 14825
+7°C/+12°C
Pdesignc
11 kW
SEER
5.22
Pdc Tj = 35°C
11 kW
EER Tj = 35°C
2.93
Pdc Tj = 30°C
8.18 kW
EER Tj = 30°C
4.4
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.23 kW
EER Tj = 25°C
5.77
Cdc Tj = 25 °C
0.99
Pdc Tj = 20°C
4.5 kW
EER Tj = 20°C
7.53
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1951 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
12.48 kW
11.59 kW
ηs
202 %
151 %
Prated
12.48 kW
11.59 kW
SCOP
5.12
3.85
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.04 kW
10.25 kW
COP Tj = -7°C
3.29
2.50
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.98 kW
6.50 kW
COP Tj = +2°C
4.92
3.67
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
4.39 kW
3.96 kW
COP Tj = +7°C
6.76
5.04
Cdh Tj = +7 °C
0.979
0.983
Pdh Tj = 12°C
4.71 kW
4.69 kW
COP Tj = 12°C
8.55
6.97
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
11.04 kW
10.25 kW
COP Tj = Tbiv
3.29
2.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.18 kW
10.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.06
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.30 kW
1.07 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
5035 kWh
6217 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
00:51 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
9.50 kW
El input
3.19 kW
3.02 kW
COP
4.70
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.75 kW
Cooling capacity
11
EER
2.93
4.70
EN 14825
+7°C/+12°C
Pdesignc
11 kW
SEER
5.22
Pdc Tj = 35°C
11 kW
EER Tj = 35°C
2.93
Pdc Tj = 30°C
8.18 kW
EER Tj = 30°C
4.4
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.23 kW
EER Tj = 25°C
5.77
Cdc Tj = 25 °C
0.99
Pdc Tj = 20°C
4.5 kW
EER Tj = 20°C
7.53
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1951 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
12.48 kW
11.59 kW
ηs
202 %
151 %
Prated
12.48 kW
11.59 kW
SCOP
5.12
3.85
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.04 kW
10.25 kW
COP Tj = -7°C
3.29
2.50
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.98 kW
6.50 kW
COP Tj = +2°C
4.92
3.67
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
4.39 kW
3.96 kW
COP Tj = +7°C
6.76
5.04
Cdh Tj = +7 °C
0.979
0.983
Pdh Tj = 12°C
4.71 kW
4.69 kW
COP Tj = 12°C
8.55
6.97
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
11.04 kW
10.25 kW
COP Tj = Tbiv
3.29
2.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.18 kW
10.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.06
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.30 kW
1.07 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
5035 kWh
6217 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
00:51 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
7.67 kW
El input
2.45 kW
2.39 kW
COP
4.90
3.21
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.87 kW
Cooling capacity
9.05
EER
3.15
2.93
EN 14825
+7°C/+12°C
Pdesignc
9.05 kW
SEER
5.40
Pdc Tj = 35°C
9.05 kW
EER Tj = 35°C
3.15
Pdc Tj = 30°C
6.86 kW
EER Tj = 30°C
4.72
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
4.31 kW
EER Tj = 25°C
6.14
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.45 kW
EER Tj = 20°C
7.5
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1541 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.84 kW
9.42 kW
ηs
204 %
143 %
Prated
10.84 kW
9.42 kW
SCOP
5.16
3.65
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
9.59 kW
8.33 kW
COP Tj = -7°C
3.42
2.43
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
5.74 kW
5.47 kW
COP Tj = +2°C
5.10
3.33
Cdh Tj = +2 °C
0.988
0.992
Pdh Tj = +7°C
4.16 kW
3.98 kW
COP Tj = +7°C
6.88
5.04
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
4.71 kW
4.75 kW
COP Tj = 12°C
8.66
6.86
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
9.59 kW
8.33 kW
COP Tj = Tbiv
3.42
2.43
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.11 kW
8.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.09
2.11
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.73 kW
0.74 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
4338 kWh
5335 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
01:01 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
12.00 kW
7.67 kW
El input
2.45 kW
2.39 kW
COP
4.90
3.21
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
2.87 kW
Cooling capacity
9.05
EER
3.15
2.93
EN 14825
+7°C/+12°C
Pdesignc
9.05 kW
SEER
5.40
Pdc Tj = 35°C
9.05 kW
EER Tj = 35°C
3.15
Pdc Tj = 30°C
6.86 kW
EER Tj = 30°C
4.72
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
4.31 kW
EER Tj = 25°C
6.14
Cdc Tj = 25 °C
0.98
Pdc Tj = 20°C
4.45 kW
EER Tj = 20°C
7.5
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1541 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
10.84 kW
9.42 kW
ηs
204 %
143 %
Prated
10.84 kW
9.42 kW
SCOP
5.16
3.65
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
9.59 kW
8.33 kW
COP Tj = -7°C
3.42
2.43
Cdh Tj = -7 °C
0.995
0.996
Pdh Tj = +2°C
5.74 kW
5.47 kW
COP Tj = +2°C
5.10
3.33
Cdh Tj = +2 °C
0.988
0.992
Pdh Tj = +7°C
4.16 kW
3.98 kW
COP Tj = +7°C
6.88
5.04
Cdh Tj = +7 °C
0.978
0.983
Pdh Tj = 12°C
4.71 kW
4.75 kW
COP Tj = 12°C
8.66
6.86
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
9.59 kW
8.33 kW
COP Tj = Tbiv
3.42
2.43
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.11 kW
8.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.09
2.11
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.995
0.996
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.73 kW
0.74 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
4338 kWh
5335 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
01:01 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
9.50 kW
El input
3.19 kW
3.02 kW
COP
4.70
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.75 kW
Cooling capacity
11
EER
2.93
4.70
EN 14825
+7°C/+12°C
Pdesignc
11 kW
SEER
5.22
Pdc Tj = 35°C
11 kW
EER Tj = 35°C
2.93
Pdc Tj = 30°C
8.18 kW
EER Tj = 30°C
4.4
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.23 kW
EER Tj = 25°C
5.77
Cdc Tj = 25 °C
0.99
Pdc Tj = 20°C
4.5 kW
EER Tj = 20°C
7.53
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1951 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
12.48 kW
11.59 kW
ηs
202 %
151 %
Prated
12.48 kW
11.59 kW
SCOP
5.12
3.85
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.04 kW
10.25 kW
COP Tj = -7°C
3.29
2.50
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.98 kW
6.50 kW
COP Tj = +2°C
4.92
3.67
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
4.39 kW
3.96 kW
COP Tj = +7°C
6.76
5.04
Cdh Tj = +7 °C
0.979
0.983
Pdh Tj = 12°C
4.71 kW
4.69 kW
COP Tj = 12°C
8.55
6.97
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
11.04 kW
10.25 kW
COP Tj = Tbiv
3.29
2.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.18 kW
10.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.06
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.30 kW
1.07 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
5035 kWh
6217 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
00:51 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
15.00 kW
9.50 kW
El input
3.19 kW
3.02 kW
COP
4.70
3.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
3.75 kW
Cooling capacity
11
EER
2.93
4.70
EN 14825
+7°C/+12°C
Pdesignc
11 kW
SEER
5.22
Pdc Tj = 35°C
11 kW
EER Tj = 35°C
2.93
Pdc Tj = 30°C
8.18 kW
EER Tj = 30°C
4.4
Cdc Tj = 30 °C
0.99
Pdc Tj = 25°C
5.23 kW
EER Tj = 25°C
5.77
Cdc Tj = 25 °C
0.99
Pdc Tj = 20°C
4.5 kW
EER Tj = 20°C
7.53
Cdc Tj = 20 °C
0.98
Poff
14 W
PTO
14 W
PSB
14 W
PCK
0 W
Annual energy consumption Qce
1951 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
35 dB(A)
35 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
Pdesignh
12.48 kW
11.59 kW
ηs
202 %
151 %
Prated
12.48 kW
11.59 kW
SCOP
5.12
3.85
Tbiv
-7 °C
-7 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
11.04 kW
10.25 kW
COP Tj = -7°C
3.29
2.50
Cdh Tj = -7 °C
0.996
0.997
Pdh Tj = +2°C
6.98 kW
6.50 kW
COP Tj = +2°C
4.92
3.67
Cdh Tj = +2 °C
0.990
0.992
Pdh Tj = +7°C
4.39 kW
3.96 kW
COP Tj = +7°C
6.76
5.04
Cdh Tj = +7 °C
0.979
0.983
Pdh Tj = 12°C
4.71 kW
4.69 kW
COP Tj = 12°C
8.55
6.97
Cdh Tj = +12 °C
0.975
0.980
Pdh Tj = Tbiv
11.04 kW
10.25 kW
COP Tj = Tbiv
3.29
2.50
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.18 kW
10.52 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.00
2.06
WTOL
60 °C
60 °C
Poff
14 W
14 W
PTO
14 W
14 W
PSB
14 W
14 W
PCK
14 W
14 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.30 kW
1.07 kW
Backup Heater
6.00 kW
6.00 kW
Annual energy consumption Qhe
5035 kWh
6217 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
135 %
COP
3.20
Heating up time
00:51 h:min
Standby power input
37.0 W
Reference hot water temperature
53 °C
Mixed water at 40°C
256 l