0,900 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
155 %
COP
3.88
Heating up time
1:28 h:min
Standby power input
27.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:28 h:min
Standby power input
33.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:28 h:min
Standby power input
30.0 W
Reference hot water temperature
52.4 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
154 %
COP
3.86
Heating up time
1:32 h:min
Standby power input
28.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:32 h:min
Standby power input
34.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
129 %
COP
3.23
Heating up time
1:32 h:min
Standby power input
31.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
3.20 kW
3.20 kW
El input
0.60 kW
1.14 kW
COP
5.33
2.81
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
0.91 kW
0.68 kW
Cooling capacity
3.20
3.20
EER
3.52
4.71
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
3.00 kW
kW
SEER
6.29
Pdc Tj = 35°C
3.00 kW
kW
EER Tj = 35°C
3.95
Pdc Tj = 30°C
2.21 kW
kW
EER Tj = 30°C
5.37
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.42 kW
kW
EER Tj = 25°C
7.44
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.63 kW
kW
EER Tj = 20°C
8.93
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
167 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.940
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
4.00 kW
3.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.50 kW
2.60 kW
COP Tj = -7°C
2.80
2.18
Cdh Tj = -7 °C
0.980
0.980
Pdh Tj = +2°C
2.00 kW
1.60 kW
COP Tj = +2°C
5.14
3.42
Cdh Tj = +2 °C
0.930
0.940
Pdh Tj = +7°C
1.40 kW
1.10 kW
COP Tj = +7°C
6.80
4.43
Cdh Tj = +7 °C
0.870
0.900
Pdh Tj = 12°C
1.60 kW
1.40 kW
COP Tj = 12°C
9.50
6.97
Cdh Tj = +12 °C
0.840
0.570
Pdh Tj = Tbiv
4.00 kW
2.90 kW
COP Tj = Tbiv
2.60
1.66
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
2.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.60
1.66
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
1631 kWh
1788 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
154 %
COP
3.86
Heating up time
1:32 h:min
Standby power input
28.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:32 h:min
Standby power input
34.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
129 %
COP
3.23
Heating up time
1:32 h:min
Standby power input
31.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
154 %
COP
3.86
Heating up time
1:32 h:min
Standby power input
28.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:32 h:min
Standby power input
34.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
129 %
COP
3.23
Heating up time
1:32 h:min
Standby power input
31.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.00 kW
5.00 kW
El input
1.00 kW
1.84 kW
COP
5.00
2.72
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Cooling
EN 14511-2
+7°C/+12°C
+18°C/+23°C
El input
1.50 kW
1.12 kW
Cooling capacity
4.50
4.80
EER
3.00
4.29
EN 14825
+7°C/+12°C
+18°C/+23°C
Pdesignc
4.00 kW
kW
SEER
6.20
Pdc Tj = 35°C
4.00 kW
kW
EER Tj = 35°C
3.47
Pdc Tj = 30°C
2.95 kW
kW
EER Tj = 30°C
5.12
Cdc Tj = 30 °C
0.9
Pdc Tj = 25°C
1.89 kW
kW
EER Tj = 25°C
7.31
Cdc Tj = 25 °C
0.9
Pdc Tj = 20°C
0.84 kW
kW
EER Tj = 20°C
9.26
Cdc Tj = 20 °C
0.9
Poff
5 W
W
PTO
0 W
W
PSB
5 W
W
PCK
0 W
W
Annual energy consumption Qce
226 kWh
kWh
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
245 %
165 %
Prated
4.00 kW
4.00 kW
SCOP
6.20
4.20
Tbiv
2 °C
2 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
4.00 kW
3.90 kW
COP Tj = +2°C
3.15
1.80
Cdh Tj = +2 °C
0.980
0.990
Pdh Tj = +7°C
2.60 kW
2.50 kW
COP Tj = +7°C
5.61
3.55
Cdh Tj = +7 °C
0.940
0.960
Pdh Tj = 12°C
1.50 kW
1.40 kW
COP Tj = 12°C
8.35
6.00
Cdh Tj = +12 °C
0.860
0.890
Pdh Tj = Tbiv
4.00 kW
3.90 kW
COP Tj = Tbiv
3.15
1.80
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.15
1.80
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.10 kW
Annual energy consumption Qhe
862 kWh
1274 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
157 %
110 %
Prated
3.00 kW
2.00 kW
SCOP
4.00
2.83
Tbiv
-20 °C
-20 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
1.80 kW
1.20 kW
COP Tj = -7°C
3.26
2.16
Cdh Tj = -7 °C
0.950
0.950
Pdh Tj = +2°C
1.80 kW
1.40 kW
COP Tj = +2°C
5.17
3.80
Cdh Tj = +2 °C
0.920
0.930
Pdh Tj = +7°C
1.30 kW
1.20 kW
COP Tj = +7°C
7.00
5.05
Cdh Tj = +7 °C
0.860
0.890
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.00
7.60
Cdh Tj = +12 °C
0.850
0.870
Pdh Tj = Tbiv
2.80 kW
1.80 kW
COP Tj = Tbiv
1.80
1.36
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
2.00 kW
2.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
1.81
1.05
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.00 kW
0.00 kW
Annual energy consumption Qhe
1848 kWh
1740 kWh
Pdh Tj = -15°C (if TOL<-20°C)
2.40
1.70
COP Tj = -15°C (if TOL<-20°C)
2.29
1.76
Cdh Tj = -15 °C
0.980
0.970
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
200 %
136 %
Prated
5.00 kW
4.00 kW
SCOP
5.07
3.47
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.20 kW
3.40 kW
COP Tj = -7°C
2.66
1.93
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
2.50 kW
2.10 kW
COP Tj = +2°C
5.15
3.48
Cdh Tj = +2 °C
0.950
0.960
Pdh Tj = +7°C
1.70 kW
1.40 kW
COP Tj = +7°C
6.95
4.60
Cdh Tj = +7 °C
0.890
0.910
Pdh Tj = 12°C
1.60 kW
1.50 kW
COP Tj = 12°C
9.45
6.90
Cdh Tj = +12 °C
0.850
0.880
Pdh Tj = Tbiv
4.70 kW
3.80 kW
COP Tj = Tbiv
2.50
1.55
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.70 kW
3.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.55
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
26 W
26 W
PSB
8 W
8 W
PCK
8 W
8 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
0.20 kW
Annual energy consumption Qhe
2038 kWh
2385 kWh
Domestic Hot Water (DHW)
Warmer Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
154 %
COP
3.86
Heating up time
1:32 h:min
Standby power input
28.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Colder Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
99 %
COP
2.48
Heating up time
1:32 h:min
Standby power input
34.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
129 %
COP
3.23
Heating up time
1:32 h:min
Standby power input
31.0 W
Reference hot water temperature
53.3 °C
Mixed water at 40°C
239 l