Certificate holders

Subtype

ELFOEnergy Storm EVO R-32 SH 18.2 , 20.2

Certificate Holder
Clivet s.p.a.
Via camp lonc 25 c.ap.
I-32032 z.i. Villapaiera - Feltre (BL)
Italy
Registration number
ICIM-PDC-000092-00
Certification Body
ICIM S.p.A.
Subtype title
ELFOEnergy Storm EVO R-32 SH 18.2 , 20.2
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

15,000 kg

Certification Date
23.12.2020
Testing basis
HP KEYMARK certification scheme rules rev. 8
Generate PDF Export model CSV Download certificate
  • Number of models 2

Models

ELFOEnergy Storm EVO WSAN-YES 18.2 R32
Configure model
Model name
ELFOEnergy Storm EVO WSAN-YES 18.2 R32
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

54.00 kW

El input

25.60 kW

COP

4.07

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

154 %

Prated

41.00 kW

SCOP

3.93

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

36.00 kW

COP Tj = -7°C

2.76

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

22.90 kW

COP Tj = +2°C

3.96

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

19.90 kW

COP Tj = +7°C

4.83

Cdh Tj = +7 °C

0.89

Pdh Tj = 12°C

24.40 kW

COP Tj = 12°C

7.05

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

36.00 kW

COP Tj = Tbiv

2.76

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

32.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.55

WTOL

55 °C

Poff

97 W

PTO

103 W

PSB

97 W

PCK

97 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

0 kWh

ELFOEnergy Storm EVO WSAN-YES 20.2 R32
Configure model
Model name
ELFOEnergy Storm EVO WSAN-YES 20.2 R32
Application
Heating (low temp)
Units
Outdoor
Climate Zone
n/a
Reversibility
Yes
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Heat output

61.00 kW

El input

25.60 kW

COP

4.00

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Sound power level outdoor

83 dB(A)

EN 14825

ηs

153 %

Prated

49.00 kW

SCOP

3.91

Tbiv

-7 °C

TOL

-10 °C

Pdh Tj = -7°C

44.50 kW

COP Tj = -7°C

2.79

Cdh Tj = -7 °C

0.90

Pdh Tj = +2°C

29.60 kW

COP Tj = +2°C

4.05

Cdh Tj = +2 °C

0.90

Pdh Tj = +7°C

20.60 kW

COP Tj = +7°C

4.25

Cdh Tj = +7 °C

0.90

Pdh Tj = 12°C

26.60 kW

COP Tj = 12°C

7.02

Cdh Tj = +12 °C

0.90

Pdh Tj = Tbiv

44.50 kW

COP Tj = Tbiv

2.79

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

41.70 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

WTOL

55 °C

Poff

97 W

PTO

103 W

PSB

97 W

PCK

97 W

Supplementary Heater: Type of energy input

Electricity

Supplementary Heater: PSUP

0.00 kW

Annual energy consumption Qhe

0 kWh