2,400 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.50 kW
7.50 kW
El input
1.65 kW
2.78 kW
COP
4.55
2.70
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
125 %
Prated
7.00 kW
6.00 kW
SCOP
4.18
3.20
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.50
1.84
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.40
3.20
Pdh Tj = +7°C
2.31 kW
2.00 kW
COP Tj = +7°C
5.35
4.45
Pdh Tj = 12°C
2.10 kW
2.30 kW
COP Tj = 12°C
6.15
5.96
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.50
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.40 kW
5.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.60 kW
0.60 kW
Annual energy consumption Qhe
3298 kWh
3726 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
7.50 kW
7.50 kW
El input
1.65 kW
2.78 kW
COP
4.55
2.70
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
64 dB(A)
64 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
167 %
127 %
Prated
7.00 kW
6.00 kW
SCOP
4.25
3.25
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.90 kW
5.10 kW
COP Tj = -7°C
2.50
1.84
Pdh Tj = +2°C
3.59 kW
3.10 kW
COP Tj = +2°C
4.40
3.20
Pdh Tj = +7°C
2.31 kW
2.00 kW
COP Tj = +7°C
5.35
4.45
Pdh Tj = 12°C
2.10 kW
2.30 kW
COP Tj = 12°C
6.15
5.96
Pdh Tj = Tbiv
5.90 kW
5.10 kW
COP Tj = Tbiv
2.50
1.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
6.40 kW
5.20 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
1.65
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
15 W
15 W
PTO
0 W
0 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.60 kW
0.60 kW
Annual energy consumption Qhe
3242 kWh
3671 kWh