2,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.10 kW
7.28 kW
El input
1.75 kW
2.46 kW
COP
4.63
2.96
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
48 dB(A)
48 dB(A)
Sound power level outdoor
55 dB(A)
55 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
168 %
126 %
Prated
6.51 kW
6.33 kW
SCOP
4.29
3.24
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
5.76 kW
5.60 kW
COP Tj = -7°C
2.59
1.94
Cdh Tj = -7 °C
0.90
0.90
Pdh Tj = +2°C
3.72 kW
3.50 kW
COP Tj = +2°C
3.92
3.02
Cdh Tj = +2 °C
0.90
0.90
Pdh Tj = +7°C
2.42 kW
2.33 kW
COP Tj = +7°C
6.53
4.69
Cdh Tj = +7 °C
0.90
0.90
Pdh Tj = 12°C
2.74 kW
2.78 kW
COP Tj = 12°C
7.82
5.93
Cdh Tj = +12 °C
0.95
0.96
Pdh Tj = Tbiv
5.76 kW
5.60 kW
COP Tj = Tbiv
2.59
1.94
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.88 kW
5.66 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.52
1.82
WTOL
60 °C
60 °C
Poff
18 W
18 W
PTO
17 W
17 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.64 kW
0.67 kW
Annual energy consumption Qhe
3139 kWh
4039 kWh