1,500 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
177 %
130 %
Prated
6.00 kW
5.00 kW
SCOP
4.50
3.33
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2569 kWh
3114 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
132 %
Prated
6.00 kW
5.00 kW
SCOP
4.58
3.38
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2525 kWh
3070 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
132 %
Prated
6.00 kW
5.00 kW
SCOP
4.58
3.38
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2525 kWh
3070 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
132 %
Prated
6.00 kW
5.00 kW
SCOP
4.58
3.38
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2525 kWh
3070 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
6.00 kW
6.00 kW
El input
1.25 kW
2.08 kW
COP
4.80
2.89
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
63 dB(A)
63 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
180 %
132 %
Prated
6.00 kW
5.00 kW
SCOP
4.58
3.38
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
4.95 kW
4.42 kW
COP Tj = -7°C
2.70
1.85
Pdh Tj = +2°C
3.01 kW
2.69 kW
COP Tj = +2°C
4.60
3.45
Pdh Tj = +7°C
1.90 kW
1.84 kW
COP Tj = +7°C
6.00
4.20
Pdh Tj = 12°C
1.80 kW
2.06 kW
COP Tj = 12°C
7.20
6.90
Pdh Tj = Tbiv
4.95 kW
4.42 kW
COP Tj = Tbiv
2.70
1.85
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.30 kW
3.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.50
1.80
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.30 kW
1.10 kW
Annual energy consumption Qhe
2525 kWh
3070 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l