1,100 kg
Heating
EN 14511-2
A35/A27
Heating capacity
5.57
El input
1.50 kW
COP
3.71
Cooling
EN 14511-2
El input
1.55 kW
Cooling capacity
5.30
EER
3.42
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
EN 12102-1
Sound power level indoor
56 dB(A)
Sound power level outdoor
64 dB(A)
EN 14825
Indoor dry(wet) bulb temperature 27(19)°C
Pdesignc
5.30 kW
SEER
7.50
Pdc Tj = 35°C
5.30 kW
EER Tj = 35°C
3.58
Pdc Tj = 30°C
3.89 kW
EER Tj = 30°C
5.03
Cdc Tj = 30 °C
0.3
Pdc Tj = 25°C
2.47 kW
EER Tj = 25°C
9.31
Cdc Tj = 25 °C
0.3
Pdc Tj = 20°C
1.97 kW
EER Tj = 20°C
14.57
Cdc Tj = 20 °C
0.3
Poff
1 W
PTO
11 W
PSB
1 W
PCK
0 W
Annual energy consumption Qce
247 kWh
Average Climate
EN 14825
Indoor dry bulb temperature: 20°C
Pdesignh
4.20 kW
SCOP
4.00
Tbiv
-7 °C
TOL
-15 °C
Pdh Tj = -7°C
3.72 kW
COP Tj = -7°C
2.73
Cdh Tj = -7 °C
0.250
Pdh Tj = +2°C
2.45 kW
COP Tj = +2°C
4.03
Cdh Tj = +2 °C
0.250
Pdh Tj = +7°C
1.55 kW
COP Tj = +7°C
4.92
Cdh Tj = +7 °C
0.250
Pdh Tj = 12°C
1.58 kW
COP Tj = 12°C
6.07
Cdh Tj = +12 °C
0.250
Pdh Tj = Tbiv
3.72 kW
COP Tj = Tbiv
2.73
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.45 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.57
Poff
1 W
PTO
11 W
PSB
1 W
PCK
0 W
Backup Heater
0.00 kW
Annual energy consumption Qhe
1470 kWh