Certificate holders

Subtype

TTF 4.6, TTF 6.6, TTF 8.6

Certificate Holder
tecalor GmbH
Fürstenbergerstr. 77
37603 Holzminden
Germany
Registration number
011-1W0396
Certification Body
DIN CERTCO Gesellschaft für Konformitätsbewertung mbH
Subtype title
TTF 4.6, TTF 6.6, TTF 8.6
Driving energy
Electricity
Heat Pump Type
Brine/Water
Refrigerant
R454C
Mass of Refrigerant

2,200 kg

Certification Date
08.09.2020
Testing basis
n/a
Generate PDF Export model CSV
  • Number of models 3

Models

TTF 4.6 (cool) / TTC 4.6 (cool)
Configure model
Model name
TTF 4.6 (cool) / TTC 4.6 (cool)
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

1.96 kW

1.26 kW

El input

0.43 kW

0.47 kW

COP

4.60

2.73

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

38 dB(A)

38 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

187 %

147 %

Prated

4.23 kW

3.76 kW

SCOP

4.87

3.87

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

4.23 kW

3.76 kW

COP Tj = +2°C

4.86

3.43

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.71 kW

2.41 kW

COP Tj = +7°C

5.24

3.95

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.20 kW

1.08 kW

COP Tj = 12°C

5.31

4.39

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.23 kW

3.76 kW

COP Tj = Tbiv

4.86

3.43

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.23 kW

3.76 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.86

3.43

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1159 kWh

1300 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

38 dB(A)

38 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

201 %

157 %

Prated

4.23 kW

3.76 kW

SCOP

5.21

4.12

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

2.55 kW

2.27 kW

COP Tj = -7°C

5.37

4.10

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

1.55 kW

1.38 kW

COP Tj = +2°C

5.45

4.37

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.13 kW

1.09 kW

COP Tj = +7°C

5.31

4.51

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.12 kW

1.09 kW

COP Tj = 12°C

5.21

4.52

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.23 kW

3.76 kW

COP Tj = Tbiv

4.86

3.43

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.23 kW

3.76 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.86

3.43

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2000 kWh

2252 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

38 dB(A)

38 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

195 %

153 %

Prated

4.23 kW

3.76 kW

SCOP

5.07

4.02

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

3.73 kW

3.32 kW

COP Tj = -7°C

5.01

3.58

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.26 kW

2.02 kW

COP Tj = +2°C

5.38

4.22

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.45 kW

1.30 kW

COP Tj = +7°C

5.34

4.47

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.13 kW

1.08 kW

COP Tj = 12°C

5.32

4.49

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

4.23 kW

3.76 kW

COP Tj = Tbiv

4.86

3.43

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

4.23 kW

3.76 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.86

3.43

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1723 kWh

1934 kWh

TTF 6.6 (cool) / TTC 6.6 (cool)
Configure model
Model name
TTF 6.6 (cool) / TTC 6.6 (cool)
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

2.37 kW

2.01 kW

El input

0.52 kW

0.69 kW

COP

4.60

2.91

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

198 %

158 %

Prated

6.70 kW

6.05 kW

SCOP

5.14

4.14

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

6.70 kW

6.05 kW

COP Tj = +2°C

4.52

3.34

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.29 kW

3.88 kW

COP Tj = +7°C

5.19

3.97

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.90 kW

1.72 kW

COP Tj = 12°C

5.71

4.81

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

6.70 kW

6.05 kW

COP Tj = Tbiv

4.52

3.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.70 kW

6.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.52

3.34

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1741 kWh

1954 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

207 %

166 %

Prated

6.70 kW

6.05 kW

SCOP

5.38

4.34

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

4.04 kW

3.65 kW

COP Tj = -7°C

5.36

4.15

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.45 kW

2.22 kW

COP Tj = +2°C

5.64

4.68

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.57 kW

1.42 kW

COP Tj = +7°C

5.76

4.80

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.13 kW

1.10 kW

COP Tj = 12°C

5.32

4.73

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

6.70 kW

6.05 kW

COP Tj = Tbiv

4.52

3.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.70 kW

6.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.52

3.34

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3069 kWh

3439 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

41 dB(A)

41 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

200 %

160 %

Prated

6.70 kW

6.05 kW

SCOP

5.20

4.18

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

5.91 kW

5.34 kW

COP Tj = -7°C

4.71

3.55

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

3.59 kW

3.25 kW

COP Tj = +2°C

5.39

4.27

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.30 kW

2.09 kW

COP Tj = +7°C

5.60

4.76

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.14 kW

1.08 kW

COP Tj = 12°C

5.47

4.61

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

6.70 kW

6.05 kW

COP Tj = Tbiv

4.52

3.34

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

6.70 kW

6.05 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.52

3.34

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

2662 kWh

2988 kWh

TTF 8.6 (cool) / TTC 8.6 (cool)
Configure model
Model name
TTF 8.6 (cool) / TTC 8.6 (cool)
Application
Heating (medium temp)
Units
Indoor
Climate Zone
Colder Climate + Warmer Climate
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
3x400V 50Hz

Heating

EN 14511-2

Low temperature

Medium temperature

Heat output

2.78 kW

2.42 kW

El input

0.60 kW

0.79 kW

COP

4.67

3.07

EN 14511-4

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

Starting and operating test

passed

Warmer Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

157 %

Prated

7.66 kW

6.93 kW

SCOP

5.13

4.13

Tbiv

2 °C

2 °C

TOL

2 °C

2 °C

Pdh Tj = +2°C

7.66 kW

6.93 kW

COP Tj = +2°C

4.29

3.22

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

4.91 kW

4.45 kW

COP Tj = +7°C

5.09

3.88

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

2.17 kW

1.97 kW

COP Tj = 12°C

5.75

4.85

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.66 kW

6.93 kW

COP Tj = Tbiv

4.29

3.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.66 kW

6.93 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.29

3.22

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

1997 kWh

2243 kWh

Colder Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

204 %

163 %

Prated

7.66 kW

6.93 kW

SCOP

5.29

4.29

Tbiv

-22 °C

-22 °C

TOL

-22 °C

-22 °C

Pdh Tj = -7°C

4.62 kW

4.18 kW

COP Tj = -7°C

5.17

4.07

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

2.81 kW

2.54 kW

COP Tj = +2°C

5.60

4.60

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

1.80 kW

1.63 kW

COP Tj = +7°C

5.76

4.90

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.13 kW

1.09 kW

COP Tj = 12°C

5.34

4.75

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.66 kW

6.93 kW

COP Tj = Tbiv

4.29

3.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.66 kW

6.93 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.29

3.22

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3570 kWh

3985 kWh

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

40 dB(A)

40 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

197 %

158 %

Prated

7.66 kW

6.93 kW

SCOP

5.12

4.14

Tbiv

-10 °C

-10 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

6.76 kW

6.12 kW

COP Tj = -7°C

4.53

3.44

Cdh Tj = -7 °C

0.90

0.90

Pdh Tj = +2°C

4.11 kW

3.72 kW

COP Tj = +2°C

5.25

4.21

Cdh Tj = +2 °C

0.90

0.90

Pdh Tj = +7°C

2.64 kW

2.39 kW

COP Tj = +7°C

5.59

4.69

Cdh Tj = +7 °C

0.90

0.90

Pdh Tj = 12°C

1.16 kW

1.08 kW

COP Tj = 12°C

5.52

4.61

Cdh Tj = +12 °C

0.90

0.90

Pdh Tj = Tbiv

7.66 kW

6.93 kW

COP Tj = Tbiv

4.29

3.22

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

7.66 kW

6.93 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.29

3.22

WTOL

75 °C

75 °C

Poff

16 W

16 W

PTO

16 W

16 W

PSB

16 W

16 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

0.00 kW

0.00 kW

Annual energy consumption Qhe

3094 kWh

3461 kWh