Certificate holders

Subtype

ATLANTIC GEOLIA 17

Certificate Holder
Groupe Atlantic
44 boulevard des Etats-Unis
85000 La Roche Sur Yon
France
Registration number
012-C700083 / Issue 1
Certification Body
RISE CERT
Subtype title
ATLANTIC GEOLIA 17
Driving energy
Electricity
Heat Pump Type
Brine/Water and Water/Water
Refrigerant
R410A
Mass of Refrigerant

2,300 kg

Certification Date
16.10.2020
Testing basis
HP Keymark Scheme Rules rev 8
Generate PDF Export model CSV Download certificate
  • Number of models 1

Models

ATLANTIC GEOLIA 17
Configure model
Model name
ATLANTIC GEOLIA 17
Application
Heating (medium temp)
Units
Indoor
Climate Zone
n/a
Reversibility
No
Cooling mode application (optional)
n/a
General Data
Power supply
1x230V 50Hz

Brine/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

16.63 kW

15.41 kW

El input

3.86 kW

5.50 kW

COP

4.31

2.80

Average Climate

EN 12102-1

Low temperature

Medium temperature

Sound power level indoor

55 dB(A)

55 dB(A)

EN 14825

Low temperature

Medium temperature

ηs

177 %

134 %

Prated

19.00 kW

18.00 kW

SCOP

4.63

3.55

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

17.00 kW

15.70 kW

COP Tj = -7°C

4.48

2.97

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

17.10 kW

16.30 kW

COP Tj = +2°C

4.68

3.58

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

17.20 kW

16.70 kW

COP Tj = +7°C

4.88

3.95

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

17.30 kW

17.00 kW

COP Tj = 12°C

5.08

4.32

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

17.00 kW

15.70 kW

COP Tj = Tbiv

4.48

2.97

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

16.50 kW

15.40 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

4.22

2.74

WTOL

55 °C

55 °C

Poff

2 W

2 W

PTO

90 W

90 W

PSB

3 W

3 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

2.70 kW

2.30 kW

Annual energy consumption Qhe

8604 kWh

10337 kWh

Water/Water Heat Pump

Heating

EN 14511-4

Starting and operating test

passed

Shutting off the heat transfer medium flow

passed

Complete power supply failure

passed

Defrost test

passed

EN 14511-2

Low temperature

Medium temperature

Heat output

22.13 kW

20.14 kW

El input

4.25 kW

5.69 kW

COP

5.21

3.54

Average Climate

EN 14825

Low temperature

Medium temperature

ηs

217 %

176 %

Prated

25.00 kW

23.00 kW

SCOP

5.63

4.60

Tbiv

-7 °C

-7 °C

TOL

-10 °C

-10 °C

Pdh Tj = -7°C

21.80 kW

20.20 kW

COP Tj = -7°C

5.42

3.76

Cdh Tj = -7 °C

0.990

0.990

Pdh Tj = +2°C

22.00 kW

20.80 kW

COP Tj = +2°C

5.68

4.64

Cdh Tj = +2 °C

0.990

0.990

Pdh Tj = +7°C

22.10 kW

21.20 kW

COP Tj = +7°C

5.94

5.18

Cdh Tj = +7 °C

0.990

0.990

Pdh Tj = 12°C

22.80 kW

21.60 kW

COP Tj = 12°C

6.20

5.72

Cdh Tj = +12 °C

0.990

0.990

Pdh Tj = Tbiv

21.80 kW

20.20 kW

COP Tj = Tbiv

5.42

3.76

Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh

21.70 kW

19.90 kW

COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh

5.29

3.54

WTOL

55 °C

55 °C

Poff

2 W

2 W

PTO

90 W

90 W

PSB

3 W

3 W

PCK

0 W

0 W

Supplementary Heater: Type of energy input

Electricity

Electricity

Supplementary Heater: PSUP

3.00 kW

2.90 kW

Annual energy consumption Qhe

9057 kWh

10272 kWh