Certificate holders

Subtype

Ecodan Power Inverter 10/12-200D AA

Certificate Holder
Mitsubishi Electric Air Conditioning Systems Europe LTD
Nettlehill Road, Houston Industrial Estate
EH54 5EQ Livingston
United Kingdom
Registration number
037-0020-20
Certification Body
SZU - Strojirensky zkusebni ustav (Engineering Test Institute, Public Enterprise)
Subtype title
Ecodan Power Inverter 10/12-200D AA
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass of Refrigerant

1,600 kg

Certification Date
06.10.2020
Testing basis
HP Keymark scheme rules rev. no. 6
Generate PDF Export model CSV Download certificate
  • Number of models 16

Models

PUD-SWM100VAA(-BS) + E*SD-*M*D
Configure model
Model name
PUD-SWM100VAA(-BS) + E*SD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

131 %

Prated

10 kW

10 kW

SCOP

4.53

3.35

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.97

0.97

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4564 kWh

6173 kWh

PUD-SWM100VAA(-BS) + E*SD-M*D
Configure model
Model name
PUD-SWM100VAA(-BS) + E*SD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

131 %

Prated

10 kW

10 kW

SCOP

4.53

3.35

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.97

0.97

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4564 kWh

6173 kWh

PUD-SWM100VAA(-BS) + E*ST20D-*M*D
Configure model
Model name
PUD-SWM100VAA(-BS) + E*ST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

131 %

Prated

10 kW

10 kW

SCOP

4.53

3.35

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.97

0.97

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4564 kWh

6173 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM100VAA(-BS) + E*ST20D-M*D
Configure model
Model name
PUD-SWM100VAA(-BS) + E*ST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

178 %

131 %

Prated

10 kW

10 kW

SCOP

4.53

3.35

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.97

0.97

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4564 kWh

6173 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM100YAA(-BS) + E*SD-*M*D
Configure model
Model name
PUD-SWM100YAA(-BS) + E*SD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

130 %

Prated

10 kW

10 kW

SCOP

4.49

3.33

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4602 kWh

6210 kWh

PUD-SWM100YAA(-BS) + E*SD-M*D
Configure model
Model name
PUD-SWM100YAA(-BS) + E*SD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

130 %

Prated

10 kW

10 kW

SCOP

4.49

3.33

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4602 kWh

6210 kWh

PUD-SWM100YAA(-BS) + E*ST20D-*M*D
Configure model
Model name
PUD-SWM100YAA(-BS) + E*ST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

130 %

Prated

10 kW

10 kW

SCOP

4.49

3.33

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4602 kWh

6210 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM100YAA(-BS) + E*ST20D-M*D
Configure model
Model name
PUD-SWM100YAA(-BS) + E*ST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

8 kW

8 kW

El input

1.6 kW

3.08 kW

COP

5

2.6

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

59 dB(A)

59 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

130 %

Prated

10 kW

10 kW

SCOP

4.49

3.33

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

8.8 kW

8.8 kW

COP Tj = -7°C

3.1

2

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

5.7 kW

5.7 kW

COP Tj = +2°C

4.46

3.16

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.4 kW

5.2 kW

COP Tj = +7°C

5.68

4.77

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.5 kW

3.6 kW

COP Tj = 12°C

7.76

6.92

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

8.8 kW

8.8 kW

COP Tj = Tbiv

3.1

2

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

8.57 kW

8.57 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.85

1.93

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.43 kW

1.43 kW

Annual energy consumption Qhe

4602 kWh

6210 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM120VAA(-BS) + E*SD-*M*D
Configure model
Model name
PUD-SWM120VAA(-BS) + E*SD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12 kW

12 kW

SCOP

4.5

3.3

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5512 kWh

7519 kWh

PUD-SWM120VAA(-BS) + E*SD-M*D
Configure model
Model name
PUD-SWM120VAA(-BS) + E*SD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12 kW

12 kW

SCOP

4.5

3.3

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5512 kWh

7519 kWh

PUD-SWM120VAA(-BS) + E*ST20D-*M*D
Configure model
Model name
PUD-SWM120VAA(-BS) + E*ST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12 kW

12 kW

SCOP

4.5

3.3

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5512 kWh

7519 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM120VAA(-BS) + E*ST20D-M*D
Configure model
Model name
PUD-SWM120VAA(-BS) + E*ST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

129 %

Prated

12 kW

12 kW

SCOP

4.5

3.3

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

1

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.99

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.99

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.97

0.98

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

15 W

15 W

PTO

15 W

15 W

PSB

15 W

15 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5512 kWh

7519 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM120YAA(-BS) + E*SD-*M*D
Configure model
Model name
PUD-SWM120YAA(-BS) + E*SD-*M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

12 kW

12 kW

SCOP

4.47

3.28

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5548 kWh

7555 kWh

PUD-SWM120YAA(-BS) + E*SD-M*D
Configure model
Model name
PUD-SWM120YAA(-BS) + E*SD-M*D
Application
Heating (medium temp)
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

12 kW

12 kW

SCOP

4.47

3.28

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5548 kWh

7555 kWh

PUD-SWM120YAA(-BS) + E*ST20D-*M*D
Configure model
Model name
PUD-SWM120YAA(-BS) + E*ST20D-*M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

12 kW

12 kW

SCOP

4.47

3.28

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5548 kWh

7555 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l

PUD-SWM120YAA(-BS) + E*ST20D-M*D
Configure model
Model name
PUD-SWM120YAA(-BS) + E*ST20D-M*D
Application
Heating + DHW + low temp
Units
Indoor + Outdoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

10 kW

10 kW

El input

2.13 kW

3.77 kW

COP

4.7

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

Sound power level outdoor

60 dB(A)

60 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

176 %

128 %

Prated

12 kW

12 kW

SCOP

4.47

3.28

Tbiv

-7 °C

-7 °C

TOL

-25 °C

-25 °C

Pdh Tj = -7°C

10.6 kW

10.6 kW

COP Tj = -7°C

2.85

1.94

Cdh Tj = -7 °C

0.99

1

Pdh Tj = +2°C

6.5 kW

6.5 kW

COP Tj = +2°C

4.45

3.1

Cdh Tj = +2 °C

0.98

0.99

Pdh Tj = +7°C

5.6 kW

5.3 kW

COP Tj = +7°C

5.83

4.73

Cdh Tj = +7 °C

0.98

0.98

Pdh Tj = 12°C

4.4 kW

4.3 kW

COP Tj = 12°C

7.86

6.94

Cdh Tj = +12 °C

0.96

0.96

Pdh Tj = Tbiv

10.6 kW

10.6 kW

COP Tj = Tbiv

2.85

1.94

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

10.2 kW

10.2 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.64

1.88

WTOL

60 °C

60 °C

Poff

22 W

22 W

PTO

22 W

22 W

PSB

22 W

22 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

1.8 kW

1.8 kW

Annual energy consumption Qhe

5548 kWh

7555 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

L

Efficiency ηDHW

148 %

COP

3.49

Heating up time

01:47 h:min

Standby power input

36 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

278 l