Certificate holders

Subtype

TTF 87.5

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0460
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 87.5
Driving energy
Electricity
Heat Pump Type
Brine/Water
Refrigerant
R410A
Mass of Refrigerant

9,000 kg

Certification Date
15.03.2021
Testing basis
HP KEYMARK certification scheme rules V8
Generate PDF Export model CSV
  • Number of models 1

Models

TTF 87.5
Configure model
Model name
TTF 87.5
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

52.18 kW

48.32 kW

El input

11.09 kW

17.02 kW

COP

4.71

2.84

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

failed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

202 %

160 %

Prated

84.67 kW

79.00 kW

SCOP

5.25

4.21

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

84.67 kW

79.00 kW

COP Tj = +2°C

3.97

2.72

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

54.43 kW

50.79 kW

COP Tj = +7°C

4.85

3.60

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

24.19 kW

24.07 kW

COP Tj = 12°C

5.85

5.16

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

84.67 kW

79.00 kW

COP Tj = Tbiv

3.97

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

84.67 kW

79.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.97

2.72

WTOL

65 °C

65 °C

Poff

9 W

9 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

21524 kWh

23056 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

204 %

165 %

Prated

84.67 kW

79.00 kW

SCOP

5.30

4.32

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

51.25 kW

48.52 kW

COP Tj = -7°C

5.06

3.85

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

31.20 kW

29.11 kW

COP Tj = +2°C

5.81

4.83

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

24.49 kW

24.11 kW

COP Tj = +7°C

5.85

5.20

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

24.39 kW

24.22 kW

COP Tj = 12°C

5.66

5.27

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

84.67 kW

79.00 kW

COP Tj = Tbiv

3.97

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

84.67 kW

79.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.97

2.72

WTOL

65 °C

65 °C

Poff

9 W

9 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

39378 kWh

45048 kWh

Pdh Tj = -15°C (if TOL<-20°C)

84.67

79.00

COP Tj = -15°C (if TOL<-20°C)

3.97

2.72

Cdh Tj = -15 °C

0.90

0.90

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

50 dB(A)

50 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

199 %

157 %

Prated

84.67 kW

79.00 kW

SCOP

5.17

4.13

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

74.90 kW

69.88 kW

COP Tj = -7°C

4.26

3.00

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

45.59 kW

42.54 kW

COP Tj = +2°C

5.14

4.08

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

29.31 kW

27.35 kW

COP Tj = +7°C

5.81

4.94

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

24.37 kW

24.08 kW

COP Tj = 12°C

5.65

5.16

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

84.67 kW

79.00 kW

COP Tj = Tbiv

3.97

2.72

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

84.67 kW

79.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.97

2.72

WTOL

65 °C

65 °C

Poff

9 W

9 W

PTO

11 W

11 W

PSB

11 W

11 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

n/a

n/a

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

33804 kWh

39457 kWh