Certificate holders

Subtype

DAIKIN ALTHERMA 3 M 11kW

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Reg. No.
011-1W0424
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA 3 M 11kW
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass Of Refrigerant

3,800 kg

Certification Date
27.10.2020
Testing basis
HP KEYMARK certification scheme rules rev. 7
Generate PDF Export model CSV
  • Number of models 4

Models

EBLA11D(3)V3
General Data
Power supply
1x230V 50Hz

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

248 %

170 %

Prated

10.00 kW

10.00 kW

SCOP

6.28

4.33

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.30 kW

9.80 kW

COP Tj = +2°C

3.30

2.18

Cdh

1.00

1.00

Pdh Tj = +7°C

6.70 kW

6.20 kW

COP Tj = +7°C

5.70

3.74

Cdh

1.00

1.00

Pdh Tj = 12°C

5.20 kW

5.00 kW

COP Tj = 12°C

7.87

5.68

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.30 kW

9.80 kW

COP Tj = Tbiv

3.30

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.30 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.30

2.18

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2128 kWh

3083 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

132 %

Prated

10.00 kW

10.00 kW

SCOP

4.73

3.37

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.20 kW

9.30 kW

COP Tj = -7°C

3.03

1.90

Cdh

 

1.00

Pdh Tj = +2°C

5.50 kW

5.40 kW

COP Tj = +2°C

4.37

3.25

Cdh

1.00

1.00

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.74

4.81

Cdh

1.00

1.00

Pdh Tj = 12°C

5.40 kW

5.30 kW

COP Tj = 12°C

8.54

6.41

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.10 kW

9.30 kW

COP Tj = Tbiv

2.58

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.10 kW

7.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.58

1.64

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

2.40 kW

Annual energy consumption Qhe

4371 kWh

6134 kWh

Cooling

EN 14825

+7°C/+12°C

Pdesignc

11.50 kW

SEER

5.79

Pdc Tj = 35°C

11.60 kW

EER Tj = 35°C

3.26

Pdc Tj = 30°C

8.80 kW

EER Tj = 30°C

4.75

Cdc

1.0

Pdc Tj = 25°C

5.70 kW

EER Tj = 25°C

6.91

Cdc

1.0

Pdc Tj = 20°C

5.80 kW

EER Tj = 20°C

8.45

Cdc

1.0

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1190 kWh

EN 14511-2

+7°C/+12°C

El input

3.56 kW

Cooling capacity

11.59

EER

3.26

EBLA11D(3)W1
General Data
Power supply
3x400V 50Hz

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

248 %

170 %

Prated

10.00 kW

10.00 kW

SCOP

6.28

4.33

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.30 kW

9.80 kW

COP Tj = +2°C

3.30

2.18

Cdh

1.00

1.00

Pdh Tj = +7°C

6.70 kW

6.20 kW

COP Tj = +7°C

5.70

3.74

Cdh

1.00

1.00

Pdh Tj = 12°C

5.20 kW

5.00 kW

COP Tj = 12°C

7.87

5.68

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.30 kW

9.80 kW

COP Tj = Tbiv

3.30

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.30 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.30

2.18

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2128 kWh

3083 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

186 %

132 %

Prated

10.00 kW

10.00 kW

SCOP

4.73

3.37

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.20 kW

9.30 kW

COP Tj = -7°C

3.03

1.90

Cdh

 

1.00

Pdh Tj = +2°C

5.50 kW

5.40 kW

COP Tj = +2°C

4.37

3.25

Cdh

1.00

1.00

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.74

4.81

Cdh

1.00

1.00

Pdh Tj = 12°C

5.40 kW

5.30 kW

COP Tj = 12°C

8.54

6.41

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.10 kW

9.30 kW

COP Tj = Tbiv

2.58

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.10 kW

7.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.58

1.64

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

2.40 kW

Annual energy consumption Qhe

4371 kWh

6134 kWh

Cooling

EN 14825

+7°C/+12°C

Pdesignc

11.50 kW

SEER

5.79

Pdc Tj = 35°C

11.60 kW

EER Tj = 35°C

3.26

Pdc Tj = 30°C

8.80 kW

EER Tj = 30°C

4.75

Cdc

1.0

Pdc Tj = 25°C

5.70 kW

EER Tj = 25°C

6.91

Cdc

1.0

Pdc Tj = 20°C

5.80 kW

EER Tj = 20°C

8.45

Cdc

1.0

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1190 kWh

EN 14511-2

+7°C/+12°C

El input

3.56 kW

Cooling capacity

11.59

EER

3.26

EDLA11D(3)V3
General Data
Power supply
1x230V 50Hz

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

237 %

165 %

Prated

10.00 kW

10.00 kW

SCOP

5.99

4.19

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.30 kW

9.80 kW

COP Tj = +2°C

3.30

2.18

Cdh

1.00

1.00

Pdh Tj = +7°C

6.70 kW

6.20 kW

COP Tj = +7°C

5.70

3.74

Cdh

1.00

1.00

Pdh Tj = 12°C

5.20 kW

5.00 kW

COP Tj = 12°C

7.87

5.68

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.30 kW

9.80 kW

COP Tj = Tbiv

3.30

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.30 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.30

2.18

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2230 kWh

3184 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

130 %

Prated

10.00 kW

10.00 kW

SCOP

4.64

3.32

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.20 kW

9.30 kW

COP Tj = -7°C

3.03

1.90

Cdh

 

1.00

Pdh Tj = +2°C

5.50 kW

5.40 kW

COP Tj = +2°C

4.37

3.25

Cdh

1.00

1.00

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.74

4.81

Cdh

1.00

1.00

Pdh Tj = 12°C

5.40 kW

5.30 kW

COP Tj = 12°C

8.54

6.41

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.10 kW

9.30 kW

COP Tj = Tbiv

2.58

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.10 kW

7.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.58

1.64

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

2.40 kW

Annual energy consumption Qhe

4456 kWh

6281 kWh

Cooling

EN 14825

+7°C/+12°C

Pdesignc

11.50 kW

SEER

5.79

Pdc Tj = 35°C

11.60 kW

EER Tj = 35°C

3.26

Pdc Tj = 30°C

8.80 kW

EER Tj = 30°C

4.75

Cdc

1.0

Pdc Tj = 25°C

5.70 kW

EER Tj = 25°C

6.91

Cdc

1.0

Pdc Tj = 20°C

5.80 kW

EER Tj = 20°C

8.45

Cdc

1.0

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1190 kWh

EN 14511-2

+7°C/+12°C

El input

3.56 kW

Cooling capacity

11.59

EER

3.26

EDLA11D(3)W1
General Data
Power supply
3x400V 50Hz

Warmer Climate

EN 14825

Low temperature

Medium temperature

ηs

237 %

165 %

Prated

10.00 kW

10.00 kW

SCOP

5.99

4.19

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

10.30 kW

9.80 kW

COP Tj = +2°C

3.30

2.18

Cdh

1.00

1.00

Pdh Tj = +7°C

6.70 kW

6.20 kW

COP Tj = +7°C

5.70

3.74

Cdh

1.00

1.00

Pdh Tj = 12°C

5.20 kW

5.00 kW

COP Tj = 12°C

7.87

5.68

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.30 kW

9.80 kW

COP Tj = Tbiv

3.30

2.18

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.30 kW

9.80 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.30

2.18

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2230 kWh

3184 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10.56 kW

10.64 kW

El input

2.19 kW

3.62 kW

COP

4.83

2.94

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level outdoor

62 dB(A)

62 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

182 %

130 %

Prated

10.00 kW

10.00 kW

SCOP

4.64

3.32

Tbiv

-10 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

9.20 kW

9.30 kW

COP Tj = -7°C

3.03

1.90

Cdh

 

1.00

Pdh Tj = +2°C

5.50 kW

5.40 kW

COP Tj = +2°C

4.37

3.25

Cdh

1.00

1.00

Pdh Tj = +7°C

4.60 kW

4.40 kW

COP Tj = +7°C

6.74

4.81

Cdh

1.00

1.00

Pdh Tj = 12°C

5.40 kW

5.30 kW

COP Tj = 12°C

8.54

6.41

Cdh

1.00

1.00

Pdh Tj = Tbiv

10.10 kW

9.30 kW

COP Tj = Tbiv

2.58

1.90

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.10 kW

7.60 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.58

1.64

WTOL

35 °C

55 °C

Poff

23 W

23 W

PTO

23 W

23 W

PSB

23 W

23 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.00 kW

2.40 kW

Annual energy consumption Qhe

4456 kWh

6281 kWh

Cooling

EN 14825

+7°C/+12°C

Pdesignc

11.50 kW

SEER

5.79

Pdc Tj = 35°C

11.60 kW

EER Tj = 35°C

3.26

Pdc Tj = 30°C

8.80 kW

EER Tj = 30°C

4.75

Cdc

1.0

Pdc Tj = 25°C

5.70 kW

EER Tj = 25°C

6.91

Cdc

1.0

Pdc Tj = 20°C

5.80 kW

EER Tj = 20°C

8.45

Cdc

1.0

Poff

23 W

PTO

23 W

PSB

23 W

PCK

0 W

Annual energy consumption Qce

1190 kWh

EN 14511-2

+7°C/+12°C

El input

3.56 kW

Cooling capacity

11.59

EER

3.26