Certificate holders

Subtype

19. Yutaki M 4.0HP (mono)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-19
Certification Body
BRE Global Limited
Subtype title
19. Yutaki M 4.0HP (mono)
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

2,800 kg

Certification Date
n/a
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

RASM-4VNE - Heating Only
Configure model
Model name
RASM-4VNE - Heating Only
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

136 %

Prated

11.00 kW

10.00 kW

SCOP

4.75

3.48

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.60 kW

8.60 kW

COP Tj = -7°C

2.74

1.80

Pdh Tj = +2°C

5.84 kW

5.23 kW

COP Tj = +2°C

5.20

3.60

Pdh Tj = +7°C

3.76 kW

3.52 kW

COP Tj = +7°C

5.80

4.80

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

6.40

5.80

Pdh Tj = Tbiv

9.60 kW

8.60 kW

COP Tj = Tbiv

2.74

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

8.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

13 W

13 W

PTO

0 W

0 W

PSB

13 W

13 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.20 kW

Annual energy consumption Qhe

4714 kWh

5786 kWh

RASM-4VNE - with cooling kit
Configure model
Model name
RASM-4VNE - with cooling kit
Application
Heating (medium temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

11.00 kW

11.00 kW

El input

2.20 kW

3.67 kW

COP

5.00

3.00

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

64 dB(A)

64 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

189 %

137 %

Prated

11.00 kW

10.00 kW

SCOP

4.80

3.50

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.60 kW

8.60 kW

COP Tj = -7°C

2.74

1.80

Pdh Tj = +2°C

5.84 kW

5.23 kW

COP Tj = +2°C

5.20

3.60

Pdh Tj = +7°C

3.76 kW

3.52 kW

COP Tj = +7°C

5.80

4.80

Pdh Tj = 12°C

3.70 kW

3.60 kW

COP Tj = 12°C

6.40

5.80

Pdh Tj = Tbiv

9.60 kW

8.60 kW

COP Tj = Tbiv

2.74

1.80

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.50 kW

8.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.65

1.90

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

13 W

13 W

PTO

0 W

0 W

PSB

13 W

13 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.50 kW

1.20 kW

Annual energy consumption Qhe

4666 kWh

5738 kWh