Certificate holders

Subtype

Buderus Logatherm WPLS.11/13/15.2

Certificate Holder
Bosch Thermotechnik GmbH (Buderus)
Sophienstraße 30-32
35576 Wetzlar
Germany
Registration number
011-1W0143
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
Buderus Logatherm WPLS.11/13/15.2
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,300 kg

Certification Date
26.09.2017
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 24

Models

Buderus Logatherm WPLS11.2 RE-S
Configure model
Model name
Buderus Logatherm WPLS11.2 RE-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

13.57 kW

El input

1.32 kW

5.75 kW

COP

4.92

2.36

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

158 %

Prated

11.86 kW

10.35 kW

SCOP

5.15

4.04

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.86 kW

10.35 kW

COP Tj = +2°C

3.45

1.97

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.64 kW

6.64 kW

COP Tj = +7°C

4.84

3.68

Cdh Tj = +7 °C

0.996

0.996

Pdh Tj = 12°C

7.25 kW

6.93 kW

COP Tj = 12°C

5.90

5.01

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.86 kW

10.35 kW

COP Tj = Tbiv

3.45

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.86 kW

10.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.45

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3079 kWh

3425 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

137 %

120 %

Prated

12.00 kW

11.00 kW

SCOP

3.49

3.08

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.31 kW

6.68 kW

COP Tj = -7°C

3.17

2.70

Cdh Tj = -7 °C

0.997

0.997

Pdh Tj = +2°C

5.94 kW

5.59 kW

COP Tj = +2°C

4.65

4.05

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

6.56 kW

6.28 kW

COP Tj = +7°C

5.30

4.72

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.27 kW

7.06 kW

COP Tj = 12°C

5.92

5.38

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

10.72 kW

9.48 kW

COP Tj = Tbiv

2.15

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.72 kW

9.48 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12.00 kW

11.00 kW

Annual energy consumption Qhe

8480 kWh

8790 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.72

9.48

COP Tj = -15°C (if TOL<-20°C)

2.15

1.85

Cdh Tj = -15 °C

0.999

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

11.02 kW

9.35 kW

SCOP

4.48

3.28

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

9.94 kW

8.39 kW

COP Tj = -7°C

2.81

2.01

Cdh Tj = -7 °C

0.998

0.998

Pdh Tj = +2°C

5.94 kW

5.03 kW

COP Tj = +2°C

4.61

3.21

Cdh Tj = +2 °C

0.995

0.996

Pdh Tj = +7°C

6.73 kW

6.55 kW

COP Tj = +7°C

5.55

4.43

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.11 kW

7.26 kW

COP Tj = 12°C

5.70

5.11

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.02 kW

9.35 kW

COP Tj = Tbiv

2.49

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.02 kW

9.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

9.35 kW

Annual energy consumption Qhe

5084 kWh

5889 kWh

Buderus Logatherm WPLS11.2 RB-S
Configure model
Model name
Buderus Logatherm WPLS11.2 RB-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

13.57 kW

El input

1.32 kW

5.75 kW

COP

4.92

2.36

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

158 %

Prated

11.86 kW

10.35 kW

SCOP

5.15

4.04

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.86 kW

10.35 kW

COP Tj = +2°C

3.45

1.97

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.64 kW

6.64 kW

COP Tj = +7°C

4.84

3.68

Cdh Tj = +7 °C

0.996

0.996

Pdh Tj = 12°C

7.25 kW

6.93 kW

COP Tj = 12°C

5.90

5.01

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.86 kW

10.35 kW

COP Tj = Tbiv

3.45

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.86 kW

10.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.45

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3079 kWh

3425 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

137 %

120 %

Prated

12.00 kW

11.00 kW

SCOP

3.49

3.08

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.31 kW

6.68 kW

COP Tj = -7°C

3.17

2.70

Cdh Tj = -7 °C

0.997

0.997

Pdh Tj = +2°C

5.94 kW

5.59 kW

COP Tj = +2°C

4.65

4.05

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

6.56 kW

6.28 kW

COP Tj = +7°C

5.30

4.72

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.27 kW

7.06 kW

COP Tj = 12°C

5.92

5.38

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

10.72 kW

9.48 kW

COP Tj = Tbiv

2.15

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.72 kW

9.48 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

8480 kWh

8790 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.72

9.48

COP Tj = -15°C (if TOL<-20°C)

2.15

1.85

Cdh Tj = -15 °C

0.999

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

11.02 kW

9.35 kW

SCOP

4.48

3.28

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

9.94 kW

8.39 kW

COP Tj = -7°C

2.81

2.01

Cdh Tj = -7 °C

0.998

0.998

Pdh Tj = +2°C

5.94 kW

5.03 kW

COP Tj = +2°C

4.61

3.21

Cdh Tj = +2 °C

0.995

0.996

Pdh Tj = +7°C

6.73 kW

6.55 kW

COP Tj = +7°C

5.55

4.43

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.11 kW

7.26 kW

COP Tj = 12°C

5.70

5.11

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.02 kW

9.35 kW

COP Tj = Tbiv

2.49

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.02 kW

9.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5084 kWh

5889 kWh

Buderus Logatherm WPLS11.2 RT-S
Configure model
Model name
Buderus Logatherm WPLS11.2 RT-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

13.57 kW

El input

1.32 kW

5.75 kW

COP

4.92

2.36

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

158 %

Prated

11.86 kW

10.35 kW

SCOP

5.15

4.04

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.86 kW

10.35 kW

COP Tj = +2°C

3.45

1.97

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.64 kW

6.64 kW

COP Tj = +7°C

4.84

3.68

Cdh Tj = +7 °C

0.996

0.996

Pdh Tj = 12°C

7.25 kW

6.93 kW

COP Tj = 12°C

5.90

5.01

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.86 kW

10.35 kW

COP Tj = Tbiv

3.45

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.86 kW

10.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.45

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3079 kWh

3425 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

137 %

120 %

Prated

12.00 kW

11.00 kW

SCOP

3.49

3.08

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.31 kW

6.68 kW

COP Tj = -7°C

3.17

2.70

Cdh Tj = -7 °C

0.997

0.997

Pdh Tj = +2°C

5.94 kW

5.59 kW

COP Tj = +2°C

4.65

4.05

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

6.56 kW

6.28 kW

COP Tj = +7°C

5.30

4.72

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.27 kW

7.06 kW

COP Tj = 12°C

5.92

5.38

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

10.72 kW

9.48 kW

COP Tj = Tbiv

2.15

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.72 kW

9.48 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12.00 kW

11.00 kW

Annual energy consumption Qhe

8480 kWh

8790 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.72

1.85

COP Tj = -15°C (if TOL<-20°C)

2.15

1.85

Cdh Tj = -15 °C

0.999

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

11.02 kW

9.35 kW

SCOP

4.48

3.28

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

9.94 kW

8.39 kW

COP Tj = -7°C

2.81

2.01

Cdh Tj = -7 °C

0.998

0.998

Pdh Tj = +2°C

5.94 kW

5.03 kW

COP Tj = +2°C

4.61

3.21

Cdh Tj = +2 °C

0.995

0.996

Pdh Tj = +7°C

6.73 kW

6.55 kW

COP Tj = +7°C

5.55

4.43

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.11 kW

7.26 kW

COP Tj = 12°C

5.70

5.11

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.02 kW

9.35 kW

COP Tj = Tbiv

2.49

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.02 kW

9.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

9.35 kW

Annual energy consumption Qhe

5084 kWh

5889 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

108 %

COP

2.52

Heating up time

01:01 h:min

Standby power input

55.0 W

Reference hot water temperature

51.3 °C

Mixed water at 40°C

253 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

69 %

COP

1.57

Heating up time

01:29 h:min

Standby power input

114.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.92

Heating up time

01:38 h:min

Standby power input

70.0 W

Reference hot water temperature

52.3 °C

Mixed water at 40°C

267 l

Buderus Logatherm WPLS11.2 RTS-S
Configure model
Model name
Buderus Logatherm WPLS11.2 RTS-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

13.57 kW

El input

1.32 kW

5.75 kW

COP

4.92

2.36

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

203 %

158 %

Prated

11.86 kW

10.35 kW

SCOP

5.15

4.04

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.86 kW

10.35 kW

COP Tj = +2°C

3.45

1.97

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.64 kW

6.64 kW

COP Tj = +7°C

4.84

3.68

Cdh Tj = +7 °C

0.996

0.996

Pdh Tj = 12°C

7.25 kW

6.93 kW

COP Tj = 12°C

5.90

5.01

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.86 kW

10.35 kW

COP Tj = Tbiv

3.45

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.86 kW

10.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.45

1.97

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3079 kWh

3425 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

137 %

120 %

Prated

12.00 kW

11.00 kW

SCOP

3.49

3.08

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

7.31 kW

6.68 kW

COP Tj = -7°C

3.17

2.70

Cdh Tj = -7 °C

0.997

0.997

Pdh Tj = +2°C

5.94 kW

5.59 kW

COP Tj = +2°C

4.65

4.05

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

6.56 kW

6.28 kW

COP Tj = +7°C

5.30

4.72

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.27 kW

7.06 kW

COP Tj = 12°C

5.92

5.38

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

10.72 kW

9.48 kW

COP Tj = Tbiv

2.15

1.85

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.72 kW

9.48 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.15

1.85

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

12.00 kW

11.00 kW

Annual energy consumption Qhe

8480 kWh

8790 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.72

9.48

COP Tj = -15°C (if TOL<-20°C)

2.15

1.85

Cdh Tj = -15 °C

0.999

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

11.02 kW

9.35 kW

SCOP

4.48

3.28

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

9.94 kW

8.39 kW

COP Tj = -7°C

2.81

2.01

Cdh Tj = -7 °C

0.998

0.998

Pdh Tj = +2°C

5.94 kW

5.03 kW

COP Tj = +2°C

4.61

3.21

Cdh Tj = +2 °C

0.995

0.996

Pdh Tj = +7°C

6.73 kW

6.55 kW

COP Tj = +7°C

5.55

4.43

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.11 kW

7.26 kW

COP Tj = 12°C

5.70

5.11

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

11.02 kW

9.35 kW

COP Tj = Tbiv

2.49

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.02 kW

9.35 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.49

1.65

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

9.35 kW

Annual energy consumption Qhe

5084 kWh

5889 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.22

Heating up time

01:00 h:min

Standby power input

68.0 W

Reference hot water temperature

50.3 °C

Mixed water at 40°C

248 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

67 %

COP

1.54

Heating up time

01:04 h:min

Standby power input

116.3 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

76 %

COP

1.76

Heating up time

01:36 h:min

Standby power input

75.0 W

Reference hot water temperature

51.2 °C

Mixed water at 40°C

251 l

Buderus Logatherm WPLS11.2 RE-T
Configure model
Model name
Buderus Logatherm WPLS11.2 RE-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

13.45 kW

El input

1.32 kW

5.69 kW

COP

4.85

2.37

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

154 %

Prated

11.88 kW

10.49 kW

SCOP

5.44

3.93

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.90 kW

10.50 kW

COP Tj = +2°C

3.29

2.13

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

7.53 kW

6.85 kW

COP Tj = +7°C

5.42

3.44

Cdh Tj = +7 °C

0.987

0.987

Pdh Tj = 12°C

7.52 kW

7.52 kW

COP Tj = 12°C

6.27

5.18

Cdh Tj = +12 °C

0.982

0.982

Pdh Tj = Tbiv

11.90 kW

10.50 kW

COP Tj = Tbiv

3.29

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.90 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.29

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2917 kWh

3563 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

146 %

112 %

Prated

11.40 kW

10.10 kW

SCOP

3.72

2.87

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

6.78 kW

6.19 kW

COP Tj = -7°C

3.48

2.61

Cdh Tj = -7 °C

0.987

0.989

Pdh Tj = +2°C

5.73 kW

5.06 kW

COP Tj = +2°C

4.87

3.51

Cdh Tj = +2 °C

0.978

0.982

Pdh Tj = +7°C

6.79 kW

6.49 kW

COP Tj = +7°C

5.92

4.57

Cdh Tj = +7 °C

0.977

0.982

Pdh Tj = 12°C

7.63 kW

7.69 kW

COP Tj = 12°C

6.89

6.02

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

10.28 kW

9.01 kW

COP Tj = Tbiv

2.57

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.28 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.57

1.87

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.40 kW

10.10 kW

Annual energy consumption Qhe

7564 kWh

8660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.28

9.01

COP Tj = -15°C (if TOL<-20°C)

2.57

1.87

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

11.70 kW

9.01 kW

SCOP

4.62

3.22

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.04 kW

7.98 kW

COP Tj = -7°C

2.85

2.04

Cdh Tj = -7 °C

0.993

0.993

Pdh Tj = +2°C

6.24 kW

5.04 kW

COP Tj = +2°C

4.69

3.19

Cdh Tj = +2 °C

0.980

0.984

Pdh Tj = +7°C

6.79 kW

6.15 kW

COP Tj = +7°C

5.82

4.07

Cdh Tj = +7 °C

0.978

0.983

Pdh Tj = 12°C

7.62 kW

7.56 kW

COP Tj = 12°C

6.94

5.73

Cdh Tj = +12 °C

0.976

0.980

Pdh Tj = Tbiv

11.70 kW

9.01 kW

COP Tj = Tbiv

2.72

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.72

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5234 kWh

5777 kWh

Buderus Logatherm WPLS11.2 RB-T
Configure model
Model name
Buderus Logatherm WPLS11.2 RB-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

13.45 kW

El input

1.32 kW

5.69 kW

COP

4.85

2.37

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

154 %

Prated

11.88 kW

10.49 kW

SCOP

5.44

3.93

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.90 kW

10.50 kW

COP Tj = +2°C

3.29

2.13

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

7.53 kW

6.85 kW

COP Tj = +7°C

5.42

3.44

Cdh Tj = +7 °C

0.987

0.987

Pdh Tj = 12°C

7.52 kW

7.52 kW

COP Tj = 12°C

6.27

5.18

Cdh Tj = +12 °C

0.982

0.982

Pdh Tj = Tbiv

11.90 kW

10.50 kW

COP Tj = Tbiv

3.29

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.90 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.29

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2917 kWh

3563 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

146 %

112 %

Prated

11.40 kW

10.10 kW

SCOP

3.72

2.87

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

6.78 kW

6.19 kW

COP Tj = -7°C

3.48

2.61

Cdh Tj = -7 °C

0.987

0.989

Pdh Tj = +2°C

5.73 kW

5.06 kW

COP Tj = +2°C

4.87

3.51

Cdh Tj = +2 °C

0.978

0.982

Pdh Tj = +7°C

6.79 kW

6.49 kW

COP Tj = +7°C

5.92

4.57

Cdh Tj = +7 °C

0.977

0.982

Pdh Tj = 12°C

7.63 kW

7.69 kW

COP Tj = 12°C

6.89

6.02

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

10.28 kW

9.01 kW

COP Tj = Tbiv

2.57

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.28 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.57

1.87

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

7564 kWh

8660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.28

9.01

COP Tj = -15°C (if TOL<-20°C)

2.57

1.87

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

11.70 kW

9.01 kW

SCOP

4.62

3.22

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.04 kW

7.98 kW

COP Tj = -7°C

2.85

2.04

Cdh Tj = -7 °C

0.993

0.993

Pdh Tj = +2°C

6.24 kW

5.04 kW

COP Tj = +2°C

4.69

3.19

Cdh Tj = +2 °C

0.980

0.984

Pdh Tj = +7°C

6.79 kW

6.15 kW

COP Tj = +7°C

5.82

4.07

Cdh Tj = +7 °C

0.978

0.983

Pdh Tj = 12°C

7.62 kW

7.56 kW

COP Tj = 12°C

6.94

5.73

Cdh Tj = +12 °C

0.976

0.980

Pdh Tj = Tbiv

11.70 kW

9.01 kW

COP Tj = Tbiv

2.72

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.72

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5234 kWh

5777 kWh

Buderus Logatherm WPLS11.2 RT-T
Configure model
Model name
Buderus Logatherm WPLS11.2 RT-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

13.45 kW

El input

1.32 kW

5.69 kW

COP

4.85

2.37

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

154 %

Prated

11.88 kW

10.49 kW

SCOP

5.44

3.93

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.90 kW

10.50 kW

COP Tj = +2°C

3.29

2.13

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

7.53 kW

6.85 kW

COP Tj = +7°C

5.42

3.44

Cdh Tj = +7 °C

0.987

0.987

Pdh Tj = 12°C

7.52 kW

7.52 kW

COP Tj = 12°C

6.27

5.18

Cdh Tj = +12 °C

0.982

0.982

Pdh Tj = Tbiv

11.90 kW

10.50 kW

COP Tj = Tbiv

3.29

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.90 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.29

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2917 kWh

3563 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

146 %

112 %

Prated

11.40 kW

10.10 kW

SCOP

3.72

2.87

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

6.78 kW

6.19 kW

COP Tj = -7°C

3.48

2.61

Cdh Tj = -7 °C

0.987

0.989

Pdh Tj = +2°C

5.73 kW

5.06 kW

COP Tj = +2°C

4.87

3.51

Cdh Tj = +2 °C

0.978

0.982

Pdh Tj = +7°C

6.79 kW

6.49 kW

COP Tj = +7°C

5.92

4.57

Cdh Tj = +7 °C

0.977

0.982

Pdh Tj = 12°C

7.63 kW

7.69 kW

COP Tj = 12°C

6.89

6.02

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

10.28 kW

9.01 kW

COP Tj = Tbiv

2.57

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.28 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.57

1.87

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.40 kW

10.10 kW

Annual energy consumption Qhe

7564 kWh

8660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.28

1.87

COP Tj = -15°C (if TOL<-20°C)

2.57

1.87

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

11.70 kW

9.01 kW

SCOP

4.62

3.22

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.04 kW

7.98 kW

COP Tj = -7°C

2.85

2.04

Cdh Tj = -7 °C

0.993

0.993

Pdh Tj = +2°C

6.24 kW

5.04 kW

COP Tj = +2°C

4.69

3.19

Cdh Tj = +2 °C

0.980

0.984

Pdh Tj = +7°C

6.79 kW

6.15 kW

COP Tj = +7°C

5.82

4.07

Cdh Tj = +7 °C

0.978

0.983

Pdh Tj = 12°C

7.62 kW

7.56 kW

COP Tj = 12°C

6.94

5.73

Cdh Tj = +12 °C

0.976

0.980

Pdh Tj = Tbiv

11.70 kW

9.01 kW

COP Tj = Tbiv

2.72

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.72

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5234 kWh

5777 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.03

Heating up time

01:03 h:min

Standby power input

70.0 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

254 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.69

Heating up time

01:32 h:min

Standby power input

130.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.89

Heating up time

01:20 h:min

Standby power input

80.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

251 l

Buderus Logatherm WPLS11.2 RTS-T
Configure model
Model name
Buderus Logatherm WPLS11.2 RTS-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

13.45 kW

El input

1.32 kW

5.69 kW

COP

4.85

2.37

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

215 %

154 %

Prated

11.88 kW

10.49 kW

SCOP

5.44

3.93

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

11.90 kW

10.50 kW

COP Tj = +2°C

3.29

2.13

Cdh Tj = +2 °C

0.995

0.995

Pdh Tj = +7°C

7.53 kW

6.85 kW

COP Tj = +7°C

5.42

3.44

Cdh Tj = +7 °C

0.987

0.987

Pdh Tj = 12°C

7.52 kW

7.52 kW

COP Tj = 12°C

6.27

5.18

Cdh Tj = +12 °C

0.982

0.982

Pdh Tj = Tbiv

11.90 kW

10.50 kW

COP Tj = Tbiv

3.29

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.90 kW

10.50 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.29

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2917 kWh

3563 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

146 %

112 %

Prated

11.40 kW

10.10 kW

SCOP

3.72

2.87

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

6.78 kW

6.19 kW

COP Tj = -7°C

3.48

2.61

Cdh Tj = -7 °C

0.987

0.989

Pdh Tj = +2°C

5.73 kW

5.06 kW

COP Tj = +2°C

4.87

3.51

Cdh Tj = +2 °C

0.978

0.982

Pdh Tj = +7°C

6.79 kW

6.49 kW

COP Tj = +7°C

5.92

4.57

Cdh Tj = +7 °C

0.977

0.982

Pdh Tj = 12°C

7.63 kW

7.69 kW

COP Tj = 12°C

6.89

6.02

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

10.28 kW

9.01 kW

COP Tj = Tbiv

2.57

1.87

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.28 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.57

1.87

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

11.40 kW

10.10 kW

Annual energy consumption Qhe

7564 kWh

8660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.28

9.01

COP Tj = -15°C (if TOL<-20°C)

2.57

1.87

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

126 %

Prated

11.70 kW

9.01 kW

SCOP

4.62

3.22

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.04 kW

7.98 kW

COP Tj = -7°C

2.85

2.04

Cdh Tj = -7 °C

0.993

0.993

Pdh Tj = +2°C

6.24 kW

5.04 kW

COP Tj = +2°C

4.69

3.19

Cdh Tj = +2 °C

0.980

0.984

Pdh Tj = +7°C

6.79 kW

6.15 kW

COP Tj = +7°C

5.82

4.07

Cdh Tj = +7 °C

0.978

0.983

Pdh Tj = 12°C

7.62 kW

7.56 kW

COP Tj = 12°C

6.94

5.73

Cdh Tj = +12 °C

0.976

0.980

Pdh Tj = Tbiv

11.70 kW

9.01 kW

COP Tj = Tbiv

2.72

1.62

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.70 kW

9.01 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.72

1.62

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5234 kWh

5777 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

77 %

COP

1.79

Heating up time

01:02 h:min

Standby power input

86.5 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

249 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

74 %

COP

1.66

Heating up time

01:05 h:min

Standby power input

132.6 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.74

Heating up time

01:18 h:min

Standby power input

85.7 W

Reference hot water temperature

51.1 °C

Mixed water at 40°C

236 l

Buderus Logatherm WPLS13.2 RE-S
Configure model
Model name
Buderus Logatherm WPLS13.2 RE-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

14.44 kW

El input

1.32 kW

6.23 kW

COP

4.92

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Buderus Logatherm WPLS13.2 RB-S
Configure model
Model name
Buderus Logatherm WPLS13.2 RB-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

14.44 kW

El input

1.32 kW

6.23 kW

COP

4.92

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Buderus Logatherm WPLS13.2 RT-S
Configure model
Model name
Buderus Logatherm WPLS13.2 RT-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

14.44 kW

El input

1.32 kW

6.23 kW

COP

4.92

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

1.75

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

108 %

COP

2.52

Heating up time

01:01 h:min

Standby power input

55.0 W

Reference hot water temperature

51.3 °C

Mixed water at 40°C

253 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

69 %

COP

1.57

Heating up time

01:29 h:min

Standby power input

114.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.92

Heating up time

01:38 h:min

Standby power input

70.0 W

Reference hot water temperature

52.3 °C

Mixed water at 40°C

267 l

Buderus Logatherm WPLS13.2 RTS-S
Configure model
Model name
Buderus Logatherm WPLS13.2 RTS-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

14.44 kW

El input

1.32 kW

6.23 kW

COP

4.92

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.22

Heating up time

01:00 h:min

Standby power input

68.0 W

Reference hot water temperature

50.3 °C

Mixed water at 40°C

248 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

67 %

COP

1.54

Heating up time

01:04 h:min

Standby power input

116.3 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

76 %

COP

1.76

Heating up time

01:36 h:min

Standby power input

75.0 W

Reference hot water temperature

51.2 °C

Mixed water at 40°C

251 l

Buderus Logatherm WPLS13.2 RB-T
Configure model
Model name
Buderus Logatherm WPLS13.2 RB-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

14.29 kW

El input

1.32 kW

6.16 kW

COP

4.85

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Buderus Logatherm WPLS13.2 RE-T
Configure model
Model name
Buderus Logatherm WPLS13.2 RE-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

14.29 kW

El input

1.32 kW

6.16 kW

COP

4.85

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Buderus Logatherm WPLS13.2 RTS-T
Configure model
Model name
Buderus Logatherm WPLS13.2 RTS-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

14.29 kW

El input

1.32 kW

6.16 kW

COP

4.85

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

77 %

COP

1.79

Heating up time

01:02 h:min

Standby power input

86.5 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

249 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

74 %

COP

1.66

Heating up time

01:05 h:min

Standby power input

132.6 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.74

Heating up time

01:18 h:min

Standby power input

85.7 W

Reference hot water temperature

51.1 °C

Mixed water at 40°C

236 l

Buderus Logatherm WPLS13.2 RT-T
Configure model
Model name
Buderus Logatherm WPLS13.2 RT-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

14.29 kW

El input

1.32 kW

6.16 kW

COP

4.85

2.32

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

1.96

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.03

Heating up time

01:03 h:min

Standby power input

70.0 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

254 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.69

Heating up time

01:32 h:min

Standby power input

130.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.89

Heating up time

01:20 h:min

Standby power input

80.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

251 l

Buderus Logatherm WPLS15.2 RB-S
Configure model
Model name
Buderus Logatherm WPLS15.2 RB-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

15.30 kW

El input

1.32 kW

6.74 kW

COP

4.92

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Buderus Logatherm WPLS15.2 RE-S
Configure model
Model name
Buderus Logatherm WPLS15.2 RE-S
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

15.30 kW

El input

1.32 kW

6.74 kW

COP

4.92

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Buderus Logatherm WPLS15.2 RT-S
Configure model
Model name
Buderus Logatherm WPLS15.2 RT-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

15.30 kW

El input

1.32 kW

6.74 kW

COP

4.92

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

1.75

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

108 %

COP

2.52

Heating up time

01:01 h:min

Standby power input

55.0 W

Reference hot water temperature

51.3 °C

Mixed water at 40°C

253 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

69 %

COP

1.57

Heating up time

01:29 h:min

Standby power input

114.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.92

Heating up time

01:38 h:min

Standby power input

70.0 W

Reference hot water temperature

52.3 °C

Mixed water at 40°C

267 l

Buderus Logatherm WPLS15.2 RTS-S
Configure model
Model name
Buderus Logatherm WPLS15.2 RTS-S
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.48 kW

15.30 kW

El input

1.32 kW

6.74 kW

COP

4.92

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

225 %

143 %

Prated

12.36 kW

7.51 kW

SCOP

5.71

3.65

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.37 kW

7.55 kW

COP Tj = +2°C

3.20

1.37

Cdh Tj = +2 °C

0.998

0.999

Pdh Tj = +7°C

7.83 kW

5.48 kW

COP Tj = +7°C

5.46

3.22

Cdh Tj = +7 °C

0.995

0.996

Pdh Tj = 12°C

7.66 kW

7.04 kW

COP Tj = 12°C

6.64

4.96

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

12.37 kW

7.55 kW

COP Tj = Tbiv

3.20

1.37

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.37 kW

7.55 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.20

1.37

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2893 kWh

2746 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

141 %

111 %

Prated

13.42 kW

12.18 kW

SCOP

3.60

2.86

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.07 kW

7.22 kW

COP Tj = -7°C

3.21

2.43

Cdh Tj = -7 °C

0.997

0.998

Pdh Tj = +2°C

5.95 kW

5.16 kW

COP Tj = +2°C

5.12

3.65

Cdh Tj = +2 °C

0.994

0.995

Pdh Tj = +7°C

6.07 kW

6.54 kW

COP Tj = +7°C

4.80

4.74

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

6.43 kW

6.93 kW

COP Tj = 12°C

4.83

4.99

Cdh Tj = +12 °C

0.995

0.995

Pdh Tj = Tbiv

10.95 kW

9.94 kW

COP Tj = Tbiv

2.36

1.75

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.95 kW

9.94 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.36

1.75

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.998

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.42 kW

12.18 kW

Annual energy consumption Qhe

9181 kWh

10512 kWh

Pdh Tj = -15°C (if TOL<-20°C)

10.95

9.94

COP Tj = -15°C (if TOL<-20°C)

2.36

1.75

Cdh Tj = -15 °C

0.998

0.999

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

171 %

134 %

Prated

13.04 kW

11.50 kW

SCOP

4.35

3.43

Tbiv

-10 °C

-9 °C

TOL

-10 °C

-9 °C

Pdh Tj = -7°C

10.79 kW

10.00 kW

COP Tj = -7°C

2.74

1.96

Cdh Tj = -7 °C

0.998

0.999

Pdh Tj = +2°C

6.91 kW

6.01 kW

COP Tj = +2°C

4.30

3.47

Cdh Tj = +2 °C

0.996

0.996

Pdh Tj = +7°C

6.61 kW

6.56 kW

COP Tj = +7°C

5.49

4.55

Cdh Tj = +7 °C

0.994

0.995

Pdh Tj = 12°C

7.60 kW

7.24 kW

COP Tj = 12°C

6.62

5.20

Cdh Tj = +12 °C

0.994

0.995

Pdh Tj = Tbiv

13.05 kW

11.07 kW

COP Tj = Tbiv

2.60

1.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

13.05 kW

11.07 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.60

1.72

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.999

0.999

WTOL

57 °C

57 °C

Poff

7 W

7 W

PTO

7 W

7 W

PSB

7 W

7 W

PCK

35 W

35 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

11.50 kW

Annual energy consumption Qhe

6194 kWh

6924 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

95 %

COP

2.22

Heating up time

01:00 h:min

Standby power input

68.0 W

Reference hot water temperature

50.3 °C

Mixed water at 40°C

248 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

67 %

COP

1.54

Heating up time

01:04 h:min

Standby power input

116.3 W

Reference hot water temperature

50.6 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

76 %

COP

1.76

Heating up time

01:36 h:min

Standby power input

75.0 W

Reference hot water temperature

51.2 °C

Mixed water at 40°C

251 l

Buderus Logatherm WPLS15.2 RB-T
Configure model
Model name
Buderus Logatherm WPLS15.2 RB-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

15.10 kW

El input

1.32 kW

6.64 kW

COP

4.85

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Buderus Logatherm WPLS15.2 RE-T
Configure model
Model name
Buderus Logatherm WPLS15.2 RE-T
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

15.10 kW

El input

1.32 kW

6.64 kW

COP

4.85

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Buderus Logatherm WPLS15.2 RTS-T
Configure model
Model name
Buderus Logatherm WPLS15.2 RTS-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

15.10 kW

El input

1.32 kW

6.64 kW

COP

4.85

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

10.05

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

77 %

COP

1.79

Heating up time

01:02 h:min

Standby power input

86.5 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

249 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

74 %

COP

1.66

Heating up time

01:05 h:min

Standby power input

132.6 W

Reference hot water temperature

50.5 °C

Mixed water at 40°C

253 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.74

Heating up time

01:18 h:min

Standby power input

85.7 W

Reference hot water temperature

51.1 °C

Mixed water at 40°C

236 l

Buderus Logatherm WPLS15.2 RT-T
Configure model
Model name
Buderus Logatherm WPLS15.2 RT-T
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6.41 kW

15.10 kW

El input

1.32 kW

6.64 kW

COP

4.85

2.27

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

209 %

155 %

Prated

12.67 kW

11.18 kW

SCOP

5.31

3.94

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

12.67 kW

11.18 kW

COP Tj = +2°C

3.32

2.13

Cdh Tj = +2 °C

0.993

0.995

Pdh Tj = +7°C

8.28 kW

7.27 kW

COP Tj = +7°C

4.96

3.48

Cdh Tj = +7 °C

0.984

0.988

Pdh Tj = 12°C

7.50 kW

7.21 kW

COP Tj = 12°C

6.42

5.12

Cdh Tj = +12 °C

0.978

0.982

Pdh Tj = Tbiv

12.67 kW

11.18 kW

COP Tj = Tbiv

3.32

2.13

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.67 kW

11.18 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.32

2.13

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.993

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3186 kWh

3787 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

144 %

111 %

Prated

13.89 kW

12.32 kW

SCOP

3.67

2.85

Tbiv

-15 °C

-15 °C

TOL

-15 °C

-15 °C

Pdh Tj = -7°C

8.50 kW

7.49 kW

COP Tj = -7°C

3.35

2.38

Cdh Tj = -7 °C

0.990

0.992

Pdh Tj = +2°C

6.02 kW

5.72 kW

COP Tj = +2°C

4.86

3.65

Cdh Tj = +2 °C

0.979

0.983

Pdh Tj = +7°C

6.72 kW

6.47 kW

COP Tj = +7°C

5.66

4.54

Cdh Tj = +7 °C

0.978

0.982

Pdh Tj = 12°C

7.51 kW

7.33 kW

COP Tj = 12°C

6.54

5.61

Cdh Tj = +12 °C

0.977

0.980

Pdh Tj = Tbiv

11.33 kW

10.05 kW

COP Tj = Tbiv

2.61

1.96

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

11.33 kW

10.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.61

1.96

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.994

0.995

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

13.89 kW

12.32 kW

Annual energy consumption Qhe

9329 kWh

10660 kWh

Pdh Tj = -15°C (if TOL<-20°C)

11.33

1.96

COP Tj = -15°C (if TOL<-20°C)

2.61

1.96

Cdh Tj = -15 °C

0.994

0.995

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

35 dB(A)

35 dB(A)

Sound power level outdoor

67 dB(A)

67 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

167 %

129 %

Prated

12.32 kW

11.30 kW

SCOP

4.25

3.29

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

10.78 kW

10.02 kW

COP Tj = -7°C

2.79

2.03

Cdh Tj = -7 °C

0.993

0.995

Pdh Tj = +2°C

6.45 kW

6.06 kW

COP Tj = +2°C

4.45

3.28

Cdh Tj = +2 °C

0.982

0.986

Pdh Tj = +7°C

6.29 kW

6.40 kW

COP Tj = +7°C

4.93

4.27

Cdh Tj = +7 °C

0.980

0.983

Pdh Tj = 12°C

6.99 kW

7.28 kW

COP Tj = 12°C

5.64

5.09

Cdh Tj = +12 °C

0.979

0.982

Pdh Tj = Tbiv

12.33 kW

11.30 kW

COP Tj = Tbiv

2.48

1.81

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

12.33 kW

11.30 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.48

1.81

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.995

0.996

WTOL

57 °C

57 °C

Poff

26 W

26 W

PTO

26 W

26 W

PSB

26 W

26 W

PCK

53 W

53 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

5994 kWh

7088 kWh

Domestic Hot Water (DHW)

Warmer Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

87 %

COP

2.03

Heating up time

01:03 h:min

Standby power input

70.0 W

Reference hot water temperature

51.5 °C

Mixed water at 40°C

254 l

Colder Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

75 %

COP

1.69

Heating up time

01:32 h:min

Standby power input

130.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

258 l

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

82 %

COP

1.89

Heating up time

01:20 h:min

Standby power input

80.0 W

Reference hot water temperature

52.1 °C

Mixed water at 40°C

251 l