3,400 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
42.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
44.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
42.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
44.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
175 %
133 %
Prated
14.00 kW
12.00 kW
SCOP
4.45
3.40
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6313 kWh
7066 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
44.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
14.00 kW
12.00 kW
SCOP
4.48
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6265 kWh
7018 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
14.00 kW
12.00 kW
SCOP
4.48
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6265 kWh
7018 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
130 %
COP
3.25
Heating up time
1:10 h:min
Standby power input
42.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
14.00 kW
12.00 kW
SCOP
4.48
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6265 kWh
7018 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
44.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
14.00 kW
14.00 kW
El input
2.97 kW
5.00 kW
COP
4.71
2.80
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
65 dB(A)
65 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
14.00 kW
12.00 kW
SCOP
4.48
3.43
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.00 kW
10.25 kW
COP Tj = -7°C
2.55
1.70
Pdh Tj = +2°C
7.30 kW
6.24 kW
COP Tj = +2°C
4.70
3.60
Pdh Tj = +7°C
4.70 kW
4.01 kW
COP Tj = +7°C
5.70
4.60
Pdh Tj = 12°C
3.50 kW
3.50 kW
COP Tj = 12°C
6.00
5.50
Pdh Tj = Tbiv
12.00 kW
10.25 kW
COP Tj = Tbiv
2.55
1.70
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.10 kW
9.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.60
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
13 W
13 W
PTO
0 W
0 W
PSB
13 W
13 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.60 kW
Annual energy consumption Qhe
6265 kWh
7018 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
134 %
COP
3.35
Heating up time
1:25 h:min
Standby power input
44.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l