15,000 kg
Heating
EN 14511-2
Heat output
54.00 kW
El input
25.60 kW
COP
4.07
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level outdoor
83 dB(A)
EN 14825
ηs
154 %
Prated
41.00 kW
SCOP
3.93
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
36.00 kW
COP Tj = -7°C
2.76
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
22.90 kW
COP Tj = +2°C
3.96
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
19.90 kW
COP Tj = +7°C
4.83
Cdh Tj = +7 °C
0.89
Pdh Tj = 12°C
24.40 kW
COP Tj = 12°C
7.05
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
36.00 kW
COP Tj = Tbiv
2.76
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
32.90 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.55
WTOL
55 °C
Poff
97 W
PTO
103 W
PSB
97 W
PCK
97 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
0 kWh
Heating
EN 14511-2
Heat output
61.00 kW
El input
25.60 kW
COP
4.00
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Sound power level outdoor
83 dB(A)
EN 14825
ηs
153 %
Prated
49.00 kW
SCOP
3.91
Tbiv
-7 °C
TOL
-10 °C
Pdh Tj = -7°C
44.50 kW
COP Tj = -7°C
2.79
Cdh Tj = -7 °C
0.90
Pdh Tj = +2°C
29.60 kW
COP Tj = +2°C
4.05
Cdh Tj = +2 °C
0.90
Pdh Tj = +7°C
20.60 kW
COP Tj = +7°C
4.25
Cdh Tj = +7 °C
0.90
Pdh Tj = 12°C
26.60 kW
COP Tj = 12°C
7.02
Cdh Tj = +12 °C
0.90
Pdh Tj = Tbiv
44.50 kW
COP Tj = Tbiv
2.79
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
41.70 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
WTOL
55 °C
Poff
97 W
PTO
103 W
PSB
97 W
PCK
97 W
Supplementary Heater: Type of energy input
Electricity
Supplementary Heater: PSUP
0.00 kW
Annual energy consumption Qhe
0 kWh