5,000 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
20.00 kW
20.00 kW
El input
4.65 kW
7.35 kW
COP
4.30
2.72
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
150 %
120 %
Prated
18.00 kW
16.00 kW
SCOP
3.83
3.08
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.60 kW
13.80 kW
COP Tj = -7°C
2.50
1.65
Pdh Tj = +2°C
9.50 kW
8.40 kW
COP Tj = +2°C
3.85
3.20
Pdh Tj = +7°C
6.10 kW
6.00 kW
COP Tj = +7°C
5.40
4.50
Pdh Tj = 12°C
7.00 kW
6.80 kW
COP Tj = 12°C
4.65
4.50
Pdh Tj = Tbiv
15.60 kW
13.80 kW
COP Tj = Tbiv
2.50
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.00 kW
12.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
36 W
36 W
PTO
0 W
0 W
PSB
36 W
36 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
3.50 kW
Annual energy consumption Qhe
9513 kWh
10452 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
20.00 kW
20.00 kW
El input
4.65 kW
7.35 kW
COP
4.30
2.72
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
47 dB(A)
47 dB(A)
Sound power level outdoor
73 dB(A)
73 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
122 %
Prated
18.00 kW
16.00 kW
SCOP
3.88
3.13
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
15.60 kW
13.80 kW
COP Tj = -7°C
2.50
1.65
Pdh Tj = +2°C
9.50 kW
8.40 kW
COP Tj = +2°C
3.85
3.20
Pdh Tj = +7°C
6.10 kW
6.00 kW
COP Tj = +7°C
5.40
4.50
Pdh Tj = 12°C
7.00 kW
6.80 kW
COP Tj = 12°C
4.65
4.50
Pdh Tj = Tbiv
15.60 kW
13.80 kW
COP Tj = Tbiv
2.50
1.65
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
16.00 kW
12.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.40
1.50
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
36 W
36 W
PTO
0 W
0 W
PSB
36 W
36 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.60 kW
3.50 kW
Annual energy consumption Qhe
9382 kWh
10320 kWh