Certificate holders

Subtype

10. Yutaki S 8.0HP (tri)

Certificate Holder
Johnson Controls-Hitachi AirConditioning Spain
Ronda Shimizu, 1. Pol. Ind. Can Torrella
08233 Vacarisses, Barcelona
Spain
Registration number
041-K002-10
Certification Body
BRE Global Limited
Subtype title
10. Yutaki S 8.0HP (tri)
Driving energy
n/a
Heat Pump Type
Outdoor Air/Water
Refrigerant
R410A
Mass of Refrigerant

5,000 kg

Certification Date
n/a
Testing basis
n/a
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

RAS-8WHNPE RWM-8.0NE - Heating Only
Configure model
Model name
RAS-8WHNPE RWM-8.0NE - Heating Only
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

20.00 kW

20.00 kW

El input

4.65 kW

7.35 kW

COP

4.30

2.72

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

73 dB(A)

73 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

150 %

120 %

Prated

18.00 kW

16.00 kW

SCOP

3.83

3.08

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

15.60 kW

13.80 kW

COP Tj = -7°C

2.50

1.65

Pdh Tj = +2°C

9.50 kW

8.40 kW

COP Tj = +2°C

3.85

3.20

Pdh Tj = +7°C

6.10 kW

6.00 kW

COP Tj = +7°C

5.40

4.50

Pdh Tj = 12°C

7.00 kW

6.80 kW

COP Tj = 12°C

4.65

4.50

Pdh Tj = Tbiv

15.60 kW

13.80 kW

COP Tj = Tbiv

2.50

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.00 kW

12.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.40

1.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

36 W

36 W

PTO

0 W

0 W

PSB

36 W

36 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.60 kW

3.50 kW

Annual energy consumption Qhe

9513 kWh

10452 kWh

RAS-8WHNPE RWM-8.0NE - with cooling kit
Configure model
Model name
RAS-8WHNPE RWM-8.0NE - with cooling kit
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-4

Operating range outdoor exchanger/indoor exchanger lower limit/lower limit

passed

Operating range outdoor exchanger/indoor exchanger upper limit/upper limit

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

20.00 kW

20.00 kW

El input

4.65 kW

7.35 kW

COP

4.30

2.72

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

47 dB(A)

47 dB(A)

Sound power level outdoor

73 dB(A)

73 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

152 %

122 %

Prated

18.00 kW

16.00 kW

SCOP

3.88

3.13

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

15.60 kW

13.80 kW

COP Tj = -7°C

2.50

1.65

Pdh Tj = +2°C

9.50 kW

8.40 kW

COP Tj = +2°C

3.85

3.20

Pdh Tj = +7°C

6.10 kW

6.00 kW

COP Tj = +7°C

5.40

4.50

Pdh Tj = 12°C

7.00 kW

6.80 kW

COP Tj = 12°C

4.65

4.50

Pdh Tj = Tbiv

15.60 kW

13.80 kW

COP Tj = Tbiv

2.50

1.65

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.00 kW

12.10 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.40

1.50

Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

0.90

0.90

WTOL

55 °C

55 °C

Poff

36 W

36 W

PTO

0 W

0 W

PSB

36 W

36 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.60 kW

3.50 kW

Annual energy consumption Qhe

9382 kWh

10320 kWh