1,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.40 kW
3.90 kW
El input
0.85 kW
1.32 kW
COP
5.20
2.95
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
127 %
Prated
5.00 kW
5.00 kW
SCOP
4.58
3.25
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.42 kW
4.42 kW
COP Tj = -7°C
3.02
2.10
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
2.69 kW
2.69 kW
COP Tj = +2°C
4.63
3.10
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
1.73 kW
1.73 kW
COP Tj = +7°C
6.48
4.46
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
1.96 kW
1.93 kW
COP Tj = 12°C
4.88
5.72
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
4.42 kW
4.42 kW
COP Tj = Tbiv
3.02
2.10
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.48 kW
4.17 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.24
1.51
WTOL
65 °C
65 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.52 kW
0.83 kW
Annual energy consumption Qhe
2253 kWh
3178 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
5.20 kW
El input
1.22 kW
1.81 kW
COP
4.92
2.87
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
40 dB(A)
40 dB(A)
Sound power level outdoor
60 dB(A)
60 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
129 %
Prated
6.00 kW
6.00 kW
SCOP
4.58
3.31
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.31 kW
5.31 kW
COP Tj = -7°C
2.75
2.00
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
3.23 kW
3.23 kW
COP Tj = +2°C
4.50
3.23
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
2.08 kW
2.08 kW
COP Tj = +7°C
6.25
4.47
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
1.96 kW
1.93 kW
COP Tj = 12°C
7.57
5.72
Cdh Tj = +12 °C
0.90
0.90
Pdh Tj = Tbiv
5.31 kW
5.31 kW
COP Tj = Tbiv
2.75
2.00
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.24 kW
4.95 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
1.80
WTOL
65 °C
65 °C
Poff
22 W
22 W
PTO
22 W
22 W
PSB
22 W
22 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.76 kW
1.05 kW
Annual energy consumption Qhe
2705 kWh
3745 kWh