21,000 kg
Heating
EN 14511-2
Heat output
65.00 kW
El input
40.10 kW
COP
4.29
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level outdoor
84 dB(A)
EN 14825
ηs
160 %
Prated
53.00 kW
SCOP
4.08
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
44.70 kW
COP Tj = -7°C
2.84
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
27.50 kW
COP Tj = +2°C
4.19
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
29.40 kW
COP Tj = +7°C
5.18
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
35.10 kW
COP Tj = 12°C
6.69
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
44.70 kW
COP Tj = Tbiv
2.84
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
40.60 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.53
WTOL
55 °C
Poff
116 W
PTO
280 W
PSB
116 W
PCK
116 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
0 kWh
Heating
EN 14511-2
Heat output
79.10 kW
El input
40.10 kW
COP
4.17
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level outdoor
85 dB(A)
EN 14825
ηs
160 %
Prated
57.00 kW
SCOP
4.07
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
50.00 kW
COP Tj = -7°C
2.78
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
29.20 kW
COP Tj = +2°C
4.11
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
30.40 kW
COP Tj = +7°C
5.29
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
35.50 kW
COP Tj = 12°C
6.70
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
50.00 kW
COP Tj = Tbiv
2.78
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
45.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
WTOL
55 °C
Poff
116 W
PTO
280 W
PSB
116 W
PCK
116 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
0 kWh
Heating
EN 14511-2
Heat output
88.00 kW
El input
40.10 kW
COP
4.15
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level outdoor
85 dB(A)
EN 14825
ηs
159 %
Prated
80.00 kW
SCOP
4.06
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
71.00 kW
COP Tj = -7°C
2.54
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
45.00 kW
COP Tj = +2°C
4.23
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
30.80 kW
COP Tj = +7°C
4.85
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
35.90 kW
COP Tj = 12°C
6.84
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
71.00 kW
COP Tj = Tbiv
2.54
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
69.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.30
WTOL
55 °C
Poff
116 W
PTO
280 W
PSB
116 W
PCK
116 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
0 kWh