1,400 kg
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
189 %
137 %
Prated
4.00 kW
4.00 kW
SCOP
4.80
3.50
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1719 kWh
2358 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
140 %
Prated
4.00 kW
4.00 kW
SCOP
4.93
3.58
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1675 kWh
2314 kWh
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
140 %
Prated
4.00 kW
4.00 kW
SCOP
4.93
3.58
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1675 kWh
2314 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
132 %
COP
3.30
Heating up time
1:43 h:min
Standby power input
37.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
263 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
140 %
Prated
4.00 kW
4.00 kW
SCOP
4.93
3.58
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1675 kWh
2314 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l
Heating
EN 14511-4
Operating range outdoor exchanger/indoor exchanger lower limit/lower limit
passed
Operating range outdoor exchanger/indoor exchanger upper limit/upper limit
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
4.30 kW
4.30 kW
El input
0.82 kW
1.43 kW
COP
5.25
3.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
37 dB(A)
37 dB(A)
Sound power level outdoor
61 dB(A)
61 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
194 %
140 %
Prated
4.00 kW
4.00 kW
SCOP
4.93
3.58
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
3.54 kW
3.50 kW
COP Tj = -7°C
3.20
2.30
Pdh Tj = +2°C
2.15 kW
2.10 kW
COP Tj = +2°C
5.20
3.73
Pdh Tj = +7°C
1.70 kW
1.60 kW
COP Tj = +7°C
6.05
4.40
Pdh Tj = 12°C
1.75 kW
1.60 kW
COP Tj = 12°C
6.25
5.00
Pdh Tj = Tbiv
3.54 kW
3.50 kW
COP Tj = Tbiv
3.20
2.30
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.00 kW
3.10 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.75
1.90
Cdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
0.90
0.90
WTOL
55 °C
55 °C
Poff
11 W
11 W
PTO
0 W
0 W
PSB
11 W
11 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
0.00 kW
0.90 kW
Annual energy consumption Qhe
1675 kWh
2314 kWh
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
XL
Efficiency ηDHW
136 %
COP
3.40
Heating up time
2:10 h:min
Standby power input
41.0 W
Reference hot water temperature
54.0 °C
Mixed water at 40°C
350 l