0,970 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.35 kW
3.70 kW
El input
0.68 kW
1.40 kW
COP
4.95
2.63
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
119 %
Prated
4.40 kW
4.00 kW
SCOP
4.46
3.04
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.90 kW
3.50 kW
COP Tj = -7°C
3.12
1.81
Cdh Tj = -7 °C
1.000
1.000
Pdh Tj = +2°C
2.40 kW
2.20 kW
COP Tj = +2°C
4.26
2.98
Cdh Tj = +2 °C
1.000
1.000
Pdh Tj = +7°C
2.00 kW
1.80 kW
COP Tj = +7°C
5.90
4.07
Cdh Tj = +7 °C
1.000
1.000
Pdh Tj = 12°C
2.30 kW
2.20 kW
COP Tj = 12°C
6.87
5.78
Cdh Tj = +12 °C
1.000
1.000
Pdh Tj = Tbiv
3.90 kW
3.50 kW
COP Tj = Tbiv
3.12
1.81
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
3.90 kW
3.30 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.72
1.61
WTOL
55 °C
55 °C
Poff
4 W
4 W
PTO
9 W
9 W
PSB
8 W
8 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.48 kW
0.65 kW
Annual energy consumption Qhe
2040 kWh
2715 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.10
Heating up time
1:45 h:min
Standby power input
30.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
245 l