1,450 kg
Brine/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
10.08 kW
kW
El input
2.48 kW
kW
COP
4.06
Average Climate
EN 12102-1
Low temperature
Medium temperature
Sound power level indoor
56 dB(A)
56 dB(A)
EN 14825
Low temperature
Medium temperature
ηs
164 %
%
Prated
12.00 kW
kW
SCOP
4.30
Tbiv
-7 °C
°C
TOL
-10 °C
°C
Pdh Tj = -7°C
10.20 kW
kW
COP Tj = -7°C
4.08
Cdh Tj = -7 °C
0.990
Pdh Tj = +2°C
10.30 kW
kW
COP Tj = +2°C
4.33
Cdh Tj = +2 °C
0.990
Pdh Tj = +7°C
10.40 kW
kW
COP Tj = +7°C
4.56
Cdh Tj = +7 °C
0.990
Pdh Tj = 12°C
10.60 kW
kW
COP Tj = 12°C
4.80
Cdh Tj = +12 °C
0.990
Pdh Tj = Tbiv
10.20 kW
kW
COP Tj = Tbiv
4.08
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
10.10 kW
kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
3.98
WTOL
50 °C
°C
Poff
2 W
W
PTO
24 W
W
PSB
4 W
W
PCK
0 W
W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.70 kW
kW
Annual energy consumption Qhe
5644 kWh
kWh
Water/Water Heat Pump
Heating
EN 14511-4
Starting and operating test
passed
Shutting off the heat transfer medium flow
passed
Complete power supply failure
passed
Defrost test
passed
EN 14511-2
Low temperature
Medium temperature
Heat output
13.38 kW
11.75 kW
El input
2.48 kW
3.52 kW
COP
5.38
3.34
Average Climate
EN 14825
Low temperature
Medium temperature
ηs
231 %
177 %
Prated
15.00 kW
14.00 kW
SCOP
5.98
4.63
Tbiv
-7 °C
-7 °C
TOL
-10 °C
-10 °C
Pdh Tj = -7°C
13.40 kW
12.40 kW
COP Tj = -7°C
5.71
3.74
Cdh Tj = -7 °C
0.990
0.990
Pdh Tj = +2°C
13.50 kW
12.80 kW
COP Tj = +2°C
6.03
4.67
Cdh Tj = +2 °C
0.990
0.990
Pdh Tj = +7°C
13.60 kW
13.00 kW
COP Tj = +7°C
6.48
5.29
Cdh Tj = +7 °C
0.990
0.990
Pdh Tj = 12°C
13.70 kW
13.30 kW
COP Tj = 12°C
6.68
5.91
Cdh Tj = +12 °C
0.990
0.990
Pdh Tj = Tbiv
13.40 kW
12.40 kW
COP Tj = Tbiv
5.71
3.74
Pdh Tj = TOL or Pdh Tj = Tdesignh if TOL < Tdesignh
13.30 kW
11.80 kW
COP Tj = TOL or COP Tj = Tdesignh if TOL < Tdesignh
5.27
3.27
WTOL
55 °C
55 °C
Poff
2 W
2 W
PTO
24 W
24 W
PSB
4 W
4 W
PCK
0 W
0 W
Supplementary Heater: Type of energy input
Electricity
Electricity
Supplementary Heater: PSUP
1.80 kW
1.80 kW
Annual energy consumption Qhe
5525 kWh
6442 kWh