2,200 kg
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.74 kW
8.49 kW
El input
2.02 kW
2.54 kW
COP
4.32
3.34
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
8.61 kW
7.92 kW
SCOP
3.87
3.20
Tbiv
-4 °C
-4 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.18 kW
5.58 kW
COP Tj = -7°C
3.18
2.28
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
7.46 kW
7.12 kW
COP Tj = +2°C
3.94
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.69 kW
8.75 kW
COP Tj = +7°C
4.66
4.18
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
10.34 kW
10.32 kW
COP Tj = 12°C
5.58
5.43
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
6.62 kW
6.09 kW
COP Tj = Tbiv
3.47
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.60 kW
5.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.04
WTOL
62 °C
62 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.01 kW
2.87 kW
Annual energy consumption Qhe
4595 kWh
5117 kWh
Heating
EN 14511-2
Low temperature
Medium temperature
Heat output
8.74 kW
8.49 kW
El input
2.02 kW
2.54 kW
COP
4.32
3.34
EN 14511-4
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
Starting and operating test
passed
Warmer Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
185 %
156 %
Prated
9.25 kW
8.92 kW
SCOP
4.71
3.98
Tbiv
4 °C
4 °C
TOL
2 °C
2 °C
Pdh Tj = +2°C
7.35 kW
6.68 kW
COP Tj = +2°C
3.68
2.52
Cdh Tj = +2 °C
1.00
1.00
Pdh Tj = +7°C
8.71 kW
8.85 kW
COP Tj = +7°C
4.50
3.59
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
10.31 kW
10.22 kW
COP Tj = 12°C
5.58
5.10
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
7.93 kW
7.64 kW
COP Tj = Tbiv
4.06
2.95
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
7.35 kW
6.68 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.68
2.95
WTOL
62 °C
62 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.90 kW
2.24 kW
Annual energy consumption Qhe
2626 kWh
2998 kWh
Colder Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
136 %
114 %
Prated
7.21 kW
6.70 kW
SCOP
3.47
2.92
Tbiv
-12 °C
-12 °C
TOL
-20 °C
-20 °C
Pdh Tj = -7°C
6.28 kW
5.85 kW
COP Tj = -7°C
3.36
2.62
Cdh Tj = -7 °C
0.99
0.99
Pdh Tj = +2°C
7.52 kW
7.28 kW
COP Tj = +2°C
4.06
3.48
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.68 kW
8.71 kW
COP Tj = +7°C
4.69
4.41
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
10.33 kW
10.37 kW
COP Tj = 12°C
5.28
5.43
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
5.31 kW
4.94 kW
COP Tj = Tbiv
2.93
2.20
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
4.73 kW
3.63 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.63
1.60
WTOL
62 °C
62 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
7.21 kW
6.70 kW
Annual energy consumption Qhe
5124 kWh
5657 kWh
Pdh Tj = -15°C (if TOL<-20°C)
4.73
4.43
COP Tj = -15°C (if TOL<-20°C)
2.63
1.96
Cdh Tj = -15 °C
1.00
1.00
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level outdoor
57 dB(A)
57 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
152 %
125 %
Prated
8.61 kW
7.92 kW
SCOP
3.87
3.20
Tbiv
-4 °C
-4 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
6.18 kW
5.58 kW
COP Tj = -7°C
3.18
2.28
Cdh Tj = -7 °C
1.00
1.00
Pdh Tj = +2°C
7.46 kW
7.12 kW
COP Tj = +2°C
3.94
3.18
Cdh Tj = +2 °C
0.99
0.99
Pdh Tj = +7°C
8.69 kW
8.75 kW
COP Tj = +7°C
4.66
4.18
Cdh Tj = +7 °C
0.99
0.99
Pdh Tj = 12°C
10.34 kW
10.32 kW
COP Tj = 12°C
5.58
5.43
Cdh Tj = +12 °C
0.99
0.99
Pdh Tj = Tbiv
6.62 kW
6.09 kW
COP Tj = Tbiv
3.47
2.56
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
5.60 kW
5.05 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
2.90
2.04
WTOL
62 °C
62 °C
Poff
15 W
15 W
PTO
15 W
15 W
PSB
15 W
15 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
3.01 kW
2.87 kW
Annual energy consumption Qhe
4595 kWh
5117 kWh