1,500 kg
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
195 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.96
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.17 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
1.00
Pdh Tj = +2°C
3.71 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
0.99
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
0.98
1.00
Pdh Tj = 12°C
3.27 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
0.98
1.00
Pdh Tj = Tbiv
6.17 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.22 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.78 kW
2.30 kW
Annual energy consumption Qhe
2501 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
195 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.96
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.17 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
1.00
Pdh Tj = +2°C
3.71 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
0.99
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
0.98
1.00
Pdh Tj = 12°C
3.27 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
0.98
1.00
Pdh Tj = Tbiv
6.17 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.22 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.78 kW
2.30 kW
Annual energy consumption Qhe
2501 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.88
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.17 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
1.00
Pdh Tj = +2°C
3.71 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
0.99
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
0.98
1.00
Pdh Tj = 12°C
3.27 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
0.98
1.00
Pdh Tj = Tbiv
6.17 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.22 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.78 kW
2.30 kW
Annual energy consumption Qhe
2538 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.88
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.17 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
1.00
Pdh Tj = +2°C
3.71 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
0.99
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
0.98
1.00
Pdh Tj = 12°C
3.27 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
0.98
1.00
Pdh Tj = Tbiv
6.17 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.22 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.78 kW
2.30 kW
Annual energy consumption Qhe
2538 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
195 %
129 %
Prated
6.00 kW
6.00 kW
SCOP
4.96
3.29
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
Pdh Tj = +2°C
3.70 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
1.00
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
1.00
1.00
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
1.00
1.00
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.20 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.80 kW
2.00 kW
Annual energy consumption Qhe
2501 kWh
3769 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
195 %
129 %
Prated
6.00 kW
6.00 kW
SCOP
4.96
3.29
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
Pdh Tj = +2°C
3.70 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
1.00
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
1.00
1.00
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
1.00
1.00
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.20 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.80 kW
2.00 kW
Annual energy consumption Qhe
2501 kWh
3769 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.88
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
Pdh Tj = +2°C
3.70 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
1.00
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
1.00
1.00
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
1.00
1.00
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.20 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.80 kW
2.00 kW
Annual energy consumption Qhe
2538 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
192 %
127 %
Prated
6.00 kW
6.00 kW
SCOP
4.88
3.26
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.20 kW
5.30 kW
COP Tj = -7°C
3.23
1.97
Cdh
1.00
Pdh Tj = +2°C
3.70 kW
3.30 kW
COP Tj = +2°C
4.94
3.23
Cdh
1.00
1.00
Pdh Tj = +7°C
3.20 kW
3.00 kW
COP Tj = +7°C
6.19
4.40
Cdh
1.00
1.00
Pdh Tj = 12°C
3.30 kW
3.30 kW
COP Tj = 12°C
7.78
6.10
Cdh
1.00
1.00
Pdh Tj = Tbiv
6.20 kW
5.30 kW
COP Tj = Tbiv
3.23
1.97
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.20 kW
4.00 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.56
1.37
WTOL
35 °C
55 °C
Poff
10 W
10 W
PTO
10 W
10 W
PSB
10 W
10 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electrical
Electrical
Supplementary Heater: PSUP
0.80 kW
2.00 kW
Annual energy consumption Qhe
2538 kWh
3806 kWh
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
39 dB(A)
39 dB(A)
Sound power level outdoor
58 dB(A)
58 dB(A)
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
4.36 kW
4.90 kW
El input
0.83 kW
1.85 kW
COP
5.23
2.65
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Domestic Hot Water (DHW)
Average Climate
EN 16147
Declared load profile
L
Efficiency ηDHW
115 %
COP
2.76
Heating up time
1:23 h:min
Standby power input
31.7 W
Reference hot water temperature
44.5 °C
Mixed water at 40°C
137 l