0,620 kg
Heating
EN 14511-2
A35/A27
Heating capacity
2.93
El input
0.67 kW
COP
4.40
Cooling
EN 14511-2
El input
0.63 kW
Cooling capacity
2.60
EER
4.14
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Starting and operating test
passed
EN 12102-1
Sound power level indoor
53 dB(A)
Sound power level outdoor
59 dB(A)
EN 14825
Indoor dry(wet) bulb temperature 27(19)°C
Pdesignc
2.60 kW
SEER
8.80
Pdc Tj = 35°C
2.60 kW
EER Tj = 35°C
4.20
Pdc Tj = 30°C
1.75 kW
EER Tj = 30°C
6.66
Cdc Tj = 30 °C
0.3
Pdc Tj = 25°C
1.11 kW
EER Tj = 25°C
10.90
Cdc Tj = 25 °C
0.3
Pdc Tj = 20°C
0.90 kW
EER Tj = 20°C
15.00
Cdc Tj = 20 °C
0.3
Poff
1 W
PTO
12 W
PSB
1 W
PCK
0 W
Annual energy consumption Qce
103 kWh
Average Climate
EN 14825
Indoor dry bulb temperature: 20°C
Pdesignh
2.40 kW
SCOP
4.60
Tbiv
-7 °C
TOL
-15 °C
Pdh Tj = -7°C
2.12 kW
COP Tj = -7°C
3.20
Cdh Tj = -7 °C
0.250
Pdh Tj = +2°C
1.30 kW
COP Tj = +2°C
4.60
Cdh Tj = +2 °C
0.250
Pdh Tj = +7°C
0.84 kW
COP Tj = +7°C
5.60
Cdh Tj = +7 °C
0.250
Pdh Tj = 12°C
0.60 kW
COP Tj = 12°C
6.50
Cdh Tj = +12 °C
0.250
Pdh Tj = Tbiv
2.12 kW
COP Tj = Tbiv
3.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.39 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
Poff
1 W
PTO
12 W
PSB
1 W
PCK
0 W
Backup Heater
0.00 kW
Annual energy consumption Qhe
730 kWh