Certificate holders

Subtype

Ecodan Zubadan 6/8-300D AA

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0026-20
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Ecodan Zubadan 6/8-300D AA
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,400 kg

Certification Date
30.11.2020
Testing basis
HP Keymark scheme rules rev. no. 6
Generate PDF Export model CSV Download certificate
  • Number of models 6

Models

PUD-SHWM60VAA(-BS) + E*ST30D-*M*D
Configure model
Model name
PUD-SHWM60VAA(-BS) + E*ST30D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1 kW

1.89 kW

COP

4.99

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

134 %

Prated

6 kW

6 kW

SCOP

4.52

3.41

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

5.3 kW

5.3 kW

COP Tj = -7°C

3.29

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.45

3.23

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

5.67

4.91

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

7.8

6.89

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

6 kW

6 kW

COP Tj = Tbiv

3.21

2.02

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.21

2.02

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2743 kWh

3631 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l

PUD-SHWM60VAA(-BS) + E*ST30D-M*D
Configure model
Model name
PUD-SHWM60VAA(-BS) + E*ST30D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

5 kW

5 kW

El input

1 kW

1.89 kW

COP

4.99

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

134 %

Prated

6 kW

6 kW

SCOP

4.52

3.41

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

5.3 kW

5.3 kW

COP Tj = -7°C

3.29

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.45

3.23

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

5.67

4.91

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

7.8

6.89

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

6 kW

6 kW

COP Tj = Tbiv

3.21

2.02

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6 kW

6 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.21

2.02

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

2743 kWh

3631 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l

PUD-SHWM80VAA(-BS) + E*ST30D-*M*D
Configure model
Model name
PUD-SHWM80VAA(-BS) + E*ST30D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.19 kW

2.26 kW

COP

5.03

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

135 %

Prated

8 kW

8 kW

SCOP

4.6

3.45

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

7.1 kW

7.1 kW

COP Tj = -7°C

3.11

2.14

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

6

4.91

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

8.21

7.05

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

8 kW

8 kW

COP Tj = Tbiv

3.09

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8 kW

8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.09

1.97

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

3597 kWh

4793 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l

PUD-SHWM80VAA(-BS) + E*ST30D-M*D
Configure model
Model name
PUD-SHWM80VAA(-BS) + E*ST30D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.19 kW

2.26 kW

COP

5.03

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

181 %

135 %

Prated

8 kW

8 kW

SCOP

4.6

3.45

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

7.1 kW

7.1 kW

COP Tj = -7°C

3.11

2.14

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.43

3.23

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

6

4.91

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

8.21

7.05

Cdh Tj = +12 °C

0.96

0.97

Pdh Tj = Tbiv

8 kW

8 kW

COP Tj = Tbiv

3.09

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8 kW

8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.09

1.97

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

3597 kWh

4793 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l

PUD-SHWM80YAA(-BS) + E*ST30D-*M*D
Configure model
Model name
PUD-SHWM80YAA(-BS) + E*ST30D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.19 kW

2.26 kW

COP

5.03

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

134 %

Prated

8 kW

8 kW

SCOP

4.55

3.42

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

7.1 kW

7.1 kW

COP Tj = -7°C

3.11

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.44

3.23

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

6

4.91

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

8.21

7.05

Cdh Tj = +12 °C

0.94

0.95

Pdh Tj = Tbiv

8 kW

8 kW

COP Tj = Tbiv

3.09

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8 kW

8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.09

1.97

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

3632 kWh

4832 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l

PUD-SHWM80YAA(-BS) + E*ST30D-M*D
Configure model
Model name
PUD-SHWM80YAA(-BS) + E*ST30D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

6 kW

6 kW

El input

1.19 kW

2.26 kW

COP

5.03

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

56 dB(A)

56 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

179 %

134 %

Prated

8 kW

8 kW

SCOP

4.55

3.42

Tbiv

-10 °C

-10 °C

TOL

-28 °C

-28 °C

Pdh Tj = -7°C

7.1 kW

7.1 kW

COP Tj = -7°C

3.11

2.14

Cdh Tj = -7 °C

0.99

0.99

Pdh Tj = +2°C

4.7 kW

4.3 kW

COP Tj = +2°C

4.44

3.23

Cdh Tj = +2 °C

0.98

0.98

Pdh Tj = +7°C

5.1 kW

5.3 kW

COP Tj = +7°C

6

4.91

Cdh Tj = +7 °C

0.97

0.98

Pdh Tj = 12°C

3.2 kW

3.1 kW

COP Tj = 12°C

8.21

7.05

Cdh Tj = +12 °C

0.94

0.95

Pdh Tj = Tbiv

8 kW

8 kW

COP Tj = Tbiv

3.09

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8 kW

8 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

3.09

1.97

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0 kW

0 kW

Annual energy consumption Qhe

3632 kWh

4832 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

121 %

COP

2.93

Heating up time

02:49 h:min

Standby power input

39 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

417 l