2,300 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
5.41 kW
4.88 kW
El input
1.27 kW
1.90 kW
COP
4.27
2.57
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
43 dB(A)
43 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
204 %
150 %
Prated
10.00 kW
10.00 kW
SCOP
5.29
3.94
Tbiv
-22 °C
-22 °C
TOL
-22 °C
-22 °C
Pdh Tj = -7°C
5.99 kW
6.05 kW
COP Tj = -7°C
5.05
3.53
Cdh Tj = -7 °C
0.980
0.990
Pdh Tj = +2°C
3.66 kW
3.76 kW
COP Tj = +2°C
5.81
4.30
Cdh Tj = +2 °C
0.970
0.980
Pdh Tj = +7°C
2.35 kW
2.46 kW
COP Tj = +7°C
5.62
5.36
Cdh Tj = +7 °C
0.960
0.960
Pdh Tj = 12°C
2.28 kW
2.39 kW
COP Tj = 12°C
5.71
5.00
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
9.83 kW
9.75 kW
COP Tj = Tbiv
3.86
2.54
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
9.83 kW
9.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.86
2.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
18 W
18 W
PTO
18 W
18 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
4659 kWh
6258 kWh
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
41 dB(A)
41 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
188 %
140 %
Prated
12.00 kW
10.00 kW
SCOP
4.91
3.70
Tbiv
-10 °C
-10 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
10.47 kW
8.65 kW
COP Tj = -7°C
3.84
2.77
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
6.53 kW
5.29 kW
COP Tj = +2°C
4.84
3.76
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
4.16 kW
3.53 kW
COP Tj = +7°C
5.86
4.35
Cdh Tj = +7 °C
0.970
0.980
Pdh Tj = 12°C
2.29 kW
2.17 kW
COP Tj = 12°C
6.19
4.48
Cdh Tj = +12 °C
0.950
0.960
Pdh Tj = Tbiv
11.57 kW
9.75 kW
COP Tj = Tbiv
3.61
2.54
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
11.57 kW
9.75 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.61
2.54
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.990
1.000
WTOL
65 °C
65 °C
Poff
18 W
18 W
PTO
18 W
18 W
PSB
18 W
18 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.00 kW
Annual energy consumption Qhe
5049 kWh
5582 kWh
Domestic Hot Water (DHW)
Colder Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
96 %
COP
2.40
Heating up time
1:49 h:min
Standby power input
70.3 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
232 l
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
96 %
COP
2.40
Heating up time
1:49 h:min
Standby power input
70.3 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
232 l