Certificate holders

Subtype

DAIKIN ALTHERMA 3 R 7 F 4KW (230L)

Certificate Holder
DAIKIN Europe N.V.
Zandvoordestraat 300
B-8400 Oostende
Belgium
Reg. No.
011-1W0366
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
DAIKIN ALTHERMA 3 R 7 F 4KW (230L)
Driving energy
Electricity
Heat Pump Type
Outdoor Air/Water
Refrigerant
R32
Mass Of Refrigerant

1,500 kg

Certification Date
09.04.2020
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 6

Models

ERGA04DV7 / EHVX04S23D3V
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

195 %

127 %

Prated

6.00 kW

6.00 kW

SCOP

4.96

3.26

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.17 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

1.00

1.00

Pdh Tj = +2°C

3.71 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

0.99

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

0.98

1.00

Pdh Tj = 12°C

3.27 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

0.98

1.00

Pdh Tj = Tbiv

6.17 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.22 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.78 kW

2.00 kW

Annual energy consumption Qhe

2501 kWh

3806 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

105 %

COP

2.61

Heating up time

1:47 h:min

Standby power input

11.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

288 l

ERGA04DV7 / EHVX04S23D6V
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

195 %

127 %

Prated

6.00 kW

6.00 kW

SCOP

4.96

3.26

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.17 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

1.00

1.00

Pdh Tj = +2°C

3.71 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

0.99

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

0.98

1.00

Pdh Tj = 12°C

3.27 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

0.98

1.00

Pdh Tj = Tbiv

6.17 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.22 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.78 kW

2.00 kW

Annual energy consumption Qhe

2501 kWh

3806 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.57

Heating up time

1:47 h:min

Standby power input

13.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

288 l

ERGA04DV7 / EHVH04S23D6V
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

192 %

127 %

Prated

6.00 kW

6.00 kW

SCOP

4.88

3.26

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.17 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

1.00

1.00

Pdh Tj = +2°C

3.71 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

0.99

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

0.98

1.00

Pdh Tj = 12°C

3.27 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

0.98

1.00

Pdh Tj = Tbiv

6.17 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.22 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

10 W

10 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.78 kW

2.00 kW

Annual energy consumption Qhe

2538 kWh

3806 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.57

Heating up time

1:47 h:min

Standby power input

13.0 W

Reference hot water temperature

52.5 °C

Mixed water at 40°C

288 l

ERGA04EV7 / EHVX04S23E3V
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

195 %

129 %

Prated

6.00 kW

6.00 kW

SCOP

4.96

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.20 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

 

1.00

Pdh Tj = +2°C

3.70 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

1.00

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

1.00

1.00

Pdh Tj = 12°C

3.30 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

1.00

1.00

Pdh Tj = Tbiv

6.20 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.20 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.80 kW

2.00 kW

Annual energy consumption Qhe

2501 kWh

3769 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.36 kW

Cooling capacity

4.52

EER

3.32

EN 14825

+7°C/+12°C

Pdesignc

4.50 kW

SEER

5.66

Pdc Tj = 35°C

4.52 kW

EER Tj = 35°C

3.32

Pdc Tj = 30°C

3.14 kW

EER Tj = 30°C

5.11

Cdc

1.0

Pdc Tj = 25°C

2.43 kW

EER Tj = 25°C

6.69

Cdc

1.0

Pdc Tj = 20°C

2.50 kW

EER Tj = 20°C

8.24

Cdc

1.0

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

480 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

105 %

COP

2.61

Heating up time

1:47 h:min

Standby power input

11.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

288 l

ERGA04EV7 / EHVX04S23E6V(G)
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

195 %

129 %

Prated

6.00 kW

6.00 kW

SCOP

4.96

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.20 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

 

1.00

Pdh Tj = +2°C

3.70 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

1.00

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

1.00

1.00

Pdh Tj = 12°C

3.30 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

1.00

1.00

Pdh Tj = Tbiv

6.20 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.20 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.80 kW

2.00 kW

Annual energy consumption Qhe

2501 kWh

3769 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.36 kW

Cooling capacity

4.52

EER

3.32

EN 14825

+7°C/+12°C

Pdesignc

4.50 kW

SEER

5.66

Pdc Tj = 35°C

4.52 kW

EER Tj = 35°C

3.32

Pdc Tj = 30°C

3.14 kW

EER Tj = 30°C

5.11

Cdc

1.0

Pdc Tj = 25°C

2.43 kW

EER Tj = 25°C

6.69

Cdc

1.0

Pdc Tj = 20°C

2.50 kW

EER Tj = 20°C

8.24

Cdc

1.0

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

480 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.57

Heating up time

1:47 h:min

Standby power input

13.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

288 l

ERGA04EV7 / EHVH04S23E6V
General Data
Power supply
1x230V 50Hz

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

195 %

129 %

Prated

6.00 kW

6.00 kW

SCOP

4.96

3.29

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.20 kW

5.30 kW

COP Tj = -7°C

3.23

1.97

Cdh

 

1.00

Pdh Tj = +2°C

3.70 kW

3.30 kW

COP Tj = +2°C

4.94

3.23

Cdh

1.00

1.00

Pdh Tj = +7°C

3.20 kW

3.00 kW

COP Tj = +7°C

6.19

4.40

Cdh

1.00

1.00

Pdh Tj = 12°C

3.30 kW

3.30 kW

COP Tj = 12°C

7.78

6.10

Cdh

1.00

1.00

Pdh Tj = Tbiv

6.20 kW

5.30 kW

COP Tj = Tbiv

3.23

1.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

5.20 kW

4.00 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

2.56

1.37

WTOL

35 °C

55 °C

Poff

10 W

10 W

PTO

10 W

10 W

PSB

10 W

10 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electrical

Electrical

Supplementary Heater: PSUP

0.80 kW

2.00 kW

Annual energy consumption Qhe

2501 kWh

3769 kWh

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

42 dB(A)

42 dB(A)

Sound power level outdoor

58 dB(A)

58 dB(A)

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

4.36 kW

4.90 kW

El input

0.83 kW

1.85 kW

COP

5.23

2.65

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Cooling

EN 14511-2

+7°C/+12°C

El input

1.36 kW

Cooling capacity

4.52

EER

3.32

EN 14825

+7°C/+12°C

Pdesignc

4.50 kW

SEER

5.66

Pdc Tj = 35°C

4.52 kW

EER Tj = 35°C

3.32

Pdc Tj = 30°C

3.14 kW

EER Tj = 30°C

5.11

Cdc

1.0

Pdc Tj = 25°C

2.43 kW

EER Tj = 25°C

6.69

Cdc

1.0

Pdc Tj = 20°C

2.50 kW

EER Tj = 20°C

8.24

Cdc

1.0

Poff

10 W

PTO

10 W

PSB

10 W

PCK

0 W

Annual energy consumption Qce

480 kWh

Domestic Hot Water (DHW)

Average Climate

EN 16147

Declared load profile

XL

Efficiency ηDHW

104 %

COP

2.57

Heating up time

1:47 h:min

Standby power input

13.0 W

Reference hot water temperature

52.0 °C

Mixed water at 40°C

288 l