4,000 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
7.03 kW
6.38 kW
El input
1.45 kW
2.04 kW
COP
4.85
3.13
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
176 %
134 %
Prated
14.50 kW
14.00 kW
SCOP
4.47
3.42
Tbiv
-8 °C
-8 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
12.90 kW
12.50 kW
COP Tj = -7°C
2.96
2.01
Pdh Tj = +2°C
7.90 kW
7.60 kW
COP Tj = +2°C
4.37
3.29
Pdh Tj = +7°C
5.10 kW
4.90 kW
COP Tj = +7°C
5.58
4.68
Pdh Tj = 12°C
6.40 kW
6.80 kW
COP Tj = 12°C
6.99
6.51
Pdh Tj = Tbiv
13.40 kW
12.70 kW
COP Tj = Tbiv
2.86
1.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
12.50 kW
11.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.71
1.95
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.97
0.98
WTOL
58 °C
58 °C
Poff
2 W
2 W
PTO
25 W
16 W
PSB
15 W
15 W
PCK
20 W
20 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
2.00 kW
3.00 kW
Annual energy consumption Qhe
6702 kWh
8431 kWh